Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| active_setpoint | 2 | I16 | 0.1 | °F |
| actual_capacity | 10 | U16 | 0.1 | % |
| actual_rpm_comp_1 | 246 | U16 | 1 | RPM |
| actual_rpm_comp_2 | 250 | U16 | 1 | RPM |
| capacity_limit_output | 42 | U16 | 0.1 | % |
| capacity_limit_setpoint | 3 | U16 | 0.1 | % |
| chiller_mode_output | 147 | U16 | 1 | |
| chiller_mode_setpoint | 145 | U16 | 1 | |
| chiller_power | 244 | U16 | 1 | kW |
| chiller_status | 146 | U16 | 1 | |
| compressor_2_active_capacity_limit | 107 | U16 | 1 | % |
| compressor_2_vfd_speed | 99 | U16 | 1 | % |
| compressor_select_current | 26 | U16 | 1 | A |
| compressor_2_current | 95 | U16 | 1 | A |
| compressor_select_discharge_temp | 19 | I16 | 0.1 | °F |
| compressor_2_discharge_temp | 91 | I16 | 0.1 | °F |
| compressor_select_percent_rla | 25 | U16 | 0.1 | % |
| compressor_2_percent_rla | 94 | U16 | 0.1 | % |
| compressor_select_power | 27 | U16 | 1 | kW |
| compressor_2_power | 96 | U16 | 1 | kW |
| compressor_select_run_hours | 174 | U16 | 10 | hours |
| compressor_2_run_hours | 235 | U16 | 10 | hours |
| compressor_select | 160 | U16 | 1 | |
| compressor_select_starts | 173 | U16 | 1 | starts |
| compressor_2_starts | 234 | U16 | 1 | starts |
| compressor_select_status | 172 | U16 | 1 | |
| compressor_2_status | 233 | U16 | 1 | |
| compressor_select_suction_temp | 15 | I16 | 0.1 | °F |
| compressor_2_suction_temp | 88 | I16 | 0.1 | °F |
| compressor_select_voltage | 29 | U16 | 1 | VAC |
| compressor_2_voltage | 98 | U16 | 1 | VAC |
| condenser_entering_water_temp | 7 | I16 | 0.1 | |
| condenser_leaving_water_temp | 8 | I16 | 0.1 | °F |
| condenser_select_pump_run_hours | 176 | U16 | 10 | hours |
| condenser_pump_2_run_hours | 232 | U16 | 10 | hours |
| condenser_select_refrigerant_pressure | 21 | I16 | 0.1 | psi |
| condenser_2_refrigerant_pressure | 93 | I16 | 0.1 | psi |
| condenser_select_saturated_refrigerant_temp | 20 | I16 | 0.1 | °F |
| condenser_2_saturated_refrigerant_temp | 92 | I16 | 0.1 | °F |
| condenser_water_flow_rate | 24 | U16 | 1 | GPM |
| cool_setpoint | 1 | I16 | 0.1 | °F |
| evaporator_entering_water_temp | 4 | I16 | 0.1 | °F |
| evaporator_leaving_water_temp_unit | 6 | I16 | 0.1 | |
| evaporator_select_refrigerant_pressure | 17 | I16 | 0.1 | psi |
| evaporator_2_refrigerant_pressure | 90 | I16 | 0.1 | psi |
| evaporator_select_saturated_refrigerant_temp | 16 | I16 | 0.1 | °F |
| evaporator_2_saturated_refrigerant_temp | 89 | I16 | 0.1 | °F |
| evaporator_water_flow_rate | 18 | U16 | 1 | GPM |
| heat_recovery_entering_water_temp | 22 | I16 | 0.1 | °F |
| heat_recovery_leaving_water_temp | 23 | I16 | 0.1 | °F |
| heat_setpoint | 5 | I16 | 0.1 | °F |
| ice_setpoint | 50 | I16 | 0.1 | °F |
| outdoor_air_temperature | 39 | I16 | 0.1 | °F |
| wiring notes | Requires Modbus Communication Module (IM 743) installed. |
| identification notes | Software part number is available via the Modbus integration tools. |
| certifications | Products manufactured in an ISO Certified Facility. |
| doc revision | ED 15063-7 |
| firmware applicability | MicroTech II Chiller Unit Controller |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.