ABB PSTX soft starter (built-in Modbus RTU)

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
fbt_return_value512U161
programmable_analog_input_1513U161
programmable_analog_input_2514U161
programmable_analog_input_3515U161
programmable_analog_input_4516U161
programmable_analog_input_5517U161
programmable_analog_input_6518U161
programmable_analog_input_7519U161
programmable_analog_input_8520U161
programmable_analog_input_9521U161
programmable_analog_input_10522U161
fbt_control_word768U161
fbt_argument_2769U161
fbt_argument_3770U161

link settings as documented (unverified): RTU; FC 01,04,15,16; Requires setting parameters: FB interface connector to Modbus RTU, Fieldbus control to On, Com3 function to Modbus RTU slave.

⚠ The motor may start unexpectedly if there is a start signal present when doing any of the actions listed below: Switching from one type of control to another (fieldbus control/hardwire control), Reset all Settings — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsCom3
connectorFB interface connector
wiring notesUses RS485 / Modbus RTU
doc revision1SFC132089M0201 July 2014
field reports — community-sourced, unverified (checked 2026-06-11)
  • By default, if no Modbus RTU message is received by the PSTX softstarter for more than 100ms, it will trip on fieldbus communication failure protection (P1E00) and stop the motor. In multi-slave networks where polling cycles exceed 100ms, this causes frequent trips unless parameter 19.4 (Fieldbus failure op) is set to 'Off'. [source]
  • confirmed: comms framing [RTU] and function codes — confirmed by ABB PSTX Built-in Modbus RTU Manual (1SFC132089M0201)
  • confirmed: comms notes regarding parameter settings (FB interface connector, Fieldbus control, Com3 function) — confirmed by ABB PSTX Built-in Modbus RTU Manual (1SFC132089M0201)
  • confirmed: control_warning regarding unexpected motor start when switching control types or resetting settings — confirmed by ABB PSTX Built-in Modbus RTU Manual (1SFC132089M0201)
  • confirmed: physical connector (FB interface connector), terminals (Com3), and RS485 physical interface — confirmed by ABB PSTX Built-in Modbus RTU Manual (1SFC132089M0201)
  • confirmed: register map addresses (fbt_return_value @ 512/0200h, programmable_analog_input_1-10 @ 513-522/0201h-020Ah, fbt_control_word @ 768/0300h, fbt_argument_2 @ 769/0301h, fbt_argument_3 @ 770/0302h) — confirmed by ABB PSTX Built-in Modbus RTU Manual (1SFC132089M0201)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.