Eaton Power Xpert PXM 4000/6000/8000 meter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

cross-referenced (demoted: under-extracted stub (<=3 regs); needs re-extraction (#52))

Imported from a third-party source and NOT verified by us — not even structure-checked. An unverified claim, shown so you can find the device; trust it no more than the source it came from.

pointaddress (0-based)typescaleunit
subnet_timeout2004U161

link settings as documented (unverified): RTU/ASCII/TCP; baud 9600/19200/38400/57600/115200; Supports Modbus RTU Slave, Slave-Gateway, Master-Gateway, Slave (ASCII), or Master-IO. The RS485 CE3 port supports Modbus RTU slave to a master monitoring system.

⚠ VERIFY THAT ANY INCOMING AC POWER OR FOREIGN POWER SOURCES ARE TURNED OFF AND LOCKED OUT BEFORE PERFORMING ANY WORK ON THE POWER XPERT METER OR ASSOCIATED EQUIPMENT. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsTerminal blocks for CT and VT connections accepting up to #10 AWG wire. 3-terminal plug for RS485.
A/B polarityData A (-) and Data B (+)
termination120 ohm 1/4 W End-of-Line Termination Resistors (EOLTR) required at each end of the cable.
connectorRJ45 modular with Grounded Metal Shield, DB9, and 3-terminal plug.
isolationOptical isolation from all other inputs and outputs, 240 Vac / 1 min. Transformer isolated 10/100 Base T with min 1,000 Vac 1 min isolation.
shield/groundTie the communication cable shield to ground only once at the RS485 master device.
response timeout1000 ms
protocol notesIf a subnet device doesn't respond within the Total Timeout, the meter responds with exception 11 (0xb) or 'Gateway Target Device Failed to Respond.'
identification notesModel number is printed on the product label located on the left side of the meter.
power100-240 Vac or 110-250 Vdc (PXMPS-1) standard power supply, 50W draw max.
environmentOperating temperature: Meter -20° to 70°C, Display -20° to 60°C. Storage temperature: -40° to 85°C. Humidity: 5% - 95% non-condensing. Max altitude: 3000 meters. Pollution Degree II for Meter and Display Back.
accuracyIEC/EN 62053-22, Classes 0.2 & 0.5 (0.2% min), ANSI C12.20 (Electricity Meters 0.2%)
certificationsCE mark, UL 61010-1 2nd Edition, FCC Part 15 Subpart B Class A
doc revisionIM02601004E
field reports — community-sourced, unverified (checked 2026-06-11)
  • K-factor register 4663 (1236 hex) is not supported in PXM 4000 prior to firmware version 12.x.x. [source]
  • confirmed: comms.baud_rates: [9600, 19200, 38400, 57600, 115200] — confirmed by Eaton Power Xpert PXM 4000/6000/8000 User and Installation Manual IM02601004E, which lists these baud rates under serial settings.
  • confirmed: comms.parity: N — confirmed by Eaton Power Xpert PXM 4000/6000/8000 User and Installation Manual IM02601004E, which lists None, Odd, or Even parity options.
  • confirmed: comms.stop_bits: 1 — confirmed by Eaton Power Xpert PXM 4000/6000/8000 User and Installation Manual IM02601004E, which lists 1 or 2 stop bits.
  • confirmed: physical.polarity: Data A (-) and Data B (+) — confirmed by Eaton Power Xpert PXM 4000/6000/8000 User and Installation Manual IM02601004E, which specifies RS485 connections.
  • confirmed: register map: subnet_timeout @ 2004 (0-based) — confirmed by Eaton Modbus Register Map for Power Xpert Meter 4000/6000/8000 (IB150014EN), which lists Subnetwork Timeout Milliseconds at register 2005 (1-based), corresponding to 2004 (0-based).

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.