Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Chiller Local/Remote | 0 | U16 | 1 | |
| Chiller Enable Output | 1 | U16 | 1 | |
| Run Enabled | 2 | U16 | 1 | |
| Chiller Capacity Limited | 3 | U16 | 1 | |
| Alarm Digital Output | 4 | U16 | 1 | |
| Evaporator Flow Switch Status | 5 | U16 | 1 | |
| Condenser Flow Switch Status | 6 | U16 | 1 | |
| Chiller ON/OFF | 7 | U16 | 1 | |
| Chiller Enable Setpoint | 8 | U16 | 1 | |
| Clear Alarms - Network | 9 | U16 | 1 | |
| Chiller Mode Output | 10 | U16 | 1 | |
| Active Setpoint | 11 | I16 | 0.1 | F/C |
| Actual Capacity | 12 | U16 | 0.1 | % |
| Active Capacity Limit Output | 13 | U16 | 0.1 | % |
| Chiller Status (Chiller Run Mode) | 14 | U16 | 1 | |
| Evaporator Entering Fluid Temperature | 15 | I16 | 0.1 | F/C |
| Evaporator Leaving Fluid Temperature | 16 | I16 | 0.1 | F/C |
| Evaporator Fluid Flow Rate | 17 | U16 | 1 | GPM/L/S |
| Condenser Entering Fluid Temperature | 18 | I16 | 0.1 | F/C |
| Condenser Leaving Fluid Temperature | 19 | I16 | 0.1 | F/C |
| Condenser Fluid Flow Rate | 20 | U16 | 1 | GPM/L/S |
| Outdoor Air Temperature | 23 | I16 | 0.1 | F/C |
| Chiller Current | 24 | U16 | 1 | Amps |
| Total Kilowatts | 26 | U16 | 1 | kW |
| Warning Alarm Index | 27 | U16 | 1 | |
| Problem Alarm Index | 28 | U16 | 1 | |
| Fault Alarm Index | 29 | U16 | 1 | |
| Warning Alarm Code | 30 | U16 | 1 | |
| Problem Alarm Code | 31 | U16 | 1 | |
| Fault Alarm Code | 32 | U16 | 1 | |
| Chiller Mode Setpoint - Network | 33 | U16 | 1 | |
| Cool Setpoint - Network | 34 | I16 | 0.1 | F/C |
| Ice Setpoint - Network | 35 | I16 | 0.1 | F/C |
| Capacity Limit Setpoint - Network | 37 | U16 | 0.1 | % |
| Circuit 1 Condenser Refrigerant Pressure | 38 | U16 | 0.1 | psi/kPa |
| Circuit 1 Condenser Saturated Refrigerant Temperature | 39 | I16 | 0.1 | F/C |
| Circuit 1 Evaporator Refrigerant Pressure | 40 | I16 | 0.1 | psi/kPa |
| Circuit 1 Evaporator Saturated Refrigerant Temperature | 41 | I16 | 0.1 | F/C |
| Circuit 2 Condenser Refrigerant Pressure | 42 | U16 | 0.1 | psi/kPa |
| Circuit 2 Condenser Saturated Refrigerant Temperature | 43 | I16 | 0.1 | F/C |
| Circuit 2 Evaporator Refrigerant Pressure | 44 | I16 | 0.1 | psi/kPa |
| Circuit 2 Evaporator Saturated Refrigerant Temperature | 45 | I16 | 0.1 | F/C |
| Circuit 3 Condenser Refrigerant Pressure | 46 | U16 | 0.1 | psi/kPa |
| Circuit 3 Condenser Saturated Refrigerant Temperature | 47 | I16 | 0.1 | F/C |
| Circuit 3 Evaporator Refrigerant Pressure | 48 | I16 | 0.1 | psi/kPa |
| Circuit 3 Evaporator Saturated Refrigerant Temperature | 49 | I16 | 0.1 | F/C |
