device library

ABB AquaMaster 3 flowmeter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
flow_rate5016F32BE1User flow units
flow_percent5018F32BE1%
pressure5024F32BE1User units
pressure_percent5026F32BE1%
left_electrode_impedance5028F32BE1kOhm
right_electrode_impedance5030F32BE1kOhm
coil_current5038F32BE1A
pulse_output_frequency5040F32BE1Hz
calibrated_velocity5050F32BE1m/s
voltage_reference5056F32BE1V
sig_a_volts5062F32BE1V
sig_b_volts5064F32BE1V
external_power_voltage5068F32BE1V
internal_3v8_voltage5070F32BE1V
internal_3v2_voltage5072F32BE1V
totaliser_forward12002U32BE1
totaliser_reverse12004U32BE1
totaliser_net12006U32BE1
totaliser_tariff_a12008U32BE1
totaliser_tariff_b12010U32BE1
external_power_status1020U161
internal_power_status1022U161

link settings as documented (unverified): RTU; FC 01,02,03,04,05,06,15,16; AquaMaster 3 RS485 MODBUS option implements the MODBUS over Serial Line protocol. Low power mode after 10s inactivity requires 1 retry to wake up within 1s.

bench facts as documented (unverified)
connectorRS485
wiring notesRS485 MODBUS option
response timeout1000 ms
protocol notesTurnaround delay: 800ms. Low power state after 10s inactivity requires 1 retry to wake up.
identification notesTransmitterUniqueID at RO 32-Bit register 4013
powerDesigned for low power consumption so that it can be used with battery or renewable energy supplies (as well as with mains power).
certificationsUKAS Calibration Laboratory No. 0255
doc revisionCOI/FET2XX/MOD/TBL–EN
firmware applicabilityWAJC2103 v01.00.00 or above
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: framing: RTU — confirmed by ABB AquaMaster 3 MODBUS Tables Supplement (COI/FET2XX/MOD/TBL-EN) stating it follows Modbus Over Serial Line V1.02 using 2-wire RS485
  • confirmed: function_codes: [1, 2, 3, 4, 5, 6, 15, 16] — confirmed by ABB AquaMaster 3 MODBUS Tables Supplement (COI/FET2XX/MOD/TBL-EN) register mapping table
  • confirmed: low power mode after 10s inactivity requires 1 retry to wake up within 1s — confirmed by ABB AquaMaster 3 MODBUS Tables Supplement (COI/FET2XX/MOD/TBL-EN) section 1.1
  • confirmed: certifications: UKAS Calibration Laboratory No. 0255 — confirmed by ABB AquaMaster 3 User Guide (OI/FET2XX-EN)
  • confirmed: doc_revision: COI/FET2XX/MOD/TBL–EN — confirmed by ABB AquaMaster 3 MODBUS Tables Supplement (COI/FET2XX/MOD/TBL-EN)
  • confirmed: firmware_applicability: WAJC2103 v01.00.00 or above — confirmed by ABB AquaMaster 3 MODBUS Tables Supplement (COI/FET2XX/MOD/TBL-EN)
  • confirmed: TransmitterUniqueID at RO 32-Bit register 4013 — confirmed by ABB AquaMaster 3 MODBUS Tables Supplement (COI/FET2XX/MOD/TBL-EN) which lists TransmitterUniqueID at 1-based address 4013 (0-based 4012)
  • confirmed: physical: RS485 — confirmed by ABB AquaMaster 3 User Guide (OI/FET2XX-EN)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.