DENT PowerScout 3/18 submeter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
System Total True Energy, LSW0U161kWh
System Total True Energy, MSW1U161kWh
System Total True Power2U161kW
System Total Reactive Power3U161kVAR
System Total Apparent Power4U161kVA
System Total Apparent Power Factor5U161PF
Average Line to Line Voltage6U161Volts
Average Line to Neutral Voltage7U161Volts
Sum of Line Currents8U161Amps
L1 Phase True Power9U161kW
L2 Phase True Power10U161kW
L3 Phase True Power11U161kW
L1 Phase Apparent Power Factor12U161aPF
L2 Phase Apparent Power Factor13U161aPF
L3 Phase Apparent Power Factor14U161aPF
L1 - L2 Voltage15U161Volts
L2 - L3 Voltage16U161Volts
L3 - L1 Voltage17U161Volts
L1 - Neutral Voltage18U161Volts
L2 - Neutral Voltage19U161Volts
L3 - Neutral Voltage20U161Volts
L1 Current21U161Amps
L2 Current22U161Amps
L3 Current23U161Amps
System Average Demand24U161kW
System Minimum Inst. Demand25U161kW
System Maximum Inst. Demand26U161kW
Synchronize Register128U161
kwh_system_lsw4000U161kWh
kwh_system_msw4001U161kWh
kw_system4002I161kW
kw_demand_system_max4003I161kW
kw_demand_system_now4004I161kW
kw_system_max4005I161kW
kw_system_min4006I161kW
kvarh_system_lsw4007U161kVARh
kvarh_system_msw4008U161kVARh
kvar_system4009I161kVAR
kvah_system_lsw4010U161kVAh
kvah_system_msw4011U161kVAh
kva_system4012U161kVA
displacement_pf_system4013I161PF
apparent_pf_system4014I161PF
amps_system_avg4015U161A
volts_line_to_line_avg4016U161V
volts_line_to_neutral_avg4017U161V
volts_l1_to_l24018U161V
volts_l2_to_l34019U161V
volts_l1_to_l34020U161V
line_frequency4021U161Hz
kwh_l1_lsw4022U161kWh
kwh_l1_msw4023U161kWh
kwh_l2_lsw4024U161kWh
kwh_l2_msw4025U161kWh
kwh_l3_lsw4026U161kWh
kwh_l3_msw4027U161kWh
kw_l14028I161kW
kw_l24029I161kW
kw_l34030I161kW
kvarh_l1_lsw4031U161kVARh
kvarh_l1_msw4032U161kVARh
kvarh_l2_lsw4033U161kVARh
kvarh_l2_msw4034U161kVARh
kvarh_l3_lsw4035U161kVARh
kvarh_l3_msw4036U161kVARh
kvar_l14037I161kVAR
kvar_l24038I161kVAR
kvar_l34039I161kVAR
kvah_l1_lsw4040U161kVAh
kvah_l1_msw4041U161kVAh
kvah_l2_lsw4042U161kVAh
kvah_l2_msw4043U161kVAh
kvah_l3_lsw4044U161kVAh
kvah_l3_msw4045U161kVAh
kva_l14046U161kVA
kva_l24047U161kVA
kva_l34048U161kVA
displacement_pf_l14049I161PF
displacement_pf_l24050I161PF
displacement_pf_l34051I161PF
apparent_pf_l14052I161PF
apparent_pf_l24053I161PF
apparent_pf_l34054I161PF
amps_l14055U161A
amps_l24056U161A
amps_l34057U161A
volts_l1_to_neutral4058U161V
Individual Phase to Neutral Voltages L24059U161V
Individual Phase to Neutral Voltages L34060U161V
Seconds since KWH register was reset LSW4061U161s
Seconds since KWH register was reset MSW4062U161s
Volts Scalar (not implemented)4064U161
Amps Scalar (not implemented)4065U161
Firmware Major Revision4068U161
Firmware Minor Revision4069U161
Model Name 10 bytes (ASCII Alpha-Numeric) 1st 2 bytes4200U161
Model 24201U161
Model 34202U161
Model 44203U161
Model Number last 2 bytes4204U161
Serial Number 10 bytes (ASCII Alpha-Numeric) 1st 2 bytes4205U161
Serial 24206U161
Serial 34207U161
Serial 44208U161
Serial Number last 2 bytes4209U161
CT Value (x2)4300U161A
Data Scalar4301U161
Demand Window Size4302U161Minutes

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 03,06,17; Up to 41 PowerScout 18 meters (249 PowerScout 3 meters) may be connected to a single RTU.

⚠ CAUTION: This METER may contain life threatening voltages. QUALIFIED PERSONNEL MUST Disconnect all high voltage wiring before USING or servicing the METER. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsconnector for four voltage wire leads (L1, L2, L3, Neutral), connectors for up to 18 CTs (PS18) or 3 CTs (PS3), three wire connector for RS-485 Modbus link
A/B polarityThe CTs are insensitive to orientation
connectorthree wire connector for the RS-485 Modbus link
isolationdouble insulation (IEC 536 Class II)
protocol notesEach PowerScout 18 uses 6 Modbus addresses (A through F), each one higher than the previous.
model register4200
serial register4205
firmware register4068
identification notesModel and Serial numbers are 10 bytes ASCII Alpha-Numeric
powerFrom L1 Phase to L2 Phase. PS 18: 5 Watts typ. @ 600VAC, 2.5W typ. @ 80VAC; non-user replaceable .5 Amp Internal fuse protection.
environmentOperating Temperature: -7 to +60 oC (20 to 140 oF), Humidity: 5% to 95% non-condensing
accuracyBetter Than 1% (<0.5% typical) for V, A, kW, kVAR, kVA, PF
certificationsConforms to UL Std 61010-1, Certified to CSA Std C22.2 No. 61010-1
doc revisionOctober 25, 2010
field reports — community-sourced, unverified (checked 2026-06-11)
  • Downloading readings of multiple loads over the fixed 9600 bps baud rate of the legacy DENT meters can cause slight variations in timestamp synchronization due to bandwidth limitations. [source]
  • confirmed: comms.baud_rates: [9600] — confirmed by the User's Manual (October 25, 2010) which states 'Communication Rate: 9600 baud' and independent research noting the fixed 9600 bps rate of the legacy PowerScout 18.
  • confirmed: comms.default_unit_id: 1 — confirmed by the User's Manual stating 'The default factory setting is hex 01 (Modbus Address Decimal 01)'.
  • confirmed: comms.framing: ['RTU'] — confirmed by the User's Manual stating 'Modbus Framing: RTU (binary)'.
  • confirmed: comms.function_codes: [3, 6, 17] — confirmed by the User's Manual stating 'The Modbus commands that are used by the PowerScout meter are the Read Holding Register command [03], the Write (Preset) Single Register command [06] and the Return Slave ID command [17 / 0x11]'.
  • confirmed: facts.accuracy: 'Better Than 1% (<0.5% typical) for V, A, kW, kVAR, kVA, PF' — confirmed by the product specifications in the User's Manual.
  • confirmed: facts.certifications: 'Conforms to UL Std 61010-1, Certified to CSA Std C22.2 No. 61010-1' — confirmed by the Safety Summary in the User's Manual.
  • confirmed: facts.control_warning: 'CAUTION: This METER may contain life threatening voltages. QUALIFIED PERSONNEL MUST Disconnect all high voltage wiring before USING or servicing the METER.' — confirmed by the Safety Summary in the User's Manual.
  • confirmed: facts.doc_revision: 'October 25, 2010' — confirmed by the cover page of the User's Manual.

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.