Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Analogue input (control) | 298 | I16 | 0.1 | °C/°F |
| contatore autorepeat | 408 | U16 | 1 | |
| Analogue output | 1486 | U16 | 1 | |
| Sequence program number active | 1503 | U16 | 1 | |
| Sequence program step number active | 1504 | U16 | 1 | |
| SP1 - Regulation set point 1 | 16392 | I16 | 0.1 | °C/°F |
| OS1 - Offset on set point 1 | 16394 | I16 | 0.1 | °C/°F |
| db1 - Tripping band above set point 1 | 16396 | U16 | 0.1 | °C/°F |
| dF1 - Differential of set point 1 | 16398 | I16 | 0.1 | °C/°F |
| HS1 - Maximum value settable for set point 1 | 16400 | I16 | 0.1 | °C/°F |
| LS1 - Minimum value settable for set point 1 | 16402 | I16 | 0.1 | °C/°F |
| HA1 - Max. alarm regulator 1 | 16404 | I16 | 0.1 | °C/°F |
| LA1 - Min. alarm regulator 1 | 16406 | I16 | 0.1 | °C/°F |
| SP2 - Regulation set point 2 | 16408 | I16 | 0.1 | °C/°F |
| OS2 - Offset on set point 2 | 16410 | I16 | 0.1 | °C/°F |
| db2 - Tripping band above set point 2 | 16412 | U16 | 0.1 | °C/°F |
| dF2 - Differential of set point 2 | 16414 | I16 | 0.1 | °C/°F |
| HS2 - Maximum value settable for set point 2 | 16416 | I16 | 0.1 | °C/°F |
| LS2 - Minimum value settable for set point 2 | 16418 | I16 | 0.1 | °C/°F |
| HA2 - Max. alarm regulator 2 | 16420 | I16 | 0.1 | °C/°F |
| LA2 - Min. alarm regulator 2 | 16422 | I16 | 0.1 | °C/°F |
| Sdi - Automatic back swing of Soft start function | 16428 | U16 | 0.1 | °C/°F |
| Afd - Alarm differential | 16430 | U16 | 0.1 | °C/°F |
| PA1 - Value of password 1 | 16432 | U16 | 1 | |
| PA2 - Value of password 2 | 16434 | U16 | 1 | |
| CA1 - Probe calibration | 16436 | I16 | 0.1 | °C/°F |
| LdL - Minimum value that can be displayed | 16438 | I16 | 0.1 | °C/°F |
| HdL - Maximum value that can be displayed | 16440 | I16 | 0.1 | °C/°F |
| dut - PID duty cycle in manual mode | 16442 | I16 | 0.1 | |
| set01 - Set point for step 0 of program 1 | 16510 | I16 | 0.1 | °C/°F |
| set11 - Set point for step 1 of program 1 | 16512 | I16 | 0.1 | °C/°F |
| set21 - Set point for step 2 of program 1 | 16514 | I16 | 0.1 | °C/°F |
| set31 - Set point for step 3 of program 1 | 16516 | I16 | 0.1 | °C/°F |
| set41 - Set point for step 4 of program 1 | 16518 | I16 | 0.1 | °C/°F |
| set51 - Set point for step 5 of program 1 | 16520 | I16 | 0.1 | °C/°F |
| set61 - Set point for step 6 of program 1 | 16522 | I16 | 0.1 | °C/°F |
| set71 - Set point for step 7 of program 1 | 16524 | I16 | 0.1 | °C/°F |
| set02 - Set point for step 0 of program 2 | 16526 | I16 | 0.1 | °C/°F |
| set12 - Set point for step 1 of program 2 | 16528 | I16 | 0.1 | °C/°F |
| set22 - Set point for step 2 of program 2 | 16530 | I16 | 0.1 | °C/°F |
| set32 - Set point for step 3 of program 2 | 16532 | I16 | 0.1 | °C/°F |
| set42 - Set point for step 4 of program 2 | 16534 | I16 | 0.1 | °C/°F |
| set52 - Set point for step 5 of program 2 | 16536 | I16 | 0.1 | °C/°F |
| set62 - Set point for step 6 of program 2 | 16538 | I16 | 0.1 | °C/°F |
| set72 - Set point for step 7 of program 2 | 16540 | I16 | 0.1 | °C/°F |
| LAO - Lower limit of analogue output | 16542 | I16 | 0.1 | |
| HAO - Upper limit of analogue output | 16544 | I16 | 0.1 | |
| SLOH - Minimum saturation of PID output H | 16710 | U16 | 0.1 | |