| Circuit 4 Condenser Refrigerant Pressure | 50 | U16 | 0.1 | psi/kPa |
| Circuit 4 Condenser Saturated Refrigerant Temperature | 51 | I16 | 0.1 | F/C |
| Circuit 4 Evaporator Refrigerant Pressure | 52 | I16 | 0.1 | psi/kPa |
| Circuit 4 Evaporator Saturated Refrigerant Temperature | 53 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 1 Suction Refrigerant Pressure | 62 | U16 | 0.1 | Psi/kPa |
| Circuit 1 Compressor 1 Suction Refrigerant Temp | 64 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 1 Discharge Refrigerant Pressure | 65 | U16 | 0.1 | Psi/kPa |
| Circuit 1 Compressor 1 Discharge Refrigerant Temp | 67 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 1 Percent RLA | 68 | U16 | 1 | % |
| Circuit 1 Compressor 1 Current | 69 | U16 | 1 | Amps |
| Circuit 1 Compressor 1 Voltage | 70 | U16 | 1 | VAC |
| Circuit 1 Compressor 1 Power | 71 | U16 | 1 | kW |
| Circuit 1 Compressor 1 Starts | 72 | U16 | 1 | starts |
| Circuit 1 Compressor 1 Run Hours | 73 | U32BE | 1 | hours |
| Circuit 1 Compressor 2 Suction Refrigerant Pressure | 75 | U16 | 0.1 | Psi/kPa |
| Circuit 1 Compressor 2 Discharge Refrigerant Pressure | 78 | U16 | 0.1 | Psi/kPa |
| Circuit 1 Compressor 2 Percent RLA | 81 | U16 | 1 | % |
| Circuit 1 Compressor 2 Starts | 85 | U16 | 1 | starts |
| Circuit 1 Compressor 2 Run Hours | 86 | U32BE | 1 | hours |
| Circuit 1 Compressor 3 Starts | 98 | U16 | 1 | starts |
| Circuit 1 Compressor 3 Run Hours | 99 | U32BE | 1 | hours |
| Circuit 2 Compressor 1 Suction Refrigerant Temperature | 103 | I16 | 0.1 | F/C |
| Circuit 2 Compressor 1 Discharge Refrigerant Temp | 106 | I16 | 0.1 | F/C |
| Circuit 2 Compressor 1 Percent RLA | 107 | U16 | 1 | % |
| Circuit 2 Compressor 1 Current | 108 | U16 | 1 | amps |
| Circuit 2 Compressor 1 Voltage | 109 | U16 | 1 | VAC |
| Circuit 2 Compressor 1 Power | 110 | U16 | 1 | kW |
| Circuit 2 Compressor 1 Starts | 111 | U16 | 1 | starts |
| Circuit 2 Compressor 1 Run Hours | 112 | U32BE | 1 | hours |
| Circuit 2 Compressor 2 Starts | 124 | U16 | 1 | starts |
| Circuit 2 Compressor 2 Run Hours | 125 | U32BE | 1 | hours |
| Circuit 2 Compressor 3 Starts | 137 | U16 | 1 | starts |
| Circuit 2 Compressor 3 Run Hours | 138 | U32BE | 1 | hours |
| Circuit 3 Compressor 1 Suction Refrigerant Temperature | 142 | I16 | 0.1 | F/C |
| Circuit 3 Compressor 1 Discharge Refrigerant Temp | 145 | I16 | 0.1 | F/C |
| Circuit 3 Compressor 1 Percent RLA | 146 | U16 | 1 | % |
| Circuit 3 Compressor 1 Current | 147 | U16 | 1 | amps |
| Circuit 3 Compressor 1 Voltage | 148 | U16 | 1 | VAC |
| Circuit 3 Compressor 1 Power | 149 | U16 | 1 | kW |
| Circuit 3 Compressor 1 Starts | 150 | U16 | 1 | starts |
