Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| System Total True Energy, LSW | 0 | U16 | 1 | kWh |
| System Total True Energy, MSW | 1 | U16 | 1 | kWh |
| System Total True Power | 2 | U16 | 1 | kW |
| System Total Reactive Power | 3 | U16 | 1 | kVAR |
| System Total Apparent Power | 4 | U16 | 1 | kVA |
| System Total Apparent Power Factor | 5 | U16 | 1 | PF |
| Average Line to Line Voltage | 6 | U16 | 1 | Volts |
| Average Line to Neutral Voltage | 7 | U16 | 1 | Volts |
| Sum of Line Currents | 8 | U16 | 1 | Amps |
| L1 Phase True Power | 9 | U16 | 1 | kW |
| L2 Phase True Power | 10 | U16 | 1 | kW |
| L3 Phase True Power | 11 | U16 | 1 | kW |
| L1 Phase Apparent Power Factor | 12 | U16 | 1 | aPF |
| L2 Phase Apparent Power Factor | 13 | U16 | 1 | aPF |
| L3 Phase Apparent Power Factor | 14 | U16 | 1 | aPF |
| L1 - L2 Voltage | 15 | U16 | 1 | Volts |
| L2 - L3 Voltage | 16 | U16 | 1 | Volts |
| L3 - L1 Voltage | 17 | U16 | 1 | Volts |
| L1 - Neutral Voltage | 18 | U16 | 1 | Volts |
| L2 - Neutral Voltage | 19 | U16 | 1 | Volts |
| L3 - Neutral Voltage | 20 | U16 | 1 | Volts |
| L1 Current | 21 | U16 | 1 | Amps |
| L2 Current | 22 | U16 | 1 | Amps |
| L3 Current | 23 | U16 | 1 | Amps |
| System Average Demand | 24 | U16 | 1 | kW |
| System Minimum Inst. Demand | 25 | U16 | 1 | kW |
| System Maximum Inst. Demand | 26 | U16 | 1 | kW |
| Synchronize Register | 128 | U16 | 1 | |
| kwh_system_lsw | 4000 | U16 | 1 | kWh |
| kwh_system_msw | 4001 | U16 | 1 | kWh |
| kw_system | 4002 | I16 | 1 | kW |
| kw_demand_system_max | 4003 | I16 | 1 | kW |
| kw_demand_system_now | 4004 | I16 | 1 | kW |
| kw_system_max | 4005 | I16 | 1 | kW |
| kw_system_min | 4006 | I16 | 1 | kW |
| kvarh_system_lsw | 4007 | U16 | 1 | kVARh |
| kvarh_system_msw | 4008 | U16 | 1 | kVARh |
| kvar_system | 4009 | I16 | 1 | kVAR |
| kvah_system_lsw | 4010 | U16 | 1 | kVAh |
| kvah_system_msw | 4011 | U16 | 1 | kVAh |
| kva_system | 4012 | U16 | 1 | kVA |
| displacement_pf_system | 4013 | I16 | 1 | PF |
| apparent_pf_system | 4014 | I16 | 1 | PF |
| amps_system_avg | 4015 | U16 | 1 | A |
| volts_line_to_line_avg | 4016 | U16 | 1 | V |
| volts_line_to_neutral_avg | 4017 | U16 | 1 | V |
| volts_l1_to_l2 | 4018 | U16 | 1 | V |
| volts_l2_to_l3 | 4019 | U16 | 1 | V |
| volts_l1_to_l3 | 4020 | U16 | 1 | V |
| line_frequency | 4021 | U16 | 1 | Hz |
| kwh_l1_lsw | 4022 | U16 | 1 | kWh |
| kwh_l1_msw | 4023 | U16 | 1 | kWh |
| kwh_l2_lsw | 4024 | U16 | 1 | kWh |
| kwh_l2_msw | 4025 | U16 | 1 | kWh |
| kwh_l3_lsw | 4026 | U16 | 1 | kWh |
| kwh_l3_msw | 4027 | U16 | 1 | kWh |
| kw_l1 | 4028 | I16 | 1 | kW |
| kw_l2 | 4029 | I16 | 1 | kW |
| kw_l3 | 4030 | I16 | 1 | kW |
| kvarh_l1_lsw | 4031 | U16 | 1 | kVARh |
| kvarh_l1_msw | 4032 | U16 | 1 | kVARh |
| kvarh_l2_lsw | 4033 | U16 | 1 | kVARh |
| kvarh_l2_msw | 4034 | U16 | 1 | kVARh |
| kvarh_l3_lsw | 4035 | U16 | 1 | kVARh |
| kvarh_l3_msw | 4036 | U16 | 1 | kVARh |
| kvar_l1 | 4037 | I16 | 1 | kVAR |
| kvar_l2 | 4038 | I16 | 1 | kVAR |
| kvar_l3 | 4039 | I16 | 1 | kVAR |
| kvah_l1_lsw | 4040 | U16 | 1 | kVAh |
