CyberPower RMCARD205/305 UPS card

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Bypass voltage Phase A0U160.1V
Bypass voltage Phase A1U160.1V
Bypass voltage Phase B2U160.1V
Bypass voltage Phase C3U160.1V
Bypass current Phase A4U160.1A
Bypass current Phase B5U160.1A
Bypass current Phase C6U160.1A
Bypass frequency Phase A7U160.01Hz
Bypass frequency Phase B8U160.01Hz
Bypass frequency Phase C9U160.01Hz
Bypass PF Phase A10U160.01
Bypass PF Phase B11U160.01
Bypass PF Phase C12U160.01
Input voltage Phase A13U160.1V
Input voltage Phase B14U160.1V
Input voltage Phase C15U160.1V
Input current Phase A16U160.1A
Input current Phase B17U160.1A
Input current Phase C18U160.1A
Input frequency Phase A19U160.01Hz
Input frequency Phase B20U160.01Hz
Input frequency Phase C21U160.01Hz
Input PF Phase A22U160.01
Input PF Phase B23U160.01
Input PF Phase C24U160.01
Output voltage Phase A25U160.1V
Output voltage Phase B26U160.1V
Output voltage Phase C27U160.1V
Output current Phase A28U160.1A
Output current Phase B29U160.1A
Output current Phase C30U160.1A
Output frequency Phase A31U160.01Hz
Output frequency Phase B32U160.01Hz
Output frequency Phase C33U160.01Hz
Output PF Phase A34U160.01
Output PF Phase B35U160.01
Output PF Phase C36U160.01
Output apparent power Phase A37U160.1kVA
Output apparent power Phase B38U160.1kVA
Output apparent power Phase C39U160.1kVA
Output active power Phase A40U160.1kW
Output active power Phase B41U160.1kW
Output active power Phase C42U160.1kW
Output reactive power Phase A43U160.1kVar
Output reactive power Phase B44U160.1kVar
Output reactive power Phase C45U160.1kVar
Load percent Phase A46U160.1%
Load percent Phase B47U160.1%
Load percent Phase C48U160.1%
Environment temperature49U161℃
Battery voltage positive50U160.1V
Battery voltage negative51U160.1V
Battery current positive52I160.1A
Battery current negative53I160.1A
Battery temperature54U160.1℃
Battery remain time55U161min
Battery capacity56U161%
Load On Source81U161
Battery Status82U161
Battery Connect Status83U161
EPO85U161
Invertor Ready Capacity86U161
Generator Input87U161
Input Fail88U161
Bypass Sequence Fail89U161
Bypass Voltage Fail90U161
Bypass Fail91U161
Bypass Over Load92U161
Bypass Over Load Timeout93U161
Bypass Untrack94U161
Output Shorted96U161
Battery EOD97U161
Battery Test Result99U161
Battery Maintain Result101U161
Manual Tx Bypass106U161
Battery Volt Low107U161
Lost N+X Redundant112U161
Sensor status116U161
First Module Online Flag Bit119U161
Second Module Online Flag Bit120U161
Operation Mode301U161
Battery Quantity in a String311U161
UPS Max Capacity322U161kVA
Output Voltage327U161V
Output Frequency328U161Hz
UPS Model Name427U161
Current Module Number2000U161
Main Input Voltage Phase A2001U160.1V
Main Input Voltage Phase B2002U160.1V
Main Input Voltage Phase C2003U160.1V
Main Input Current Phase A2004U160.1A
Main Input Current Phase B2005U160.1A
Main Input Current Phase C2006U160.1A
Main Input Frequency Phase A2007U160.01Hz
Main Input Frequency Phase B2008U160.01Hz
Main Input Frequency Phase C2009U160.01Hz
Input PF Phase A2010U160.01
Input PF Phase B2011U160.01
Input PF Phase C2012U160.01
Positive Battery String Voltage2015U160.1V
Negative Battery String Voltage2016U160.1V
Positive Charger Current2019U160.1A
Negative Charger Current2020U160.1A
Positive Discharge Current2021U160.1A
Negative Discharge Current2022U160.1A
Output Current Phase A2026U160.1V
Output Current Phase B2027U160.1V
Output Current Phase C2028U160.1V
Output Frequency Phase A2029U160.01A
Output Frequency Phase B2030U160.01A
Output Frequency Phase C2031U160.01A
Output PF Phase A2032U160.01
Output PF Phase B2033U160.01
Output PF Phase C2034U160.01
Output Voltage Phase A2035U160.1V
Output Voltage Phase B2036U160.1V
Output Voltage Phase C2037U160.1V
Bypass Voltage Phase A2038U160.1V
Bypass Voltage Phase B2039U160.1V
Bypass Voltage Phase C2040U160.1V
Output Apparent Power Phase A2041U160.1kVA
Output Apparent Power Phase B2042U160.1kVA
Output Apparent Power Phase C2043U160.1kVA
Output Active Power Phase A2044U160.1kW
Output Active Power Phase B2045U160.1kW
Output Active Power Phase C2046U160.1kW
Output Reactive Power Phase A2047U160.1kVar
Output Reactive Power Phase B2048U160.1kVar
Output Reactive Power Phase C2049U160.1kVar
Output Load Percentage Phase A2050U160.1%
Output Load Percentage Phase B2051U160.1%
Output Load Percentage Phase C2052U160.1%
Module 1 Comprehensive Alarm3071U161
Module 1 Comprehensive Alarm3072U161

link settings as documented (unverified): TCP/RTU; unit ID 255; FC 03,16; Port TCP/502. Unit ID can be any value, recommended 0xFF or 0x00.

bench facts as documented (unverified)
model register427
field reports — community-sourced, unverified (checked 2026-06-11)
  • Some module alarms may be incorrectly triggered when a Bypass Voltage Detect Fail occurs on the Three-Phase Modular UPS (resolved in firmware v1.6.0). [source]
  • confirmed: Port TCP/502, Unit ID can be any value, recommended 0xFF or 0x00 — confirmed by CyberPower RMCARD205 Remote Management Card User Manual [1.4.3]
  • confirmed: UPS Model Name at register 427~439 — confirmed by CyberPower RMCARD205 Modbus TCP Register Map for 3-Phase UPS
  • confirmed: Bypass voltage Phase A at register 0, Phase B at register 2, Phase C at register 3 — confirmed by CyberPower RMCARD205 Modbus TCP Register Map for 3-Phase UPS

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.