Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
total_yield22U32BE1kWh
daily_yield24U160.1kWh
efficiency25U160.001%
power_factor26I160.001
p_max27U160.1kW
run_time28U160.1Min
active_power29U160.1kW
apparent_power30U160.1kVA
grid_voltage_uab31U160.1V
grid_voltage_ubc32U160.1V
grid_voltage_uca33U160.1V
grid_current_ia34U160.1A
grid_current_ib35U160.1A
grid_current_ic36U160.1A
pv_voltage_137U160.1V
pv_current_138I160.1A
pv_voltage_239U160.1V
pv_current_240I160.1A
pv_voltage_341U160.1V
pv_current_342I160.1A
grid_frequency43U160.1Hz
heatsink_temperature44I160.1C
ambient_temperature45I160.1C
work_mode47U161
reactive_power59I160.1kvar
pv_input_total_power69U160.1kW
on_off4096U161
p_set4097U160.001%
pf_set4098I160.001
q_set4099I160.1%

link settings as documented (unverified): RTU; FC 03,04,06,16; Modbus RTU protocol. Data bits: 8, Parity: None, Stop bits: 1.

bench facts as documented (unverified)
wiring notesRS485 interface
protocol notesUnused or unsupported data points set to 'Not Implemented' values (int8: 0x80, uint8: 0xFF, int16: 0x8000, uint16: 0xFFFF, int32: 0x80000000, uint32: 0xFFFFFFFF, string: 0x00)
model register0x000A
serial register0x0006
firmware register0x0005
identification notesModel register is string20 at 0x000A. Serial number is uint64 BCD at 0x0006. MinorVer is at 0x0005, MajorVer is at 0x0041.
power60kW
doc revision0.04
firmware applicabilityV11.00
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Modbus RTU framing, 8 data bits, no parity, 1 stop bit — confirmed by CPS Inverter Model Data Mapping Specification For 403X [8.2.5]
  • confirmed: Unused or unsupported data points set to 'Not Implemented' values (int8: 0x80, uint8: 0xFF, int16: 0x8000, uint16: 0xFFFF, int32: 0x80000000, uint32: 0xFFFFFFFF, string: 0x00) — confirmed by CPS Inverter Model Data Mapping Specification For 403X
  • confirmed: Identification registers: MinorVer at 0x0005, SN at 0x0006, Model at 0x000A, and MajorVer at 0x0041 — confirmed by CPS Inverter Model Data Mapping Specification For 403X
  • confirmed: Telemetry registers: daily_yield @ 24 (0x0018), efficiency @ 25 (0x0019), power_factor @ 26 (0x001A), grid_voltage_uab @ 31 (0x001F), pv_voltage_1 @ 37 (0x0025), grid_frequency @ 43 (0x002B), heatsink_temperature @ 44 (0x002C), ambient_temperature @ 45 (0x002D), work_mode @ 47 (0x002F), reactive_power @ 59 (0x003B) — confirmed by CPS Inverter Model Data Mapping Specification For 403X
  • confirmed: Control registers: on_off @ 4096 (0x1000), p_set @ 4097 (0x1001), pf_set @ 4098 (0x1002), q_set @ 4099 (0x1003) — confirmed by CPS Inverter Model Data Mapping Specification For 403X

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.