Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
Setpoint99I160.01%
Actual Value100I160.01%
Control Word101U161
Status Word102U161
Serial Control Word109U161
Serial Setpoint110I160.01%
Number of active alarms11099U161
Number of listed alarms that has not yet been cleared11100U161
Highest state of any listed alarm11101U161
Highest severity level of any active alarm11102U161
If locked, ICP is waiting for external reset command or restart11103U161
Reset level required to clear any active alarm11104U161
Code of highest ranked alarm11200U161
Code of second highest ranked alarm11201U161
AlarmStatus.Alarm311202U161
AlarmStatus.Alarm411203U161
AlarmStatus.Alarm511204U161
AlarmStatus.Alarm611205U161
AlarmStatus.Alarm711206U161
AlarmStatus.Alarm811207U161
AlarmStatus.Alarm911208U161
AlarmStatus.Alarm1011209U161
Suction Pressure12000I160.01bar(a)
Discharge Pressure12001I160.01bar(a)
Evaporating Temperature (SST)12002I160.1°C
Condensing Temperature (SDT)12003I160.1°C
Envelope Status12004U161
Envelope Zone12005U161
Discharge temperature12009I160.1°C
AUX temperature12010I160.1°C
High Pressure Switch12021U161
Crank Case Oil Heater12022U161
Oil Sensor 112024U161
Oil Sensor 212025U161
Motor start is requested12026U161
Head cooling fan12027U161
Liquid injection cooling valve12028U161
Compressor start unloading valve12029U161
Capacity control valve CR-112030U161
Capacity control valve CR-212031U161
Capacity control valve CR-312032U161
Motor overheat thermistor resistance (PTC)13000U161Ohm
Estimated motor power consumption13001U160.1kW
Motor drive frequency (speed)13002U160.1Hz
Motor start contactor 113005U161
Motor start contactor 213006U161
System operating state13999U161
Control Output Current15149I160.01A
State of the Operation LED15989U161
State of the Warning LED15990U161
State of the Fault LED15991U161
State of the Communication LED15992U161
Year20099U161
Month and Day20100U161
Hour and Minute20101U161
Millisecond20102U161ms
Serial Control Source20299U161
Serial Control Timeout Function20300U161
Serial Control Timeout Time20301U161s
Refrigerant selection22099U161
Dedicated OEM functionality selection22199U161
Mains supply voltage specification (single phase)22299U161V
Device Operating Hours29999U32LE1h
Compressor Running Hours30009U32LE1h
Compressor Start Count30011U32LE1
Power Up Count30019U32LE1
Compressor type selection42099U161
COM1 Address65408U161
COM1 Baudrate65409U161
COM1 Stop Bits65410U161
COM1 Parity65411U161

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.