| SHIH - Maximum saturation of PID output H | 16712 | U16 | 0.1 | |
| bPH - PID proportional band H | 16714 | U16 | 0.1 | °C/°F |
| tiH - PID integral time H | 16716 | U16 | 1 | secs |
| tdH - PID derivative time H | 16718 | U16 | 1 | secs |
| ttH - Integral time for PID windup anti-reset H | 16720 | U16 | 1 | secs |
| biAH - PID static polarization H | 16722 | I16 | 0.1 | |
| PEdH - Partial period with PID duty cycle H | 16724 | U16 | 1 | sec |
| SLOC - Minimum saturation of PID output C | 16728 | U16 | 0.1 | |
| SHIC - Maximum saturation of PID output C | 16730 | U16 | 0.1 | |
| bPC - PID proportional band C | 16732 | U16 | 0.1 | °C/°F |
| tiC - PID integral time C | 16734 | U16 | 1 | secs |
| tdC - PID derivative time C | 16736 | U16 | 1 | secs |
| ttC - Integral time for PID windup anti-reset C | 16738 | U16 | 1 | secs |
| biAC - PID static polarization C | 16740 | I16 | 0.1 | |
| PEdC - Partial period with PID duty cycle C | 16742 | U16 | 1 | secs |
| APLH - Amplitude of oscillation in auto-tuning mode H | 16746 | U16 | 0.1 | °C/°F |
| biAtH - Relay polarization in auto-tuning mode H | 16748 | U16 | 0.1 | |
| APrH - Relay amplitude in auto-tuning mode H | 16750 | U16 | 0.1 | |
| AHrH - Relay hysteresis in auto-tuning mode H | 16752 | U16 | 0.1 | °C/°F |
| APLC - Amplitude of oscillation in auto-tuning mode C | 16762 | U16 | 0.1 | °C/°F |
| biAtC - Relay polarization in auto-tuning mode C | 16764 | I16 | 0.1 | |
| APrC - Relay amplitude in auto-tuning mode C | 16766 | U16 | 0.1 | |
| AHrC - Relay hysteresis in auto-tuning mode C | 16768 | U16 | 0.1 | °C/°F |
| Out 2 status | 32802 | U16 | 1 | |
| Out 1 status | 32811 | U16 | 1 | |
| Digital input status | 33048 | U16 | 1 | |
| Alarm status | 33051 | U16 | 1 | |
| Autotuning status | 33057 | U16 | 1 | |
| Control 33058 | 33058 | U16 | 1 | |
| Control 33059 | 33059 | U16 | 1 | |
| Setpoint status | 33060 | U16 | 1 | |
| Sequence program control | 33063 | U16 | 1 | |
| Cont. Cycle status | 33073 | U16 | 1 | |
| Status 33285 | 33285 | U16 | 1 | |
| Out Buzzer | 34283 | U16 | 1 | |
| Failed autotuning | 34552 | U16 | 1 | |
| del01_m - Enabling delay in minutes for step 0 of program 1 | 49214 | U16 | 1 | min |
| del01_h - Enabling delay in hours for step 0 of program 1 | 49215 | U16 | 1 | hours |
| del11_m - Enabling delay in minutes for step 1 of program 1 | 49216 | U16 | 1 | min |
| del11_h - Enabling delay in hours for step 1 of program 1 | 49217 | U16 | 1 | hours |
| del21_m - Enabling delay in minutes for step 2 of program 1 | 49218 | U16 | 1 | min |
| del21_h - Enabling delay in hours for step 2 of program 1 | 49219 | U16 | 1 | hours |
| del31_m - Enabling delay in minutes for step 3 of program 1 | 49220 | U16 | 1 | min |
| del31_h - Enabling delay in hours for step 3 of program 1 | 49221 | U16 | 1 | hours |
| del41_m - Enabling delay in minutes for step 4 of program 1 | 49222 | U16 | 1 | min |
| del41_h - Enabling delay in hours for step 4 of program 1 | 49223 | U16 | 1 | hours |
| del51_m - Enabling delay in minutes for step 5 of program 1 | 49224 | U16 | 1 | min |
| del51_h - Enabling delay in hours for step 5 of program 1 | 49225 | U16 | 1 | hours |
| del61_m - Enabling delay in minutes for step 6 of program 1 | 49226 | U16 | 1 | min |
