Belimo UK24MOD MP-to-Modbus gateway

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Series number 4th part0U161
Actuator type1U161
Time monitoring2U161s
Min / Vmin setting3U160.01%
Max / Vmax setting4U160.01%
Errors / Malfunctions5U161
Sensor type6U161
Current sensor value7U161
Series number 1st part8U161
Series number 2nd part9U161
Series number 4th part10U161
Actuator type11U161
Time monitoring12U161s
Min13U160.01%
Max14U160.01%
Absolute volumetric flow15U161
Nominal volumetric flow16U161
Modbus baud rate (V1.06 and older)160U16100
Modbus address (V1.06 and older)161U161
Response delay (V1.06 and older)162U161ms
Firmware Version (V1.06 and older)163U161
Modbus baud rate1000U16100
Modbus address1001U161
Response delay1002U161ms
Firmware Version1003U161

link settings as documented (unverified): RTU; baud 9600/19200/38400/76800; FC 03,06; Baud rate, parity, and termination are adjustable via DIP switches. Parity can be NONE (2 stop bits) or EVEN (1 stop bit).

⚠ Due to safety considerations, the only override values permitted in the case of actuators for fire dampers are Open (1) and Fast_closed (6). The operating position (Open) must also be repeated within 120 seconds (recommendation: 90 sec.). — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsPlug-screw terminal, 3-pin (Modbus RTU and MP-Bus), 2-pin (Supply)
A/B polarityD-, D+ ┴
termination150 , adjustable via DIP switch
connectorPlug-screw terminal
isolationThe GND of the RS485 line is galvanically isolated from the MP-Bus GND.
wiring notesAll terminals suitable for 2 x 1.5 mm2. Tool connector is RJ12.
response timeout2 ms
sentinel values65535 is entered for absolute/relative volumetric flow if the actuator type does not support it.
protocol notesThe response delay of the device is set to a fixed 4 ms with 9600 Bd. A delay of 2 ms is used as a default with higher baud rates. Adjustable via register 1003 (2...100 ms).
serial registerMP[n] + 9, MP[n] + 10, MP[n] + 11
firmware register1004
identification notesService registers 1001-1004 (former 161-164) provide service information.
powerAC 24V, 50/60 Hz / DC 24V (Power supply range: AC / DC 21.6…26.4 V), 3 VA
environmentAmbient temperature: 0…+40° C, Protection class: III Safety extra-low voltage
certificationsCE pursuant to 2004/108/EC
doc revisionv1.11 • 12.2016
firmware applicabilityV1.08
field reports — community-sourced, unverified (checked 2026-06-11)
  • In firmware versions V1.07 and older, Modbus telegrams longer than 20 Bytes (e.g., Read Holding Registers with more than 8 registers) cause wrong register entries. This was fixed in firmware V1.08. [source]
  • confirmed: Baud rates [9600, 19200, 38400, 76800] and Modbus RTU framing — confirmed by Belimo UK24MOD Datasheet
  • confirmed: Modbus function codes 3 and 6 — confirmed by Belimo UK24MOD Datasheet
  • confirmed: DIP switch configuration for baud rate, parity, and termination — confirmed by Belimo UK24MOD Datasheet
  • confirmed: CE certification pursuant to 2004/108/EC — confirmed by Belimo UK24MOD Datasheet
  • confirmed: Safety override control warning for fire damper actuators — confirmed by Belimo UK24MOD Datasheet
  • confirmed: Document revision v1.11 • 12.2016 — confirmed by Belimo UK24MOD Datasheet
  • confirmed: Ambient temperature 0…+40° C and Protection class III — confirmed by Belimo UK24MOD Datasheet
  • confirmed: Firmware applicability V1.08 — confirmed by Belimo UK24MOD Datasheet

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.