| Circuit 3 Compressor 1 Run Hours | 151 | U32BE | 1 | hours |
| Circuit 4 Compressor 1 Suction Refrigerant Temperature | 181 | I16 | 0.1 | F/C |
| Circuit 4 Compressor 1 Discharge Refrigerant Temp | 184 | I16 | 0.1 | F/C |
| Circuit 4 Compressor 1 Starts | 189 | U16 | 1 | starts |
| Circuit 4 Compressor 1 Run Hours | 190 | U32BE | 1 | hours |
| Condenser Pump 1 Run Hours | 296 | U32BE | 1 | Hrs |
| Condenser Pump 1 Status | 298 | U16 | 1 | |
| Condenser Pump 2 Run Hours | 299 | U32BE | 1 | Hrs |
| Condenser Pump 2 Status | 301 | U16 | 1 | |
| Evaporator Pump 1 Run Hours | 302 | U32BE | 1 | hours |
| Evaporator Pump 1 Status | 304 | U16 | 1 | |
| Evaporator Pump 2 Run Hours | 305 | U32BE | 1 | hours |
| Evaporator Pump 2 Status | 307 | U16 | 1 | |
| Year | 308 | U16 | 1 | |
| Month | 309 | U16 | 1 | |
| Date | 310 | U16 | 1 | |
| Day of Week | 311 | U16 | 1 | |
| Hour | 312 | U16 | 1 | |
| Minute | 313 | U16 | 1 | |
| Second | 314 | U16 | 1 | |
| Units | 315 | U16 | 1 | |
| Chiller Model | 316 | U16 | 1 | |
| Chiller Location | 317 | U16 | 1 | |
| Application Software Version | 333 | U16 | 1 | |
| Evaporator Entering Water Temperature Sensor Failure | 365 | U16 | 1 | |
| Bad Setpoint Override Input | 376 | U16 | 1 | |
| Bad Demand Limit Input | 377 | U16 | 1 | |
| RESTART DELAYED - Power Loss While Running Circuit 1 | 383 | U16 | 1 | |
| RESTART DELAYED - Power Loss While Running Circuit 2 | 384 | U16 | 1 | |
| RESTART DELAYED - Power Loss While Running Circuit 3 | 385 | U16 | 1 | |
| RESTART DELAYED - Power Loss While Running Circuit 4 | 386 | U16 | 1 | |
| START INHIBITED - Ambient Temperature Low | 387 | U16 | 1 | |
| INHIBIT LOAD - Condenser Pressure High Circuit 1 | 389 | U16 | 1 | |
| INHIBIT LOAD - Condenser Pressure High Circuit 2 | 390 | U16 | 1 | |
| INHIBIT LOAD - Condenser Pressure High Circuit 3 | 391 | U16 | 1 | |
| INHIBIT LOAD - Condenser Pressure High Circuit 4 | 392 | U16 | 1 | |
| UNLOAD - Condenser Pressure High Circuit 1 | 394 | U16 | 1 | |
| UNLOAD - Condenser Pressure High Circuit 2 | 395 | U16 | 1 | |
| UNLOAD - Condenser Pressure High Circuit 3 | 396 | U16 | 1 | |
| UNLOAD - Condenser Pressure High Circuit 4 | 397 | U16 | 1 | |
| Unit Low Source Temp Warning | 398 | U16 | 1 | |
| INHIBIT LOAD - Evaporator Pressure Low Circuit 1 | 410 | U16 | 1 | |
| INHIBIT LOAD - Evaporator Pressure Low Circuit 2 | 411 | U16 | 1 | |
| INHIBIT LOAD - Evaporator Pressure Low Circuit 3 | 412 | U16 | 1 | |
| INHIBIT LOAD - Evaporator Pressure Low Circuit 4 | 413 | U16 | 1 | |
| UNLOAD - Evaporator Pressure Low Circuit 1 | 415 | U16 | 1 | |
