device library

Eaton IQ100/IQ130/IQ140/IQ150 meter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
amps_a_amps1010F32BE1A
positive_power_factor_3_ph_maximum_avg_demand_none3126F32BE1PF
power_energy_format_pppp_nn_eee_ddd30004U161kWh
frequency_hz1024F32BE1Hz
positive_pf_3_ph_average_100_to_1002014F32BE1
positive_watts_3_ph_maximum_avg_demand_watts3116F32BE1kW
meter_status_bit_mapped4998U161
meter_type_bit_mapped15U161
amps_b_amps1012F32BE1A
amps_c_amps1014F32BE1A
neutral_current_amps1026F32BE1A

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.