Allen-Bradley PowerFlex 4/40/4M drive (DSI Modbus)

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Output Freq1U160.1Hz
Commanded Freq2U160.1Hz
Output Current3U160.01A
Output Voltage4U160.1VAC
DC Bus Voltage5U161VDC
Drive Status6U161
Fault 1 Code7U161
Fault 2 Code8U161
Fault 3 Code9U161
Process Display10U32BE0.01
Control Source12U161
Contrl In Status13U161
Dig In Status14U161
Comm Status15U161
Control SW Ver16U160.01
Drive Type17U161
Elapsed Run Time18U1610Hrs
Testpoint Data19U161
Analog In 0-10V20U160.1%
Analog In 4-20mA21U160.1%
Drive Temp22U161degC
Motor NP Volts101U161VAC
Motor NP Hertz102U161Hz
Motor OL Current103U160.1A
Minimum Freq104U160.1Hz
Maximum Freq105U161Hz
Start Source106U161
Stop Mode107U161
Speed Reference108U161
Accel Time 1109U160.1Secs
Decel Time 1110U160.1Secs
Motor OL Ret111U161
Reset To Defalts112U161
Digital In1 Sel201U161
Digital In2 Sel202U161
Anlg In 0-10V Lo211U160.1%
Anlg In 0-10V Hi212U160.1%
Anlg In4-20mA Lo213U160.1%
Anlg In4-20mA Hi214U160.1%
Relay Out Sel221U161
Relay Out Level222U32BE0.1
Language301U161
Comm Data Rate302U161
Comm Node Addr303U161
Comm Loss Action304U161
Comm Loss Time305U160.1Secs
Comm Format306U161
Comm Write Mode307U161
Accel Time 2401U160.1Secs
Decel Time 2402U160.1Secs
S Curve %403U161%
Jog Frequency404U160.1Hz
Jog Accel/Decel405U160.1Secs
Internal Freq409U160.1Hz
Preset Freq 0410U160.1Hz
Preset Freq 1411U160.1Hz
Preset Freq 2412U160.1Hz
Preset Freq 3413U160.1Hz
Skip Frequency418U161Hz
Skip Freq Band419U160.1Hz
DC Brake Time424U160.1Secs
DC Brake Level425U160.1A
DB Resistor Sel427U161
DB Duty Cycle428U161%
Start At PowerUp433U161
Reverse Disable434U161
Flying Start En435U161
Compensation436U161
Slip Hertz @ FLA437U160.1Hz
Process Time Lo438U160.01
Process Time Hi439U160.01
Process Factor440U160.1
Bus Reg Mode441U161
Current Limit442U160.1A
Motor OL Select444U161
PWM Frequency446U160.1kHz
SW Current Trip448U160.1A
Fault Clear450U161
Auto Rstrt Tries451U161
Auto Rstrt Delay452U160.1Secs
Boost Select453U161
Maximum Voltage457U161VAC
Program Lock458U161
Testpoint Sel459U161
Motor NP FLA461U160.1A
Logic Command8192U161
Reference8193U160.1Hz
Logic Status8448U161
Drive Error Codes8449U161
Feedback8451U160.1Hz

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 100; FC 03,06,16; Power to drive must be cycled before any changes will affect drive operation. Supported formats include RTU 8-N-1, 8-E-1, 8-O-1, 8-N-2, 8-E-2, and 8-O-2.

⚠ Risk of equipment damage exists if writing parameter data to Non-Volatile Storage (NVS) frequently. NVS will quickly exceed its life cycle. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsControl Terminal 16, RJ45 DSI port pins 4 and 5
A/B polarityTxRxD+, TxRxD-
termination120 ohm resistor at each end of the network cable
connectorRJ45
isolationNetwork Common is internally tied to I/O Terminal 04 (Digital Common)
shield/groundThe shield should be grounded at ONLY ONE location.
wiring notesOnly pins 4 and 5 on the RJ45 plug should be wired.
protocol notesModbus devices can be 0-based or 1-based. Register addresses may need to be offset by +1 depending on the master.
identification notesTo access drive parameters, the Modbus register address equals the parameter number.
power120V AC 1-Phase, 240V AC 1-Phase, 240V AC 3-Phase, 480V AC 3-Phase
environmentAmbient Operating Temperature: -10°C to 40°C (0 mm clearance) or 50°C (25 mm clearance). Storage: -40°C to +85°C, 0% to 95% RH non-condensing.
certificationsUL, CE
doc revisionPublication 22F-UM001D-EN-E
firmware applicabilityFRN 1.xx - 2.xx
field reports — community-sourced, unverified (checked 2026-06-11)
  • Standard RJ45 Ethernet cables should not be plugged directly into the DSI port without isolating pins, as other pins (such as pins carrying power for HIM modules) can cause communication issues or hardware damage if connected to standard RS-485 transceivers. Only pins 4 and 5 should be wired for Modbus RTU. [source]
  • confirmed: comms.default_baud: 9600 — confirmed by PowerFlex 4M User Manual (Publication 22F-UM001E-EN-E) parameter C302 [Comm Data Rate] default
  • confirmed: comms.default_unit_id: 100 — confirmed by PowerFlex 4M User Manual parameter C303 [Comm Node Addr] default
  • confirmed: physical.connector: RJ45 — confirmed by manual and application notes describing the DSI port
  • confirmed: physical.notes: Only pins 4 and 5 on the RJ45 plug should be wired — confirmed by field guides and forum discussions identifying Pin 4 as TxRxD+ (Data+) and Pin 5 as TxRxD- (Data-)
  • confirmed: quirks.notes: Modbus devices can be 0-based or 1-based — confirmed by Rockwell Publication 2080-UM002H-EN-E noting that register addresses may need to be offset by +1 depending on the master

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.