| del61_h - Enabling delay in hours for step 6 of program 1 | 49227 | U16 | 1 | hours |
| del71_m - Enabling delay in minutes for step 7 of program 1 | 49228 | U16 | 1 | min |
| del71_h - Enabling delay in hours for step 7 of program 1 | 49229 | U16 | 1 | hours |
| del02_m - Enabling delay in minutes for step 0 of program 2 | 49230 | U16 | 1 | min |
| del02_h - Enabling delay in hours for step 0 of program 2 | 49231 | U16 | 1 | hours |
| del12_m - Enabling delay in minutes for step 1 of program 2 | 49232 | U16 | 1 | min |
| del12_h - Enabling delay in hours for step 1 of program 2 | 49233 | U16 | 1 | hours |
| del22_m - Enabling delay in minutes for step 2 of program 2 | 49234 | U16 | 1 | min |
| del22_h - Enabling delay in hours for step 2 of program 2 | 49235 | U16 | 1 | hours |
| del32_m - Enabling delay in minutes for step 3 of program 2 | 49236 | U16 | 1 | min |
| del32_h - Enabling delay in hours for step 3 of program 2 | 49237 | U16 | 1 | hours |
| del42_m - Enabling delay in minutes for step 4 of program 2 | 49238 | U16 | 1 | min |
| del42_h - Enabling delay in hours for step 4 of program 2 | 49239 | U16 | 1 | hours |
| del52_m - Enabling delay in minutes for step 5 of program 2 | 49240 | U16 | 1 | min |
| del52_h - Enabling delay in hours for step 5 of program 2 | 49241 | U16 | 1 | hours |
| del62_m - Enabling delay in minutes for step 6 of program 2 | 49242 | U16 | 1 | min |
| del62_h - Enabling delay in hours for step 6 of program 2 | 49243 | U16 | 1 | hours |
| del72_m - Enabling delay in minutes for step 7 of program 2 | 49244 | U16 | 1 | min |
| del72_h - Enabling delay in hours for step 7 of program 2 | 49245 | U16 | 1 | hours |
| dur01_m - Duration in minutes for step 0 of program 1 | 49246 | U16 | 1 | min |
| dur01_h - Duration in hours for step 0 of program 1 | 49247 | U16 | 1 | hours |
| dur11_m - Duration in minutes for step 1 of program 1 | 49248 | U16 | 1 | min |
| dur11_h - Duration in hours for step 1 of program 1 | 49249 | U16 | 1 | hours |
| dur21_m - Duration in minutes for step 2 of program 1 | 49250 | U16 | 1 | min |
| dur21_h - Duration in hours for step 2 of program 1 | 49251 | U16 | 1 | hours |
| dur31_m - Duration in minutes for step 3 of program 1 | 49252 | U16 | 1 | min |
| dur31_h - Duration in hours for step 3 of program 1 | 49253 | U16 | 1 | hours |
| dur41_m - Duration in minutes for step 4 of program 1 | 49254 | U16 | 1 | min |
| dur41_h - Duration in hours for step 4 of program 1 | 49255 | U16 | 1 | hours |
| dur51_m - Duration in minutes for step 5 of program 1 | 49256 | U16 | 1 | min |
| dur51_h - Duration in hours for step 5 of program 1 | 49257 | U16 | 1 | hours |
| dur61_m - Duration in minutes for step 6 of program 1 | 49258 | U16 | 1 | min |
| dur61_h - Duration in hours for step 6 of program 1 | 49259 | U16 | 1 | hours |
| dur71_m - Duration in minutes for step 7 of program 1 | 49260 | U16 | 1 | min |
| dur71_h - Duration in hours for step 7 of program 1 | 49261 | U16 | 1 | hours |
| dur02_m - Duration in minutes for step 0 of program 2 | 49262 | U16 | 1 | min |
| dur02_h - Duration in hours for step 0 of program 2 | 49263 | U16 | 1 | hours |
| dur12_m - Duration in minutes for step 1 of program 2 | 49264 | U16 | 1 | min |
| dur12_h - Duration in hours for step 1 of program 2 | 49265 | U16 | 1 | hours |