| UNLOAD - Evaporator Pressure Low Circuit 2 | 416 | U16 | 1 | |
| UNLOAD - Evaporator Pressure Low Circuit 3 | 417 | U16 | 1 | |
| UNLOAD - Evaporator Pressure Low Circuit 4 | 418 | U16 | 1 | |
| UNLOAD - Compressor Motor Current High Circuit 1, Comp 1 | 419 | U16 | 1 | |
| UNLOAD - Compressor Motor Current High Circuit 2, Comp 1 | 421 | U16 | 1 | |
| UNLOAD - Compressor Motor Current High Circuit 3, Comp 1 | 423 | U16 | 1 | |
| COMP SHUTDOWN - Low Pressure Ratio Circuit 1, Comp 1 | 439 | U16 | 1 | |
| COMP SHUTDOWN - Low Pressure Ratio Circuit 2, Comp 1 | 441 | U16 | 1 | |
| COMP SHUTDOWN - Low Pressure Ratio Circuit 3, Comp 1 | 443 | U16 | 1 | |
| COMP SHUTDOWN - Low Pressure Ratio Circuit 4, Comp 1 | 444 | U16 | 1 | |
| UNIT SHUTDOWN - Outside Air Temp Sensor Fault | 445 | U16 | 1 | |
| COMPRESSOR SHUTDOWN - Current Overload Trip Circuit 1, Comp 1 | 446 | U16 | 1 | |
| COMPRESSOR SHUTDOWN - Current Overload Trip Circuit 2, Comp 1 | 448 | U16 | 1 | |
| COMPRESSOR SHUTDOWN - Current Overload Trip Circuit 3, Comp 1 | 450 | U16 | 1 | |
| COMP SHUTDOWN - Motor Protector Trip Circuit 1 Comp 1 | 465 | U16 | 1 | |
| COMP SHUTDOWN - Motor Protector Trip Circuit 2 Comp 1 | 467 | U16 | 1 | |
| COMP SHUTDOWN - Motor Temp High Circuit 1, Comp 1 | 477 | U16 | 1 | |
| COMP SHUTDOWN - Motor Temp High Circuit 2, Comp 1 | 479 | U16 | 1 | |
| COMP SHUTDOWN - Motor Temp High Circuit 3, Comp 1 | 481 | U16 | 1 | |
| COMP SHUTDOWN - Motor Temp High Circuit 4, Comp 1 | 482 | U16 | 1 | |
| CIRCUIT SHUTDOWN - Condenser Pressure Sensor Circuit 1 Fault | 508 | U16 | 1 | |
| CIRCUIT SHUTDOWN - Condenser Pressure Sensor Circuit 2 Fault | 510 | U16 | 1 | |
| COMP SHUTDOWN - Condenser Pressure Sensor Fault Circuit 3, Comp 1 | 512 | U16 | 1 | |
| COMP SHUTDOWN - Condenser Pressure Sensor Fault Circuit 4, Comp 1 | 513 | U16 | 1 | |
| CIRCUIT SHUTDOWN - Condenser Pressure High Trip Circuit 1 Fault | 516 | U16 | 1 | |
| CIRCUIT SHUTDOWN - Condenser Pressure High Trip Circuit 2 Fault | 518 | U16 | 1 | |
| COMP SHUTDOWN - Condenser Pressure High Circuit 3, Comp 1 | 520 | U16 | 1 | |
| COMP SHUTDOWN - Condenser Pressure High Circuit 4, Comp 1 | 521 | U16 | 1 | |
| COMP SHUTDOWN - Discharge Temp Sensor Fault Circuit 1, Comp 1 | 528 | U16 | 1 | |
| COMP SHUTDOWN - Discharge Temp Sensor Fault Circuit 2, Comp 1 | 530 | U16 | 1 | |
| COMP SHUTDOWN - Discharge Temp Sensor Fault Circuit 3, Comp 1 | 532 | U16 | 1 | |
| COMP SHUTDOWN - Discharge Temp Sensor Fault Circuit 4, Comp 1 | 533 | U16 | 1 | |
| COMP SHUTDOWN - Discharge Temp High Circuit 1, Comp 1 | 534 | U16 | 1 | |
