device library

Crompton Integra 1530/1560/1580 metering system

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
volts_10F32BE1min
volts_22F32BE1V
volts_34F32BE1V
current_16F32BE1A
current_28F32BE1A
current_310F32BE1A
w_phase_112F32BE1W
w_phase_214F32BE1W
w_phase_316F32BE1W
va_phase_118F32BE1VA
va_phase_220F32BE1VA
va_phase_322F32BE1VA
var_phase_124F32BE1var
var_phase_226F32BE1var
var_phase_328F32BE1var
power_factor_phase_130F32BE1
power_factor_phase_232F32BE1
power_factor_phase_334F32BE1
phase_angle_phase_136F32BE1deg
phase_angle_phase_238F32BE1deg
phase_angle_phase_340F32BE1deg
volts_ave42F32BE1V
current_ave46F32BE1A
current_sum48F32BE1A
watts_sum52F32BE1W
va_sum56F32BE1VA
var_sum60F32BE1var
power_factor_ave62F32BE1
average_phase_angle66F32BE1deg
frequency70F32BE1Hz
wh_import72F32BE1Wh
wh_export74F32BE1Wh
varh_import76F32BE1varh
varh_export78F32BE1varh
vah80F32BE1VAh
w_demand_import84F32BE1W
w_max_demand_import86F32BE1W
a_demand104F32BE1A
a_max_demand106F32BE1A
v_l1_l2200F32BE1V
v_l2_l3202F32BE1V
v_l3_l1204F32BE1V
average_line_to_line_volts206F32BE1V
neutral_current224F32BE1A
thd_volts_1234F32BE1%
thd_volts_2236F32BE1%
thd_volts_3238F32BE1%
thd_current_1240F32BE1%
thd_current_2242F32BE1%
thd_current_3244F32BE1%
thd_voltage_mean248F32BE1%
thd_current_mean250F32BE1%
power_factor_ind_cap254F32BE1

link settings as documented (unverified): RTU; baud 2400/4800/9600/19200; FC 03,04,16; Broadcast mode (address 0) is not supported. Stop bits can be 1 or 2 depending on parity configuration.

bench facts as documented (unverified)
terminals2-wire RS485, via 3 screw terminals
A/B polarityAll 'A' and 'B' connections are daisy chained together.
terminationThe cable should be terminated at each end with a 120 ohm (0.25 Watt min.) resistor.
connector3 screw terminals
shield/groundThe screens should also be connected to the 'Gnd' terminal.
wiring notesTypically 22 gauge Belden 8761 or equivalent.
max registers/read80
response timeout150 ms
broadcastnot supported
protocol notesEach request for data must be restricted to 40 parameters or less (80 registers). Exceeding this limit will cause a Modbus exception code.
identification notesRegister Order parameter at holding register 40041 can be used to detect/set floating point byte order.
doc revisionIssue 1 Jan 2006
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Baud rates [2400, 4800, 9600, 19200] and framing [RTU] — confirmed by the Integra 1530 Installation Manual
  • confirmed: Parity N, stop bits 1 or 2 depending on parity configuration — confirmed by the Integra 1530 Installation Manual
  • confirmed: Function codes 3, 4, 16 — confirmed by the Integra 1530 Installation Manual
  • confirmed: Broadcast mode (address 0) is not supported — confirmed by the Integra 1530 Installation Manual
  • confirmed: Register Order parameter at holding register 40041 can be used to detect/set floating point byte order — confirmed by the Integra 1530 Installation Manual
  • confirmed: Physical connector: 2-wire RS485 via 3 screw terminals, using twisted pair screened cable (Typically 22 gauge Belden 8761 or equivalent) — confirmed by the Integra 1530 Installation Manual
  • confirmed: Polarity: All 'A' and 'B' connections are daisy chained together — confirmed by the Integra 1530 Installation Manual
  • confirmed: Shield ground: The screens should also be connected to the 'Gnd' terminal — confirmed by the Integra 1530 Installation Manual

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.