ASCO 5140 connectivity module

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

cross-referenced (demoted: under-extracted stub (<=3 regs); needs re-extraction (#52))

Imported from a third-party source and NOT verified by us — not even structure-checked. An unverified claim, shown so you can find the device; trust it no more than the source it came from.

pointaddress (0-based)typescaleunit
line_to_line_voltage_ab16U161V

link settings as documented (unverified): TCP; Modbus/TCP is always enabled. Default TCP port is 10001. Default IP address is 169.254.1.1.

bench facts as documented (unverified)
terminalsPower terminal plug provided
connectorRJ-45
wiring notesDIN mount vertical. Ports: 2 (yellow stripe) for ASCO devices, 4 (blue stripe) for Ethernet. Dimensions: 4" x 5" x 2" (4 cm, 11 cm, 10 cm)
protocol notesThe Modbus register map is the same as that of the downstream device. The 5140 QEM maps the Modbus data using the downstream device address.
power24 V dc, 1.7 W
environment-4° F to 158° F (-20° C to +70° C)
doc revision381333-417 D

⚠ disputed: Modbus/TCP is always enabled — disputed by newer manual revision 381333-459 D, which states that Modbus/TCP is default disabled and must be manually enabled [3.4.2]

⚠ disputed: Default TCP port is 10001 — disputed by newer manual revision 381333-459 D, which states that TCP Port 1 defaults to 502 for Modbus/TCP, while Port 2 defaults to 10001 for ASCOBusII/TCP

field reports — community-sourced, unverified (checked 2026-06-11)
  • The manual contains a metric conversion typo for dimensions: '4” x 5” x 2” (4 cm, 11 cm, 10 cm)' where 4 inches is incorrectly converted to 4 cm, and 2 inches is incorrectly converted to 10 cm. [source]
  • In newer firmware versions (documented in manual 381333-459 D), Modbus/TCP is disabled by default and must be manually enabled, and the default port changes to 502. [source]
  • confirmed: Modbus/TCP is always enabled in revision D — confirmed by ASCO 5140 Installation Manual 381333-417 D [1.4.1]
  • confirmed: Default TCP port is 10001 in revision D — confirmed by ASCO 5140 Installation Manual 381333-417 D
  • confirmed: Default IP address is 169.254.1.1 — confirmed by ASCO 5140 Installation Manual 381333-417 D and Schneider Electric support
  • confirmed: Power requirements are 24 V dc, 1.7 W — confirmed by ASCO 5140 Installation Manual 381333-417 D
  • confirmed: Dimensions are listed as 4" x 5" x 2" (4 cm, 11 cm, 10 cm) — confirmed by ASCO 5140 Installation Manual 381333-417 D
  • confirmed: The Modbus register map is the same as that of the downstream device — confirmed by ASCO 5140 Installation Manual 381333-417 D
  • confirmed: line_to_line_voltage_ab is at 0-based address 16 (1-based 40017) — confirmed by ASCO 5140 Installation Manual 381333-417 D

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.