Eliwell ID 985 refrigeration controller

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Operating differential6146U161
Set point offset6148I161
End of defrost temperature6150I161
Compressor output activation/deactivation time before defrosting6152I161
Evaporator fan shut-down temperature6154I161
Evaporator fan start-up temperature6156I161
Evaporator fan operating differential.6158U161
alarm differential6160U161
Temperature alarm exclusion time after defrost cycle6162U161
Cell probe calibration6164I161
Calibration of evaporator probe6166I161
Calibration of probe6168I161
Minimum value that can be displayed6170I161
Maximum value that can be displayed6172I161
Configurability and polarity digital input 16174I161
Map code6176U161
Set point6178I161
Maximum settable Set point value6180I161
Minimum settable Set point value6182I161
Maximum alarm threshold6184I161
Minimum alarm threshold6186I161
Alarm set point for 3rd probe6196I161
Alarm differential 3rd probe6198I161
Configurability and polarity digital input 26200I161
End of defrost temperature 2nd evaporator6366I161
Condenser fan activation set point6370I161
Condenser fan operating differential.6372I161
Minimum compressor output activation time6715U161
Maximum compressor output activation time6716U161
load switching off enabled when door switch is switched on6717U161
Delay in enabling digital inputs6718U161
Compressor output ON time if control probe faulty6719U161
Compressor output OFF time if control probe faulty6720U161
Delay in activating compressor output after start-up.6721U161
Delay in activating compressor output after shut-down.6722U161
Delay between two consecutive switch-ons of compressor output6723U161
Output in activating output after power-on6724U161
Type of defrost6725U161
Unit of measurement for defrost times6726U161
Unit of measurement for duration of defrosting6727U161
Defrosting time count mode6728U161
Delay in activating defrost cycle after start-up6729U161
Defrost time out6730U161
Defrost activation request after power-on6731U161
Time before defrosting during which the compressor output is not activated6732U161
FSt parameter mode (absolute or relative)6733U161
Delay in enabling evaporator fans after defrost cycle6734U161
Dripping time6735U161
Exclusion of evaporator fans during defrost cycle6736U161
Status of evaporator fans when compressor output OFF6737U161
Status of evaporator fans when door is open6738U161
Delay in shut down of evaporator fans after compressor is disabled6739U161
Time evaporator fans are ON in duty cycle mode6740U161
Time evaporator fans are OFF in duty cycle mode6741U161
Device address6742U161
Family address6743U161
HAL and LAL parameter modes (absolute or relative)6744U161
alarm excluded at power on6745U161
High and low temperature alarm exclusion time after door is closed6746U161
Alarm exclusion time when door is open6747U161
Temperature alarm signal delay time6748U161
Alarm signal for defrost ended timed out6749U161
External alarm disables controllers6750U161
Polarity of alarm output6751U161
Keyboard lock enabled6753U161
Display with decimal point6754U161
Intervention of calibration6755U161
Locked Resources at end of defrosting6756U161
Display of fundamental state6757U161
Time for activation of functions from keyboard6758U161
Digital output 1 configurability6759U161
Digital output 2 configurability6760U161
Digital output 3 configurability6761U161
Digital output 4 configurability6762U161
UP button configurability6764U161
DOWN button configurability6765U161
ESC button configurability6766U161
inversion of ST1 with ST2 enabled6767U161
Presence of cell probe6768U161
Presence of evaporator probe6769U161
Presence of 3rd probe6770U161
Interval between defrosts6771U161
Probe enabled for temperature alarm signalling (probe 1 and/or 3)6776U161
Time out for display lock after end of defrosting6777U161
Aux/light button or Digital Input active when instrument is off6778U161
Operating mode on stand-by6779U161
Light relay enable from door switch6780U161
Delay in switching off of light relay after door is closed6781U161
switching off of cell light button-enabled during delay set in parameter dLt6782U161
Password 1 value6783U161
Password 2 value6784U161
Selection of NTC/PTC type of analogue input6785U161
°C or °F selection6786U161
Hours of start of 1st daily defrost6788U161
Hours of start of 2nd daily defrost6789U161
Hours of start of 3rd daily defrost6790U161
Hours of start of 4th daily defrost6791U161
Hours of start of 5th daily defrost6792U161
Hours of start of 6th daily defrost6793U161
Hours of start of 7th daily defrost6794U161
Hours of start of 8th daily defrost6795U161
Minutes of start of 1st daily defrost6796U161
Minutes of start of 2nd daily defrost6797U161
Minutes of start of 3rd daily defrost6798U161
Minutes of start of 4th daily defrost6799U161
Minutes of start of 5th daily defrost6800U161
Minutes of start of 6th daily defrost6801U161
Minutes of start of 7th daily defrost6802U161
Minutes of start of 8th daily defrost6803U161
Hours of start of 1st festive defrost6804U161
Hours of start of 2nd festive defrost6805U161
Hours of start of 3rd festive defrost6806U161
Hours of start of 4th festive defrost6807U161
Hours of start of 5th festive defrost6808U161
Hours of start of 6th festive defrost6809U161
Hours of start of 7th festive defrost6810U161
Hours of start of 8th festive defrost6811U161
Minutes of start of 1st festive defrost6812U161
Minutes of start of 2nd festive defrost6813U161
Minutes of start of 3rd festive defrost6814U161
Minutes of start of 4th festive defrost6815U161
Minutes of start of 5th festive defrost6816U161
Minutes of start of 6th festive defrost6817U161
Minutes of start of 7th festive defrost6818U161
Minutes of start of 8th festive defrost6819U161
Enables functions during events on 1st day6820U161
Enables functions during events on 2nd day6821U161
Enables functions during events on 3rd day6822U161
Enables functions during events on 4th day6823U161
Enables functions during events on 5th day6824U161
Enables functions during events on 6th day6825U161
Enables functions during events on 7th day6826U161
Enables functions during events every day6827U161
Duration of event 1st day6828U161
Duration of event 2nd day6829U161
Duration of event 3rd day6830U161
Duration of event 4th day6831U161
Duration of event 5th day6832U161
Duration of event 6th day6833U161
Duration of event 7th day6834U161
Duration of daily event6835U161
Enables daily or holiday defrosting 1st day6836U161
Enables daily or holiday defrosting 2nd day6837U161
Enables daily or holiday defrosting 3rd day6838U161
Enables daily or holiday defrosting 4th day6839U161
Enables daily or holiday defrosting 5th day6840U161
Enables daily or holiday defrosting 6th day6841U161
Enables daily or holiday defrosting 7th day6842U161
Hour of start of event 1st day6844U161
Hour of start of event 2nd day6845U161
Hour of start of event 3rd day6846U161
Hour of start of event 4th day6847U161
Hour of start of event 5th day6848U161
Hour of start of event 6th day6849U161
Hour of start of event 7th day6850U161
Hour of start of event every day6851U161
minutes of start of event 1st day6852U161
minutes of start of event 2nd day6853U161
minutes of start of event 3rd day6854U161
minutes of start of event 4th day6855U161
minutes of start of event 5th day6856U161
minutes of start of event 6th day6857U161
minutes of start of event 7th day6858U161
Minutes of start of event every day6859U161
Selection of Master, Slave, Echo6860U161
Number of Slaves in network(refers to Master)6861U161
Presence of local Echoes referring to single slave6862U161
Simultaneous or sequential defrosting6863U161
Distributed display (refers to slave)6864U161
Activation of network functions6865U161
Locked Resources at end of defrosting6866U161
Presence of RTC6867U161
Defrost start-up mode for applications with two evaporators6876U161
Defrost time out 2nd evaporator6877U161
Number of errors allowed per maximum/minimum pressure switch input6880U161
Minimum/maximum pressure switch error count time6881U161
Condenser fan start-up delay after defrosting6886U161
exclusion of condenser fans during defrosting6887U161
Display on eco6888U161
FORCED behaviour from digital input6889U161
enables forced behaviour from digital input6890U161
delay in enabling compressor after activation of digital input6891U161
delay in enabling fans after activation of digital input6892U161
Modbus Parity Bit6893U161
Modbus Stop Bit6894U161
Analogue input 18504I161
Analogue input 28506I161
Analogue input 38508I161
Analogue input 1 (control) 18510I161
Analogue input 2 (control) 18512I161
Analogue input 3 (control) 18514I161
Command enabling timeout from serial.8548U161
Status Word 87638763U161
Control Word 88018801U161
Control Word 88028802U161
Status Word 88148814U161
Status Word 88158815U161
Status Word 88188818U161
Status Word 88238823U161
Status Word 88268826U161
Status Word 90099009U161