| COMP SHUTDOWN - Discharge Temp High Circuit 2, Comp 1 | 536 | U16 | 1 | |
| COMP SHUTDOWN - Discharge Temp High Circuit 3, Comp 1 | 538 | U16 | 1 | |
| COMP SHUTDOWN - Discharge Temp High Circuit 4, Comp 1 | 539 | U16 | 1 | |
| UNIT SHUTDOWN - Evaporator Water Flow Loss | 541 | U16 | 1 | |
| UNIT SHUTDOWN - Evaporator LWT or EWT Low (Freeze) | 542 | U16 | 1 | |
| CIRCUIT SHUTDOWN - Low Evaporator Pressure Trip Circuit 1 Fault | 544 | U16 | 1 | |
| CIRCUIT SHUTDOWN - Low Evaporator Pressure Trip Circuit 2 Fault | 546 | U16 | 1 | |
| COMP SHUTDOWN - Evaporator Pressure Low Circuit 3, Comp 1 | 548 | U16 | 1 | |
| COMP SHUTDOWN - Evaporator Pressure Low Circuit 4, Comp 1 | 549 | U16 | 1 | |
| CIRCUIT SHUTDOWN - Evaporator Pressure Sensor Circuit 1 Fault | 551 | U16 | 1 | |
| CIRCUIT SHUTDOWN - Evaporator Pressure Sensor Circuit 2 Fault | 553 | U16 | 1 | |
| COMP SHUTDOWN - Evaporator Pressure Sensor Fault Circuit 3, Comp 1 | 555 | U16 | 1 | |
| COMP SHUTDOWN - Evaporator Pressure Sensor Fault Circuit 4, Comp 1 | 556 | U16 | 1 | |
| PUMP 2 START ATTEMPTED - Evaporator Pump 1 Failure | 574 | U16 | 1 | |
| PUMP 1 START ATTEMPTED - Evaporator Pump 2 Failure | 575 | U16 | 1 | |
| COMP LOCKOUT - Number of Allowed Re-Starts Exceeded Circuit 1, Comp 1 | 582 | U16 | 1 | |
| COMP LOCKOUT - Number of Allowed Re-Starts Exceeded Circuit 2, Comp 1 | 584 | U16 | 1 | |
| COMP LOCKOUT - Number of Allowed Re-Starts Exceeded Circuit 3, Comp 1 | 586 | U16 | 1 | |
| COMP LOCKOUT - Number of Allowed Re-Starts Exceeded Circuit 4, Comp 1 | 587 | U16 | 1 | |
| UNIT SHUTDOWN - Evaporator Leaving Water Temp Sensor Fault | 588 | U16 | 1 | |
| Evaporator Leaving Water Temperature 1 Sensor Fault | 589 | U16 | 1 | |
| Evaporator Leaving Water Temperature 2 Sensor Fault | 590 | U16 | 1 | |
| CIRCUIT SHUTDOWN - Evaporator 1 Freeze Protection | 591 | U16 | 1 | |
| CIRCUIT SHUTDOWN - Evaporator 2 Freeze Protection | 592 | U16 | 1 | |
| COMP SHUTDOWN - Mechanical High Pressure Trip Circuit 1, Comp 1 | 600 | U16 | 1 | |
| COMP SHUTDOWN - Mechanical High Pressure Trip Circuit 2, Comp 1 | 602 | U16 | 1 | |
| COMP SHUTDOWN - Mechanical High Pressure Trip Circuit 3, Comp 1 | 604 | U16 | 1 | |
| COMP SHUTDOWN - Mechanical High Pressure Trip Circuit 4, Comp 1 | 605 | U16 | 1 | |
| COMPRESSOR SHUTDOWN - Oil Delta Pressure High Circuit 1, Comp 1 | 636 | U16 | 1 | |
| COMPRESSOR SHUTDOWN - Oil Delta Pressure High Circuit 2, Comp 1 | 638 | U16 | 1 | |
| COMPRESSOR SHUTDOWN - Oil Delta Pressure High Circuit 3, Comp 1 | 640 | U16 | 1 | |
| COMPRESSOR SHUTDOWN - Oil Delta Pressure High Circuit 4, Comp 1 | 641 | U16 | 1 | |
