device library

Daikin Applied MicroTech II chiller controller

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
active_setpoint2I160.1°F
actual_capacity10U160.1%
actual_rpm_comp_1246U161RPM
actual_rpm_comp_2250U161RPM
capacity_limit_output42U160.1%
capacity_limit_setpoint3U160.1%
chiller_mode_output147U161
chiller_mode_setpoint145U161
chiller_power244U161kW
chiller_status146U161
compressor_2_active_capacity_limit107U161%
compressor_2_vfd_speed99U161%
compressor_select_current26U161A
compressor_2_current95U161A
compressor_select_discharge_temp19I160.1°F
compressor_2_discharge_temp91I160.1°F
compressor_select_percent_rla25U160.1%
compressor_2_percent_rla94U160.1%
compressor_select_power27U161kW
compressor_2_power96U161kW
compressor_select_run_hours174U1610hours
compressor_2_run_hours235U1610hours
compressor_select160U161
compressor_select_starts173U161starts
compressor_2_starts234U161starts
compressor_select_status172U161
compressor_2_status233U161
compressor_select_suction_temp15I160.1°F
compressor_2_suction_temp88I160.1°F
compressor_select_voltage29U161VAC
compressor_2_voltage98U161VAC
condenser_entering_water_temp7I160.1
condenser_leaving_water_temp8I160.1°F
condenser_select_pump_run_hours176U1610hours
condenser_pump_2_run_hours232U1610hours
condenser_select_refrigerant_pressure21I160.1psi
condenser_2_refrigerant_pressure93I160.1psi
condenser_select_saturated_refrigerant_temp20I160.1°F
condenser_2_saturated_refrigerant_temp92I160.1°F
condenser_water_flow_rate24U161GPM
cool_setpoint1I160.1°F
evaporator_entering_water_temp4I160.1°F
evaporator_leaving_water_temp_unit6I160.1
evaporator_select_refrigerant_pressure17I160.1psi
evaporator_2_refrigerant_pressure90I160.1psi
evaporator_select_saturated_refrigerant_temp16I160.1°F
evaporator_2_saturated_refrigerant_temp89I160.1°F
evaporator_water_flow_rate18U161GPM
heat_recovery_entering_water_temp22I160.1°F
heat_recovery_leaving_water_temp23I160.1°F
heat_setpoint5I160.1°F
ice_setpoint50I160.1°F
outdoor_air_temperature39I160.1°F

link settings as documented (unverified): RTU; FC 01,02,03,04,05,06,15,16; Supports RTU mode only. Uses 8 data bits, 1 or 2 stop bits, and no parity. Baud rates from 1200 to 19200 bps.

bench facts as documented (unverified)
wiring notesRequires Modbus Communication Module (IM 743) installed.
identification notesSoftware part number is available via the Modbus integration tools.
certificationsProducts manufactured in an ISO Certified Facility.
doc revisionED 15063-7
firmware applicabilityMicroTech II Chiller Unit Controller
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Supports RTU mode only, uses 8 data bits, 1 or 2 stop bits, and no parity — confirmed by Sales and Engineering Data Sheet ED 15063-7
  • confirmed: Requires Modbus Communication Module (IM 743) installed — confirmed by Sales and Engineering Data Sheet ED 15063-7 and IM 743-6
  • confirmed: active_setpoint @ 2, actual_capacity @ 10, capacity_limit_output @ 42, capacity_limit_setpoint @ 3, chiller_mode_output @ 147, chiller_mode_setpoint @ 145, chiller_status @ 146 — confirmed by Sales and Engineering Data Sheet ED 15063-7
  • confirmed: compressor_select @ 160 (Holding Register 40161) — confirmed by Sales and Engineering Data Sheet ED 15063-7
  • confirmed: compressor_2_active_capacity_limit @ 107, compressor_2_vfd_speed @ 99 — confirmed by Sales and Engineering Data Sheet ED 15063-7

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.