device library

E-Mon Multi-Mon energy monitor

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
v1_voltage13952U32LE0.1
v2_voltage13954U32LE0.1
v3_voltage13956U32LE0.1
i1_current13958U32LE0.01
i2_current13960U32LE0.01
i3_current13962U32LE0.01
kw_l113964U32LE0.001
kw_l213966U32LE0.001
kw_l313968U32LE0.001
kvar_l113970U32LE0.001
kvar_l213972U32LE0.001
kvar_l313974U32LE0.001
kva_l113976U32LE0.001
kva_l213978U32LE0.001
kva_l313980U32LE0.001
power_factor_l113982U32LE0.001
power_factor_l213984U32LE0.001
power_factor_l313986U32LE0.001
total_kw14336U32LE0.001
total_kvar14338U32LE0.001
total_kva14340U32LE0.001
total_pf14342U32LE0.001
frequency14466U32LE0.01
kwh_import14720U32LE0.1
kwh_export14722U32LE0.1
kvarh_import14728U32LE0.1
kvarh_export14730U32LE0.1
kvah_total14736U32LE0.1

link settings as documented (unverified): RTU/ASCII/TCP; baud 300/600/1200/2400/4800/9600/19200/38400/57600/115200; unit ID 1; FC 03,04,06,16,08; Broadcast mode using address 0 is not supported.

bench facts as documented (unverified)
wiring notesCommunication interface options: RS-232, RS-422, RS-485, Infrared, Dial-Up Modem, RF Modem, Ethernet, GSM/GPRS
broadcastnot supported
model register46084
serial register46080
firmware register46100
doc revisionBG0548 Rev. A1

⚠ disputed: frequency @ 14466 — disputed by E-Mon Multi-Mon MODBUS Reference Guide BG0548 Section 3.1, which shows the 1-Second Auxiliary Values block starting at 14464, where offset +2,3 (14466-14467) is 'In (neutral) Current' and offset +4,5 (14468-14469) is 'Frequency'

field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: baud_rates [300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200] — confirmed by E-Mon Multi-Mon MODBUS Reference Guide BG0548 Section 3.7
  • confirmed: framing ['RTU', 'ASCII', 'TCP'] — confirmed by E-Mon Multi-Mon MODBUS Reference Guide BG0548 Section 2.1
  • confirmed: broadcast_supported: false — confirmed by E-Mon Multi-Mon MODBUS Reference Guide BG0548 Section 2.2
  • confirmed: identification registers (serial @ 46080, model @ 46084, firmware @ 46100) — confirmed by E-Mon Multi-Mon MODBUS Reference Guide BG0548 Section 3.1
  • confirmed: register map (v1_voltage @ 13952, total_kw @ 14336, kwh_import @ 14720, kvah_total @ 14736) — confirmed by E-Mon Multi-Mon MODBUS Reference Guide BG0548 Section 3.1

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.