| COMP SHUTDOWN - Oil Feed Pressure Sensor Fault Circuit 1, Comp 1 | 642 | U16 | 1 | |
| COMP SHUTDOWN - Oil Feed Pressure Sensor Fault Circuit 2, Comp 1 | 644 | U16 | 1 | |
| COMP SHUTDOWN - Oil Feed Pressure Sensor Fault Circuit 3, Comp 1 | 646 | U16 | 1 | |
| COMP SHUTDOWN - Oil Feed Pressure Sensor Fault Circuit 4, Comp 1 | 647 | U16 | 1 | |
| SHUTDOWN - Phase Voltage Protection (Unit) | 660 | U16 | 1 | |
| COMP SHUTDOWN - Starter Fault Compressor Circuit 1, Comp 1 | 661 | U16 | 1 | |
| COMP SHUTDOWN - Starter Fault Compressor Circuit 2, Comp 1 | 663 | U16 | 1 | |
| COMP SHUTDOWN - Starter Fault Compressor Circuit 3, Comp 1 | 665 | U16 | 1 | |
| COMP SHUTDOWN - Starter Fault Compressor Circuit 4, Comp 1 | 666 | U16 | 1 | |
| Circuit 1, Compressor 1 Oil Feed Loss | 672 | U16 | 1 | |
| Circuit 2, Compressor 1 Oil Feed Loss | 674 | U16 | 1 | |
| COMP SHUTDOWN - Suction Temp Sensor Fault Circuit 1, Comp 1 | 697 | U16 | 1 | |
| COMP SHUTDOWN - Suction Temp Sensor Fault Circuit 2, Comp 1 | 699 | U16 | 1 | |
| COMP SHUTDOWN - Suction Temp Sensor Fault Circuit 3, Comp 1 | 701 | U16 | 1 | |
| COMP SHUTDOWN - Suction Temp Sensor Fault Circuit 4, Comp 1 | 702 | U16 | 1 | |
| COMP SHUTDOWN - No Pressure At Startup Circuit 1 | 710 | U16 | 1 | |
| COMP SHUTDOWN - No Pressure At Startup Circuit 2 | 711 | U16 | 1 | |
| COMP SHUTDOWN - No Pressure At Startup Circuit 3 | 712 | U16 | 1 | |
| COMP SHUTDOWN - No Pressure At Startup Circuit 4 | 713 | U16 | 1 | |
| COMP SHUTDOWN - Mechanical Low Pressure Trip Circuit 1, Comp 1 | 716 | U16 | 1 | |
| COMP SHUTDOWN - Mechanical Low Pressure Trip Circuit 2, Comp 1 | 718 | U16 | 1 | |
| COMP SHUTDOWN - Mechanical Low Pressure Trip Circuit 3, Comp 1 | 720 | U16 | 1 | |
| COMP SHUTDOWN - Mechanical Low Pressure Trip Circuit 4, Comp 1 | 721 | U16 | 1 | |
| Controller Board Offline Circuit 1 | 722 | U16 | 1 | |
| Controller Board Offline Circuit 2 | 723 | U16 | 1 | |
| Controller Board Offline Circuit 3 | 724 | U16 | 1 | |
| Controller Board Offline Circuit 4 | 725 | U16 | 1 | |
| COMP SHUTDOWN - Motor Temp Sensor Fault Circuit 1, Comp 1 | 733 | U16 | 1 | |
| COMP SHUTDOWN - Motor Temp Sensor Fault Circuit 2, Comp 1 | 734 | U16 | 1 | |
| COMP SHUTDOWN - Motor Temp Sensor Fault Circuit 3, Comp 1 | 735 | U16 | 1 | |
| COMP SHUTDOWN - Motor Temp Sensor Fault Circuit 4, Comp 1 | 736 | U16 | 1 | |
| Unit Power Restore | 739 | U16 | 1 | |
| Circuit Failed Pumpdown - Circuit 1 | 740 | U16 | 1 | |
| Circuit Failed Pumpdown - Circuit 2 | 741 | U16 | 1 | |
| Circuit Failed Pumpdown - Circuit 3 | 742 | U16 | 1 | |
| Circuit Failed Pumpdown - Circuit 4 | 743 | U16 | 1 | |
