device library

Daikin VRV Modbus interface EKMBDXB

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
unit_1_00_on_off_status2000U161
unit_1_00_operation_status2001U161
unit_1_00_room_temperature_set_point_read2002I160.1°C
unit_1_00_room_temperature2004I160.1°C
unit_1_00_leaving_water_set_point_heating_read2800I160.1°C
unit_1_00_leaving_water_set_point_cooling_read2801I160.1°C
unit_1_00_error_code3600U161
central_forced_off1000U161
unit_1_00_on_off_command2000U161
unit_1_00_operation_mode_setting2001U161
unit_1_00_room_temperature_set_point_write2002I160.1°C
unit_1_00_leaving_water_set_point_heating_write2400I160.1°C
unit_1_00_leaving_water_set_point_cooling_write2401I160.1°C
unit_1_00_domestic_hot_water_storage_set_point_write2402I160.1°C
unit_1_00_user_interface_lock2800U161°C

link settings as documented (unverified): RTU; default 9600 8E1; FC 03,04,06,16; Silent internal time: 5ms at 9600bps, 2.5ms at 19200bps. Response time is Silent Interval Time + 20ms.

⚠ The number of control commands per indoor unit is limited to 7000 per year. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsX3M (RS-485), F1/F2 (DIII-net), X1M (Power supply)
A/B polarityA+, B-
terminationSS2 On = 120 Ohm, SS3 On = 100 Ohm, SS1 not used. Factory default is 0 Ohm (SS2=Off & SS3=Off)
connectorTerminal strips
shield/groundProtective earth
wiring notesBMS RS485 (2 wire, max 500m), DIII net (F1F2) maximum 64 indoor units and maximum 10 outdoors
max registers/read32
response timeout25 ms
inter-frame delay5 ms
broadcastsupported
protocol notesThe number of control commands per indoor unit is limited to 7000 per year.
power220 – 240 VAC 50/60 Hz
environmentTemp range 0 till 60°C, Indoor installation, IP X0
doc revision4P642495-1A– 2022.02
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms.baud_rates: [9600, 19200], default_baud: 9600, framing: ['RTU'], parity: 'E', stop_bits: 1 — confirmed by Daikin Central Europe Modbus Interface DIII Design Guide (4P642495-1A– 2022.02)
  • confirmed: facts.control_warning: 'The number of control commands per indoor unit is limited to 7000 per year.' — confirmed by Daikin Central Europe Modbus Interface DIII Design Guide (4P642495-1A– 2022.02)
  • confirmed: facts.environment: 'Temp range 0 till 60°C, Indoor installation, IP X0' — confirmed by Daikin Central Europe Modbus Interface DIII Design Guide (4P642495-1A– 2022.02)
  • confirmed: facts.physical.terminals: 'X3M (RS-485), F1/F2 (DIII-net), X1M (Power supply)' — confirmed by Daikin Central Europe Modbus Interface DIII Design Guide (4P642495-1A– 2022.02)
  • confirmed: facts.power: '220 – 240 VAC 50/60 Hz' — confirmed by Daikin Central Europe Modbus Interface DIII Design Guide (4P642495-1A– 2022.02)
  • confirmed: quirks.max_read_registers: 32 — confirmed by Daikin Central Europe Modbus Interface DIII Design Guide (4P642495-1A– 2022.02)
  • confirmed: register_map: unit_1_00_on_off_status @ 2000, unit_1_00_on_off_command @ 2000 — confirmed by openHAB community integration and Daikin Central Europe Modbus Interface DIII Design Guide (4P642495-1A– 2022.02) where register 32001/42001 maps to 0-based address 2000

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.