ABB ACS355 machinery drive (needs FMBA-01 RS485 adapter)

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
control_word0U161
status_word3U161
speed_and_dir100I161
speed101I161
output_frequency102I160.1
current103U160.1
torque104I160.1
power105I160.1
dc_bus_voltage106U161
output_voltage108U161
drive_temp109I160.1
kwh_counter114U161
analog_input_1119I160.1
analog_input_2120I160.1
analog_output_1123U160.1
motor_temp144I161
control_board_temp149I160.1

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 03,06,08,16,23; Supports Modbus RTU protocol. EIA-485 or RS-232 interface.

⚠ According to IEC 60664 and IEC 61800-5-1, the connection of the motor thermistor to the digital input requires double or reinforced insulation. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsX1 on FMBA-01 Modbus adapter or X2 on control panel
connectorRJ-45 for RS-232, Terminal block for EIA-485
shield/groundGround the shield in the cabling between the activation switch and the control board at the control board.
max registers/read120
broadcastsupported
protocol notesParameter writes through standard Modbus are always volatile unless saved with parameter 1607 PARAM SAVE.
power1-phase 200...240 V AC, 3-phase 200...240 V AC, or 3-phase 380...480 V AC
environmentEnclosure degree of protection: IP20
certificationsCE, C-UL US, RoHS, TÜV NORD, C-Tick
doc revision3AUA0000066143 Rev E, EFFECTIVE: 2020-11-02
field reports — community-sourced, unverified (checked 2026-06-11)
  • Users frequently encounter off-by-one addressing errors when using standard Modbus libraries (such as ArduinoModbus or Unitronics) because the drive's documentation lists 1-based register addresses (e.g., 40101 for Speed/Direction), whereas protocol-layer clients require 0-based offsets (e.g., 100). [source]
  • If the RS-485 communication lines (A and B) are swapped, the drive's EFB OK MESSAGES parameter (5306) will not increment, while EFB CRC ERRORS (5307) and EFB UART ERRORS (5308) will continuously increase. [source]
  • confirmed: doc_revision: 3AUA0000066143 Rev E, EFFECTIVE: 2020-11-02 — confirmed by ABB Library document index [1.1.1]
  • confirmed: comms.baud_rates: [1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200] — confirmed by parameter 5202 (BAUD RATE) in the ACS355 User's Manual
  • confirmed: comms.default_baud: 9600 — confirmed by parameter 5202 default setting of 9.6 kb/s
  • confirmed: comms.default_unit_id: 1 — confirmed by parameter 5201 (STATION ID) default setting of 1
  • confirmed: comms.framing: ['RTU'] — confirmed by FMBA-01 Modbus Adapter Module User's Manual stating it supports RTU protocol only
  • confirmed: comms.function_codes: [3, 6, 8, 16, 23] — confirmed by the 'Function Codes' section in the ACS355 User's Manual
  • confirmed: comms.parity: 'N' and stop_bits: 1 — confirmed by parameter 5203 (PARITY) default setting of '8 NONE 1'
  • confirmed: facts.certifications: 'CE, C-UL US, RoHS, TÜV NORD, C-Tick' — confirmed by the ABB and Baldor Drives Catalog

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.