| External Event | 744 | U16 | 1 | |
| Controller Board Offline - Unit | 745 | U16 | 1 | |
| COMP SHUTDOWN - No Pressure Change After Start Circuit 1 | 746 | U16 | 1 | |
| COMP SHUTDOWN - No Pressure Change After Start Circuit 2 | 747 | U16 | 1 | |
| COMP SHUTDOWN - No Pressure Change After Start Circuit 3 | 748 | U16 | 1 | |
| COMP SHUTDOWN - No Pressure Change After Start Circuit 4 | 749 | U16 | 1 | |
| SHUTDOWN - Phase Voltage Protection Circuit 1 | 750 | U16 | 1 | |
| SHUTDOWN - Phase Voltage Protection Circuit 2 | 751 | U16 | 1 | |
| SHUTDOWN - Phase Voltage Protection Circuit 3 | 752 | U16 | 1 | |
| SHUTDOWN - Phase Voltage Protection Circuit 4 | 753 | U16 | 1 | |
| Evaporator Entering Water Temperature Sensor Failure | 754 | U16 | 1 | |
| COMP SHUTDOWN - Slide Position Sensor Fault Circuit 1, Comp 1 | 755 | U16 | 1 | |
| COMP SHUTDOWN - Slide Position Sensor Fault Circuit 2, Comp 1 | 757 | U16 | 1 | |
| COMP SHUTDOWN - Slide Position Sensor Fault Circuit 3, Comp 1 | 759 | U16 | 1 | |
| COMP SHUTDOWN - Slide Position Sensor Fault Circuit 4, Comp 1 | 760 | U16 | 1 | |
| COMPRESSOR SHUTDOWN - COMPRESSOR VFD Fault Circuit 1, Comp 1 | 761 | U16 | 1 | |
| COMPRESSOR SHUTDOWN - COMPRESSOR VFD Fault Circuit 2, Comp 1 | 763 | U16 | 1 | |
| COMPRESSOR SHUTDOWN - COMPRESSOR VFD Fault Circuit 3, Comp 1 | 765 | U16 | 1 | |
| COMP SHUTDOWN - COMPRESSOR VFD Over Heat Fault Circuit 1, Comp 1 | 767 | U16 | 1 | |
| COMP SHUTDOWN - COMPRESSOR VFD Over Heat Fault Circuit 2, Comp 1 | 769 | U16 | 1 | |
| COMP SHUTDOWN - COMPRESSOR VFD Over Heat Fault Circuit 3, Comp 1 | 771 | U16 | 1 | |
| COMP SHUTDOWN - COM ERROR With COMPRESSOR VFD Circuit 1, Comp 1 | 773 | U16 | 1 | |
| COMP SHUTDOWN - COM ERROR With COMPRESSOR VFD Circuit 2, Comp 1 | 775 | U16 | 1 | |
| COMP SHUTDOWN - COM ERROR With COMPRESSOR VFD Circuit 3, Comp 1 | 777 | U16 | 1 | |
| INHIBIT LOAD - Compressor Motor Current High Circuit 1, Comp 1 | 779 | U16 | 1 | |
| INHIBIT LOAD - Compressor Motor Current High Circuit 2, Comp 1 | 781 | U16 | 1 | |
| INHIBIT LOAD - Compressor Motor Current High Circuit 3, Comp 1 | 783 | U16 | 1 | |
| UNIT STOP - Emergency Stop Alarm | 797 | U16 | 1 | |
| UNIT STOP - Evaporator Water Temperature Inverted | 798 | U16 | 1 | |
| UNIT STOP - External Alarm | 799 | U16 | 1 | |
| COMP SHUTDOWN - Low Discharge Superheat Circuit 1, Comp 1 | 807 | U16 | 1 | |
| COMP SHUTDOWN - Low Discharge Superheat Circuit 2, Comp 1 | 809 | U16 | 1 | |
| COMP SHUTDOWN - Low Discharge Superheat Circuit 3, Comp 1 | 811 | U16 | 1 | |
| Bad Current Limit Input | 813 | U16 | 1 | |
| Option Controller Communication Failed | 814 | U16 | 1 | |