| kvah_l1_msw | 4041 | U16 | 1 | kVAh |
| kvah_l2_lsw | 4042 | U16 | 1 | kVAh |
| kvah_l2_msw | 4043 | U16 | 1 | kVAh |
| kvah_l3_lsw | 4044 | U16 | 1 | kVAh |
| kvah_l3_msw | 4045 | U16 | 1 | kVAh |
| kva_l1 | 4046 | U16 | 1 | kVA |
| kva_l2 | 4047 | U16 | 1 | kVA |
| kva_l3 | 4048 | U16 | 1 | kVA |
| displacement_pf_l1 | 4049 | I16 | 1 | PF |
| displacement_pf_l2 | 4050 | I16 | 1 | PF |
| displacement_pf_l3 | 4051 | I16 | 1 | PF |
| apparent_pf_l1 | 4052 | I16 | 1 | PF |
| apparent_pf_l2 | 4053 | I16 | 1 | PF |
| apparent_pf_l3 | 4054 | I16 | 1 | PF |
| amps_l1 | 4055 | U16 | 1 | A |
| amps_l2 | 4056 | U16 | 1 | A |
| amps_l3 | 4057 | U16 | 1 | A |
| volts_l1_to_neutral | 4058 | U16 | 1 | V |
| Individual Phase to Neutral Voltages L2 | 4059 | U16 | 1 | V |
| Individual Phase to Neutral Voltages L3 | 4060 | U16 | 1 | V |
| Seconds since KWH register was reset LSW | 4061 | U16 | 1 | s |
| Seconds since KWH register was reset MSW | 4062 | U16 | 1 | s |
| Volts Scalar (not implemented) | 4064 | U16 | 1 | |
| Amps Scalar (not implemented) | 4065 | U16 | 1 | |
| Firmware Major Revision | 4068 | U16 | 1 | |
| Firmware Minor Revision | 4069 | U16 | 1 | |
| Model Name 10 bytes (ASCII Alpha-Numeric) 1st 2 bytes | 4200 | U16 | 1 | |
| Model 2 | 4201 | U16 | 1 | |
| Model 3 | 4202 | U16 | 1 | |
| Model 4 | 4203 | U16 | 1 | |
| Model Number last 2 bytes | 4204 | U16 | 1 | |
| Serial Number 10 bytes (ASCII Alpha-Numeric) 1st 2 bytes | 4205 | U16 | 1 | |
| Serial 2 | 4206 | U16 | 1 | |
| Serial 3 | 4207 | U16 | 1 | |
| Serial 4 | 4208 | U16 | 1 | |
| Serial Number last 2 bytes | 4209 | U16 | 1 | |
| CT Value (x2) | 4300 | U16 | 1 | A |
| Data Scalar | 4301 | U16 | 1 | |
| Demand Window Size | 4302 | U16 | 1 | Minutes |
⚠ CAUTION: This METER may contain life threatening voltages. QUALIFIED PERSONNEL MUST Disconnect all high voltage wiring before USING or servicing the METER. — Starkest reads only; we never write a control register.
| terminals | connector for four voltage wire leads (L1, L2, L3, Neutral), connectors for up to 18 CTs (PS18) or 3 CTs (PS3), three wire connector for RS-485 Modbus link |
| A/B polarity | The CTs are insensitive to orientation |
| connector | three wire connector for the RS-485 Modbus link |
| isolation | double insulation (IEC 536 Class II) |
| protocol notes | Each PowerScout 18 uses 6 Modbus addresses (A through F), each one higher than the previous. |
| model register | 4200 |
| serial register | 4205 |
| firmware register | 4068 |
| identification notes | Model and Serial numbers are 10 bytes ASCII Alpha-Numeric |
| power | From L1 Phase to L2 Phase. PS 18: 5 Watts typ. @ 600VAC, 2.5W typ. @ 80VAC; non-user replaceable .5 Amp Internal fuse protection. |
| environment | Operating Temperature: -7 to +60 oC (20 to 140 oF), Humidity: 5% to 95% non-condensing |
| accuracy | Better Than 1% (<0.5% typical) for V, A, kW, kVAR, kVA, PF |
| certifications | Conforms to UL Std 61010-1, Certified to CSA Std C22.2 No. 61010-1 |
| doc revision | October 25, 2010 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.