Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Name | 99 | U16 | 1 | |
| Manufacturer | 116 | U16 | 1 | |
| Modbus table version | 121 | I16 | 1 | |
| Firmware version | 122 | U16 | 1 | |
| Platform type | 139 | U16 | 1 | |
| Station serial number | 156 | U16 | 1 | |
| Date year | 167 | I16 | 1 | yr |
| Date month | 168 | I16 | 1 | month |
| Date day | 169 | I16 | 1 | day |
| Time hour | 170 | I16 | 1 | hr |
| Time minute | 171 | I16 | 1 | min |
| Time second | 172 | I16 | 1 | s |
| Uptime | 173 | U64LE | 0.001 | s |
| Time zone | 177 | I16 | 1 | min |
| Meter state | 299 | U16 | 1 | |
| Meter last value timestamp | 300 | U64LE | 0.001 | s |
| Meter type | 304 | U16 | 1 | |
| Voltage Phase V (L1-N) | 305 | F32LE | 1 | V |
| Voltage Phase V (L2-N) | 307 | F32LE | 1 | V |
| Voltage Phase V(L3-N) | 309 | F32LE | 1 | V |
| Voltage Phase V(L1-L2) | 311 | F32LE | 1 | V |
| Voltage Phase V(L2-L3) | 313 | F32LE | 1 | V |
| Voltage Phase V(L3-L1) | 315 | F32LE | 1 | V |
| Current N | 317 | F32LE | 1 | A |
| Current Phase L1 | 319 | F32LE | 1 | A |
| Current Phase L2 | 321 | F32LE | 1 | A |
| Current Phase L3 | 323 | F32LE | 1 | A |
| Current Sum | 325 | F32LE | 1 | A |
| Power Factor Phase L1 | 327 | F32LE | 1 | |
| Power Factor Phase L2 | 329 | F32LE | 1 | |
| Power Factor Phase L3 | 331 | F32LE | 1 | |
| Power Factor Sum | 333 | F32LE | 1 | |
| Frequency | 335 | F32LE | 1 | Hz |
| Real Power Phase L1 | 337 | F32LE | 1 | W |
| Real Power Phase L2 | 339 | F32LE | 1 | W |
| Real Power Phase L3 | 341 | F32LE | 1 | W |
| Real Power Sum | 343 | F32LE | 1 | W |
| Apparent Power Phase L1 | 345 | F32LE | 1 | VA |
| Apparent Power Phase L2 | 347 | F32LE | 1 | VA |
| Apparent Power Phase L3 | 349 | F32LE | 1 | VA |
| Apparent Power Sum | 351 | F32LE | 1 | VA |
| Reactive Power Phase L1 | 353 | F32LE | 1 | VAr |
| Reactive Power Phase L2 | 355 | F32LE | 1 | VAr |
| Reactive Power Phase L3 | 357 | F32LE | 1 | VAr |
| Reactive Power Sum | 359 | F32LE | 1 | VAr |
| Real Energy Delivered Phase L1 | 361 | F64LE | 1 | Wh |
| Real Energy Delivered Phase L2 | 365 | F64LE | 1 | Wh |
| Real Energy Delivered Phase L3 | 369 | F64LE | 1 | Wh |
| Real Energy Delivered Sum | 373 | F64LE | 1 | Wh |
| Real Energy Consumed Phase L1 | 377 | F64LE | 1 | Wh |
| Real Energy Consumed Phase L2 | 381 | F64LE | 1 | Wh |
| Real Energy Consumed Phase L3 | 385 | F64LE | 1 | Wh |
| Real Energy Consumed Sum | 389 | F64LE | 1 | Wh |
| Apparent Energy Phase L1 | 393 | F64LE | 1 | VAh |
| Apparent Energy Phase L2 | 397 | F64LE | 1 | VAh |
| Apparent Energy Phase L3 | 401 | F64LE | 1 | VAh |
| Apparent Energy Sum | 405 | F64LE | 1 | VAh |
| Reactive Energy Phase L1 | 409 | F64LE | 1 | VArh |
| Reactive Energy Phase L2 | 413 | F64LE | 1 | VArh |
| Reactive Energy Phase L3 | 417 | F64LE | 1 | VArh |
| Reactive Energy Sum | 421 | F64LE | 1 | VArh |
| Station Active Max Current | 1099 | F32LE | 1 | A |
| Temperature | 1101 | F32LE | 1 | °C |
| OCPP state | 1103 | U16 | 1 | |
| Number of sockets | 1104 | U16 | 1 | |
| Availability | 1199 | U16 | 1 | |
| Mode 3 state | 1200 | U16 | 1 | |
| Actual Applied Max Current | 1205 | F32LE | 1 | A |
| Modbus Server Max Current valid time | 1207 | U32LE | 1 | s |
| Modbus Server Max Current | 1209 | F32LE | 1 | A |
| Active Load Balancing Safe Current | 1211 | F32LE | 1 | A |
| Modbus Server received setpoint accounted for | 1213 | U16 | 1 | |
| Charge using 1 or 3 phases | 1214 | U16 | 1 | |
| SCN name | 1399 | U16 | 1 | |
| SCN Sockets | 1403 | U16 | 1 | |
| SCN Total Consumption Phase L1 | 1404 | F32LE | 1 | A |
| SCN Total Consumption Phase L2 | 1406 | F32LE | 1 | A |
| SCN Total Consumption Phase L3 | 1408 | F32LE | 1 | A |
| SCN Actual Max Current Phase L1 | 1410 | F32LE | 1 | A |
| SCN Actual Max Current Phase L2 | 1412 | F32LE | 1 | A |
| SCN Actual Max Current Phase L3 | 1414 | F32LE | 1 | A |
| SCN Max Current for each Phase L1 | 1416 | F32LE | 1 | A |
| SCN Max Current for each Phase L2 | 1418 | F32LE | 1 | A |
| SCN Max Current for each Phase L3 | 1420 | F32LE | 1 | A |
| Remaining valid time Max Current Phase L | 1422 | U32LE | 1 | s |
| Remaining valid time Max Current Phase L2 | 1424 | U32LE | 1 | s |
| Remaining valid time Max Current Phase L3 | 1426 | U32LE | 1 | s |
| SCN Safe current | 1428 | F32LE | 1 | A |
| SCN Modbus Server Max Current enable | 1430 | U16 | 1 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.