| dur22_m - Duration in minutes for step 2 of program 2 | 49266 | U16 | 1 | min |
| dur22_h - Duration in hours for step 2 of program 2 | 49267 | U16 | 1 | hours |
| dur32_m - Duration in minutes for step 3 of program 2 | 49268 | U16 | 1 | min |
| dur32_h - Duration in hours for step 3 of program 2 | 49269 | U16 | 1 | hours |
| dur42_m - Duration in minutes for step 4 of program 2 | 49270 | U16 | 1 | min |
| dur42_h - Duration in hours for step 4 of program 2 | 49271 | U16 | 1 | hours |
| dur52_m - Duration in minutes for step 5 of program 2 | 49272 | U16 | 1 | min |
| dur52_h - Duration in hours for step 5 of program 2 | 49273 | U16 | 1 | hours |
| dur62_m - Duration in minutes for step 6 of program 2 | 49274 | U16 | 1 | min |
| dur62_h - Duration in hours for step 6 of program 2 | 49275 | U16 | 1 | hours |
| dur72_m - Duration in minutes for step 7 of program 2 | 49276 | U16 | 1 | min |
| dur72_h - Duration in hours for step 7 of program 2 | 49277 | U16 | 1 | hours |
| H21 - Configurability of digital output 1 | 49314 | U16 | 1 | |
| dn1 - Start-up delay of regulator 1 | 49316 | U16 | 1 | secs |
| do1 - Shutdown delay of regulator 1 | 49317 | U16 | 1 | min |
| di1 - Delay between two consecutive starts of regulator 1 | 49318 | U16 | 1 | min |
| dE1 - Start-up delay after the shutdown of regulator 1 | 49319 | U16 | 1 | secs |
| On1 - ON time of regulator 1 due faulty probe | 49320 | U16 | 1 | min |
| OF1 - OFF time of regulator 1 due faulty probe | 49321 | U16 | 1 | min |
| dn2 - Start-up delay of regulator 2 | 49323 | U16 | 1 | secs |
| do2 - Shutdown delay of regulator 2 | 49324 | U16 | 1 | min |
| di2 - Delay between two consecutive starts of regulator 2 | 49325 | U16 | 1 | min |
| dE2 - Start-up delay after the shutdown of regulator 2 | 49326 | U16 | 1 | secs |
| On2 - ON time of regulator 2 due faulty probe | 49327 | U16 | 1 | min |
| OF2 - OFF time of regulator 2 due faulty probe | 49328 | U16 | 1 | min |
| dSi - Value of soft start regulator step | 49329 | U16 | 0.1 | °C/°F |
| Std - Duration of soft start regulator step | 49330 | U16 | 1 | hh/min/secs |
| unt - Unit of measurement for step duration | 49331 | U16 | 1 | |
| SEn - Selects the regulator on which the soft start function must be enabled | 49332 | U16 | 1 | |
| Con - ON time for cyclic regulator output | 49333 | U16 | 1 | min |
| Cof - OFF time for cyclic regulator output | 49334 | U16 | 1 | min |
| Att - Mode of parameter HA1-HA2 and LA-LA2 | 49335 | U16 | 1 | |
| PAO - Temperature alarms disabling time from Power On | 49336 | U16 | 1 | hours |
| SAO - Timeout for 'set point not reached' alarm | 49337 | U16 | 1 | hours |
| tAO - Temperature alarms delay time | 49338 | U16 | 1 | min |
| AOP - Polarity of alarm output | 49339 | U16 | 1 | |
| PtS - Protocol selection | 49341 | U16 | 1 | |
| FAA - Family address | 49342 | U16 | 1 | |
| dEA - Device address | 49343 | U16 | 1 | |
| PtY - Modbus parity bit | 49344 | U16 | 1 | |
| StP - Modbus stop bit | 49345 | U16 | 1 | |
| LOC - Enable keyboard lock | 49346 | U16 | 1 | |
| ndt - Display with decimal point | 49347 | U16 | 1 | |
| Cai - Calibration enabling | 49348 | U16 | 1 | |
| dro - °C/°F selection | 49349 | U16 | 1 | |
| H00 - Type of probe selection | 49350 | U16 | 1 | |