| UNIT STOP - PVM GFP Fault | 815 | U16 | 1 | |
| CIRCUIT SHUTDOWN - PVM GFP Circuit 1 Fault | 816 | U16 | 1 | |
| CIRCUIT SHUTDOWN - PVM GFP Circuit 2 Fault | 817 | U16 | 1 | |
| COMP SHUTDOWN - Refrig Charge Circuit 1 | 821 | U16 | 1 | |
| COMP SHUTDOWN - Refrig Charge Circuit 2 | 822 | U16 | 1 | |
| COMP SHUTDOWN - Refrig Charge Circuit 3 | 823 | U16 | 1 | |
| Low Refrigerant Charge - Circuit 1 | 824 | U16 | 1 | |
| Low Refrigerant Charge - Circuit 2 | 825 | U16 | 1 | |
| Low Refrigerant Charge - Circuit 3 | 826 | U16 | 1 | |
| Chiller Network Communication Failure | 827 | U16 | 1 | |
| Circuit 1 Compressor 1 Stator Temperature 1 | 903 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 2 Stator Temperature 1 | 904 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 1 Stator Temperature 2 | 909 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 2 Stator Temperature 2 | 910 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 1 Stator Temperature 3 | 915 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 2 Stator Temperature 3 | 916 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 1 Motor Gap Temperature | 921 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 2 Motor Gap Temperature | 922 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 1 Motor Case Temperature | 927 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 2 Motor Case Temperature | 928 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 1 Rotor Pump Temperature | 933 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 2 Rotor Pump Temperature | 934 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 1 Lift Temperature | 939 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 2 Lift Temperature | 940 | I16 | 0.1 | F/C |
| Circuit 1 Compressor 1 Lift Pressure | 945 | U16 | 0.1 | Psi/kPa |
| Circuit 1 Compressor 2 Lift Pressure | 946 | U16 | 0.1 | Psi/kPa |
| Circuit 1 Compressor 1 Unavailable | 969 | U16 | 1 | |
| Circuit 2 Compressor 1 Unavailable | 971 | U16 | 1 | |
| Circuit 4 Compressor 1 Oil Feed Pressure | 1730 | I16 | 0.1 | psi/kPa |
| Circuit 3 Compressor 1 Oil Feed Pressure | 1769 | I16 | 0.1 | psi/kPa |
| Circuit 2 Compressor 1 Oil Feed Pressure | 1808 | I16 | 0.1 | psi/kPa |
| Circuit 1 Compressor 1 Oil Feed Pressure | 1848 | I16 | 0.1 | psi/kPa |
| Waterside Economizer State | 1853 | U16 | 1 | |
| Waterside Economizer Enable Setpoint | 1854 | U16 | 1 | |
| Circuit 1 Liquid Line Refrigerant Temperature | 1983 | I16 | 0.1 | F/C |
| Circuit 1 Suction Refrigerant Temperature | 1989 | I16 | 1 | F/C |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.