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 03,16,43; The baud rate must be set to 9600 bauds. Parity is configurable via parameter PtY (default none), and stop bits via parameter StP (default 1b).

bench facts as documented (unverified)
terminals5-path connector TTL cable (30cm)
connector5-path connector TTL cable
shield/groundshielded and twisted (e.g.: Belden cable model 8762)
wiring notesBus Adapter BA150 used for RS485 connection.
max registers/read60
broadcastsupported
protocol notesA maximum of 60 consecutive registers can be read or written. Parameters belonging to two different non-consecutive blocks cannot be read using a single command.
identification notesDevice ID fields can be read using Modbus command 43: Field 0 (Manufacturer ID = 'Invensys'), Field 1 (Instrument model ID = '0028_0402'), Field 2 (Instrument version ID = '00E2_0001').
FC 43 device IDsupported
doc revision2005/03/0
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: The baud rate must be set to 9600 bauds. Parity is configurable via parameter PtY (default none), and stop bits via parameter StP (default 1b). — confirmed by Eliwell ID 985/E LX Modbus Serial Communication Protocol manual
  • confirmed: Device ID fields can be read using Modbus command 43: Field 0 (Manufacturer ID = 'Invensys'), Field 1 (Instrument model ID = '0028_0402'), Field 2 (Instrument version ID = '00E2_0001'). — confirmed by Eliwell ID 985/E LX Modbus Serial Communication Protocol manual
  • confirmed: set_point @ 6178, operating_differential @ 6146, max_set_point @ 6180, min_set_point @ 6182, end_of_defrost_temperature @ 6150, end_of_defrost_temperature_2nd_evap @ 6366, evaporator_fan_shutdown_temperature @ 6154, evaporator_fan_startup_temperature @ 6156, analogue_input_1 @ 8504, analogue_input_2 @ 8506, analogue_input_3 @ 8508, analogue_input_1_control @ 8510, analogue_input_2_control @ 8512, analogue_input_3_control @ 8514, status_digital_inputs @ 9009, alarms_1 @ 8814, alarms_2 @ 8815, controller_status @ 8818, relay_status @ 8763 — confirmed by Eliwell ID 985/E LX Modbus Serial Communication Protocol manual

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.