| H02 - Keyboard functions enabling time | 49351 | U16 | 1 | secs |
| H01 - Configure type of regulators | 49352 | U16 | 1 | |
| H06 - Key or aux./light digital input ON with unit OFF | 49353 | U16 | 1 | |
| H08 - Standby operating mode | 49354 | U16 | 1 | |
| H10 - Delay output enabling from Power On | 49355 | U16 | 1 | min |
| H11 - ID configuration | 49356 | U16 | 1 | |
| H13 - Polarity and priority of digital inputs | 49357 | U16 | 1 | |
| H14 - Enabling delay of digital inputs | 49358 | U16 | 1 | min |
| H22 - Configurability of digital output 2 | 49359 | U16 | 1 | |
| H31 - UP button configurability | 49361 | U16 | 1 | |
| H32 - DOWN button configurability | 49362 | U16 | 1 | |
| run - Select PID automatic or manual mode | 49364 | U16 | 1 | |
| Adt - Enable duty cycle parameters adaptation | 49365 | U16 | 1 | |
| tun - Select auto-tuning for hot/cold adjustment | 49366 | U16 | 1 | |
| AtO - Auto-tuning timeout | 49368 | U16 | 1 | hours |
| PrE - Enable pre-tuning | 49370 | U16 | 1 | |
| ASA - Save parameters automatically after auto-tuning | 49371 | U16 | 1 | |
| start01 - Duration of step 0 counted from start or set point reached by program 1 | 49373 | U16 | 1 | |
| start11 - Duration of step 1 counted from start or set point reached by program 1 | 49374 | U16 | 1 | |
| start21 - Duration of step 2 counted from start or set point reached by program 1 | 49375 | U16 | 1 | |
| start31 - Duration of step 3 counted from start or set point reached by program 1 | 49376 | U16 | 1 | |
| start41 - Duration of step 4 counted from start or set point reached by program 1 | 49377 | U16 | 1 | |
| start51 - Duration of step 5 counted from start or set point reached by program 1 | 49378 | U16 | 1 | |
| start61 - Duration of step 6 counted from start or set point reached by program 1 | 49379 | U16 | 1 | |
| start71 - Duration of step 7 counted from start or set point reached by program 1 | 49380 | U16 | 1 | |
| start02 - Duration of step 0 counted from start or set point reached by program 2 | 49381 | U16 | 1 | |
| start12 - Duration of step 1 counted from start or set point reached by program 2 | 49382 | U16 | 1 | |
| start22 - Duration of step 2 counted from start or set point reached by program 2 | 49383 | U16 | 1 | |
| start32 - Duration of step 3 counted from start or set point reached by program 2 | 49384 | U16 | 1 | |
| start42 - Duration of step 4 counted from start or set point reached by program 2 | 49385 | U16 | 1 | |
| start52 - Duration of step 5 counted from start or set point reached by program 2 | 49386 | U16 | 1 | |
| start62 - Duration of step 6 counted from start or set point reached by program 2 | 49387 | U16 | 1 | |
| start72 - Duration of step 7 counted from start or set point reached by program 2 | 49388 | U16 | 1 | |
| reg01 - Regulator active for step 0 of program 1 | 49389 | U16 | 1 | |
| reg11 - Regulator active for step 1 of program 1 | 49390 | U16 | 1 | |
| reg21 - Regulator active for step 2 of program 1 | 49391 | U16 | 1 | |
| reg31 - Regulator active for step 3 of program 1 | 49392 | U16 | 1 | |
| reg41 - Regulator active for step 4 of program 1 | 49393 | U16 | 1 | |
| reg51 - Regulator active for step 5 of program 1 | 49394 | U16 | 1 | |
| reg61 - Regulator active for step 6 of program 1 | 49395 | U16 | 1 | |
