Cla-Val electronic valve controller

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Analog Input Modbus Override6U161
Digital Input Modbus Override7U161
Digital Input DI1999U161
Digital Input DI21000U161
Digital Input DI31001U161
Digital Input DI41002U161
Digital Input DI51003U161
Digital Input DI61004U161
Digital Output SO11005U161
Digital Output SO21006U161
Digital Output RO11007U161
Digital Output RO21008U161
AI12999I32BE0.01
AI23001I32BE0.01
AI33003I32BE0.01
AI43005I32BE0.01
AI53007I32BE0.01
AI63009I32BE0.01
AO13035I32BE0.01
AO23037I32BE0.01
AO33039I32BE0.01
AO43041I32BE0.01
field reports — community-sourced, unverified (checked 2026-06-11)
  • In R-Engine version 2.2.0, when remote backup of the ValvApps to an FTP server (or Link2Valves server) is enabled, the active PID process could get corrupted during the backup process. [source]
  • In R-Engine versions prior to 2.9.2, downloading a new R-Engine version via L2V (Link2Valves) could cause the device to get stuck in an infinite restart loop. [source]
  • In R-Engine versions prior to 2.5.0, log export on USB was broken (bug introduced in version 2.4.0). [source]
  • In older R-Engine versions, a device restart was required after switching between Modbus tables. [source]
  • confirmed: di1 @ 999, di2 @ 1000, di3 @ 1001, di4 @ 1002, di5 @ 1003, di6 @ 1004 — confirmed by Cla-Val VC-22D / D22 Modbus Registers Table (registers 41000 to 41005, 1-based)
  • confirmed: so1 @ 1005, so2 @ 1006, ro1 @ 1007, ro2 @ 1008 — confirmed by Cla-Val VC-22D / D22 Modbus Registers Table (registers 41006 to 41009, 1-based)
  • confirmed: ai1 @ 2999, ai2 @ 3001, ai3 @ 3003, ai4 @ 3005, ai5 @ 3007, ai6 @ 3009 — confirmed by Cla-Val VC-22D / D22 Modbus Registers Table (registers 43000 to 43011, 1-based, 32-bit values)
  • confirmed: ao1 @ 3035, ao2 @ 3037, ao3 @ 3039, ao4 @ 3041 — confirmed by Cla-Val VC-22D / D22 Modbus Registers Table (registers 43036 to 43043, 1-based, 32-bit values)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.