Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| PVN1 | 0 | F32BE | 1 | |
| ID | 0 | U16 | 1 | |
| Module Status | 1 | U16 | 1 | |
| PVN2 | 2 | F32BE | 1 | |
| M1-M3 Status | 2 | U16 | 1 | |
| M4-M6 Status | 3 | U16 | 1 | |
| PVN3 | 4 | F32BE | 1 | |
| SystemSwitch | 4 | U16 | 1 | |
| DI1 Status | 5 | U16 | 1 | |
| PVN4 | 6 | F32BE | 1 | |
| DI2 Status | 6 | U16 | 1 | |
| Reserved | 7 | U16 | 1 | |
| PVN5 | 8 | F32BE | 1 | |
| DO1 | 8 | U16 | 1 | |
| DO2 | 9 | U16 | 1 | |
| PVN6 | 10 | F32BE | 1 | |
| AO1 | 10 | F32BE | 1 | mA |
| PVN7 | 12 | F32BE | 1 | |
| AO2 | 12 | F32BE | 1 | mA |
| PVN8 | 14 | F32BE | 1 | |
| DI1Frequency | 14 | F32BE | 1 | Hz |
| PVN9 | 16 | F32BE | 1 | |
| DI1Flow | 16 | F32BE | 1 | L/min |
| PVN10 | 18 | F32BE | 1 | |
| DI1TotA | 18 | F32BE | 1 | L |
| PVN11 | 20 | F32BE | 1 | |
| DI1TotB | 20 | F32BE | 1 | L |
| PVN12 | 22 | F32BE | 1 | |
| DI2Frequency | 22 | F32BE | 1 | Hz |
| PVN13 | 24 | F32BE | 1 | |
| DI2Flow | 24 | F32BE | 1 | L/min |
| PVN14 | 26 | F32BE | 1 | |
| DI2TotA | 26 | F32BE | 1 | L |
| PVN15 | 28 | F32BE | 1 | |
| DI2TotB | 28 | F32BE | 1 | L |
| PVN16 | 30 | F32BE | 1 | |
| Reserved | 30 | F32BE | 1 | |
| PVN17 | 32 | F32BE | 1 | |
| M1 ID | 32 | U16 | 1 | |
| M1 Module Status | 33 | U16 | 1 | |
| PVN18 | 34 | F32BE | 1 | |
| M1 Reserved | 34 | U16 | 1 | |
| M1 Reserved | 35 | U16 | 1 | |
| PVN19 | 36 | F32BE | 1 | |
| M1 Reserved | 36 | U16 | 1 | |
| M1 Reserved | 37 | U16 | 1 | |
| PVN20 | 38 | F32BE | 1 | |
| PVC ID | 512 | U16 | 1 | |
| PVC1 Status | 513 | U16 | 1 | |
| PVC1 Value | 514 | F32BE | 1 | |
| PVC2 Status | 516 | U16 | 1 | |
| PVC2 Value | 517 | F32BE | 1 | |
| PVC3 Status | 519 | U16 | 1 | |
| PVC3 Value | 520 | F32BE | 1 | |
| PVC4 Status | 522 | U16 | 1 | |
| PVC4 Value | 523 | F32BE | 1 | |
| PVC5 Status | 525 | U16 | 1 | |
| PVC5 Value | 526 | F32BE | 1 | |
| PVC6 Status | 528 | U16 | 1 | |
| PVC6 Value | 529 | F32BE | 1 | |
| PVC7 Status | 531 | U16 | 1 | |
| PVC7 Value | 532 | F32BE | 1 | |
| PVC8 Status | 534 | U16 | 1 | |
| PVC8 Value | 535 | F32BE | 1 | |
| PVC9 Status | 537 | U16 | 1 | |
| PVC9 Value | 538 | F32BE | 1 | |
| PVC10 Status | 540 | U16 | 1 | |
| PVC10 Value | 541 | F32BE | 1 | |
| PVC11 Status | 543 | U16 | 1 | |
| PVC11 Value | 544 | F32BE | 1 | |
| PVC12 Status | 546 | U16 | 1 | |
| PVC12 Value | 547 | F32BE | 1 |
| wiring notes | The data exchange between the device Type 8619 and the other equipment of the network is only possible 25 s after the device start. |
| protocol notes | The device Type 8619 stores and sends the values of all variables in 'big-endian' format. |
| identification notes | Identity object (EtherNet/IP) lists Product Code 8619, Vendor ID 87, Product Name multiCELL. |
| doc revision | Supplement to Operating Instructions 2204/03_EU-ML 00569043 / Original_EN |
| firmware applicability | from software version B.02.00 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.