| reg71 - Regulator active for step 7 of program 1 | 49396 | U16 | 1 | |
| reg02 - Regulator active for step 0 of program 2 | 49397 | U16 | 1 | |
| reg12 - Regulator active for step 1 of program 2 | 49398 | U16 | 1 | |
| reg22 - Regulator active for step 2 of program 2 | 49399 | U16 | 1 | |
| reg32 - Regulator active for step 3 of program 2 | 49400 | U16 | 1 | |
| reg42 - Regulator active for step 4 of program 2 | 49401 | U16 | 1 | |
| reg52 - Regulator active for step 5 of program 2 | 49402 | U16 | 1 | |
| reg62 - Regulator active for step 6 of program 2 | 49403 | U16 | 1 | |
| reg72 - Regulator active for step 7 of program 2 | 49404 | U16 | 1 | |
| soft01 - Enable soft start for step 0 of program 1 | 49405 | U16 | 1 | |
| soft11 - Enable soft start for step 1 of program 1 | 49406 | U16 | 1 | |
| soft21 - Enable soft start for step 2 of program 1 | 49407 | U16 | 1 | |
| soft31 - Enable soft start for step 3 of program 1 | 49408 | U16 | 1 | |
| soft41 - Enable soft start for step 4 of program 1 | 49409 | U16 | 1 | |
| soft51 - Enable soft start for step 5 of program 1 | 49410 | U16 | 1 | |
| soft61 - Enable soft start for step 6 of program 1 | 49411 | U16 | 1 | |
| soft71 - Enable soft start for step 7 of program 1 | 49412 | U16 | 1 | |
| soft02 - Enable soft start for step 0 of program 2 | 49413 | U16 | 1 | |
| soft12 - Enable soft start for step 1 of program 2 | 49414 | U16 | 1 | |
| soft22 - Enable soft start for step 2 of program 2 | 49415 | U16 | 1 | |
| soft32 - Enable soft start for step 3 of program 2 | 49416 | U16 | 1 | |
| soft42 - Enable soft start for step 4 of program 2 | 49417 | U16 | 1 | |
| soft52 - Enable soft start for step 5 of program 2 | 49418 | U16 | 1 | |
| soft62 - Enable soft start for step 6 of program 2 | 49419 | U16 | 1 | |
| soft72 - Enable soft start for step 7 of program 2 | 49420 | U16 | 1 | |
| rele01 - Enable auxiliary output for step 0 of program 1 | 49421 | U16 | 1 | |
| rele11 - Enable auxiliary output for step 1 of program 1 | 49422 | U16 | 1 | |
| rele21 - Enable auxiliary output for step 2 of program 1 | 49423 | U16 | 1 | |
| rele31 - Enable auxiliary output for step 3 of program 1 | 49424 | U16 | 1 | |
| rele41 - Enable auxiliary output for step 4 of program 1 | 49425 | U16 | 1 | |
| rele51 - Enable auxiliary output for step 5 of program 1 | 49426 | U16 | 1 | |
| rele61 - Enable auxiliary output for step 6 of program 1 | 49427 | U16 | 1 | |
| rele71 - Enable auxiliary output for step 7 of program 1 | 49428 | U16 | 1 | |
| rele02 - Enable auxiliary output for step 0 of program 2 | 49429 | U16 | 1 | |
| rele12 - Enable auxiliary output for step 1 of program 2 | 49430 | U16 | 1 | |
| rele22 - Enable auxiliary output for step 2 of program 2 | 49431 | U16 | 1 | |
| rele32 - Enable auxiliary output for step 3 of program 2 | 49432 | U16 | 1 | |
| rele42 - Enable auxiliary output for step 4 of program 2 | 49433 | U16 | 1 | |
| rele52 - Enable auxiliary output for step 5 of program 2 | 49434 | U16 | 1 | |
| rele62 - Enable auxiliary output for step 6 of program 2 | 49435 | U16 | 1 | |
| rele72 - Enable auxiliary output for step 7 of program 2 | 49436 | U16 | 1 | |
| fine01 - End step 0 of program 1 | 49437 | U16 | 1 | |
| fine11 - End step 1 of program 1 | 49438 | U16 | 1 | |
