Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
PCD1 Control Word (Coils 1-16)0U161
Array index8U161
PCD2 Reference Value (Coils 17-32)16U161
PCD1 Status Word (Coils 33-48)32U161
PCD2 Given output frequency (Coils 49-64)48U161
Write parameters to eeprom64U161
Address (VLT 2800) / Protocol (VLT 6000/8000)4999U161
Baudrate (VLT 2800) / Address (VLT 6000/8000)5009U161
Protocol (VLT 2800)5609U161
Modbus parity and message framing5699U161
Modbus communications timeout5709U161ms