| fine21 - End step 2 of program 1 | 49439 | U16 | 1 | |
| fine31 - End step 3 of program 1 | 49440 | U16 | 1 | |
| fine41 - End step 4 of program 1 | 49441 | U16 | 1 | |
| fine51 - End step 5 of program 1 | 49442 | U16 | 1 | |
| fine61 - End step 6 of program 1 | 49443 | U16 | 1 | |
| fine71 - End step 7 of program 1 | 49444 | U16 | 1 | |
| fine02 - End step 0 of program 2 | 49445 | U16 | 1 | |
| fine12 - End step 1 of program 2 | 49446 | U16 | 1 | |
| fine22 - End step 2 of program 2 | 49447 | U16 | 1 | |
| fine32 - End step 3 of program 2 | 49448 | U16 | 1 | |
| fine42 - End step 4 of program 2 | 49449 | U16 | 1 | |
| fine52 - End step 5 of program 2 | 49450 | U16 | 1 | |
| fine62 - End step 6 of program 2 | 49451 | U16 | 1 | |
| fine72 - End step 7 of program 2 | 49452 | U16 | 1 | |
| step01 - Number of partial cycle to run for step 0 of program 1 | 49453 | U16 | 1 | |
| step11 - Number of partial cycle to run for step 1 of program 1 | 49454 | U16 | 1 | |
| step21 - Number of partial cycle to run for step 2 of program 1 | 49455 | U16 | 1 | |
| step31 - Number of partial cycle to run for step 3 of program 1 | 49456 | U16 | 1 | |
| step41 - Number of partial cycle to run for step 4 of program 1 | 49457 | U16 | 1 | |
| step51 - Number of partial cycle to run for step 5 of program 1 | 49458 | U16 | 1 | |
| step61 - Number of partial cycle to run for step 6 of program 1 | 49459 | U16 | 1 | |
| step71 - Number of partial cycle to run for step 7 of program 1 | 49460 | U16 | 1 | |
| step02 - Number of partial cycle to run for step 0 of program 2 | 49461 | U16 | 1 | |
| step12 - Number of partial cycle to run for step 1 of program 2 | 49462 | U16 | 1 | |
| step22 - Number of partial cycle to run for step 2 of program 2 | 49463 | U16 | 1 | |
| step32 - Number of partial cycle to run for step 3 of program 2 | 49464 | U16 | 1 | |
| step42 - Number of partial cycle to run for step 4 of program 2 | 49465 | U16 | 1 | |
| step52 - Number of partial cycle to run for step 5 of program 2 | 49466 | U16 | 1 | |
| step62 - Number of partial cycle to run for step 6 of program 2 | 49467 | U16 | 1 | |
| step72 - Number of partial cycle to run for step 7 of program 2 | 49468 | U16 | 1 | |
| AOL - Analog output configuration | 49469 | U16 | 1 | |
| AOF - Operation mode of analogue output | 49470 | U16 | 1 | |
| AOS - Operation mode of analogue output with probe error | 49471 | U16 | 1 | |
| cH - Derivative PID weighting set point H | 49548 | U16 | 1 | |
| cC - Derivative PID weighting set point C | 49551 | U16 | 1 | |
| FunH - Select regulation algorithm H | 49552 | U16 | 1 | |
| FunC - Select regulation algorithm C | 49554 | U16 | 1 |
| terminals | RS485 cable shielded and twisted (e.g.: Belden cable model 8762) |
| connector | 5-path connector TTL cable (30cm) |
| wiring notes | Bus Adapter BA150 |
| max registers/read | 60 |
| broadcast | supported |
| protocol notes | Parameters belonging to two different non-consecutive blocks cannot be read using a single command. |
| identification notes | Field code 0: Manufacturer ID ('Invensys'), Field code 1: Instrument model ID ('003E_000A'), Field code 2: Instrument version ID ('00F8_0011') |
| FC 43 device ID | supported |
| doc revision | 2010/04/0 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.