Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| remote_on_off | 179 | U16 | 1 | |
| remove_reset_by_hand_latch_state | 180 | U16 | 1 | |
| heartbeat_counter | 299 | U16 | 1 | s |
| grid_reactive_power | 300 | F32LE | 1 | VAr |
| grid_voltage | 302 | F32LE | 1 | V |
| grid_active_power | 304 | F32LE | 1 | W |
| grid_current | 306 | F32LE | 1 | A |
| global_state | 1049 | U16 | 1 | |
| alarm_state | 1050 | U16 | 1 | |
| dc_dc_converter_state | 1051 | U16 | 1 | |
| dc_ac_converter_state | 1052 | U16 | 1 | |
| derating_state | 1053 | U16 | 1 | |
| daily_energy | 1069 | U32BE | 1 | Wh |
| total_energy | 1071 | U32BE | 1 | Wh |
| partial_energy | 1073 | U32BE | 1 | Wh |
| weekly_energy | 1075 | U32BE | 1 | Wh |
| monthly_energy | 1077 | U32BE | 1 | Wh |
| yearly_energy | 1079 | U32BE | 1 | Wh |
| mean_grid_voltage | 1089 | F32LE | 1 | V |
| mean_output_current | 1091 | F32LE | 1 | A |
| output_active_power_instantaneous | 1093 | F32LE | 1 | W |
| output_active_power_absolute_peak | 1095 | F32LE | 1 | W |
| output_active_power_daily_peak | 1097 | F32LE | 1 | W |
| output_active_power_feedback | 1099 | F32LE | 1 | W |
| reactive_power_feedback | 1101 | F32LE | 1 | VAr |
| power_factor_feedback | 1103 | F32LE | 1 | |
| mean_grid_frequency | 1105 | F32LE | 1 | Hz |
| active_power_dc_input_1 | 1107 | F32LE | 1 | W |
| voltage_dc_input_1 | 1109 | F32LE | 1 | V |
| current_dc_input_1 | 1111 | F32LE | 1 | A |
| active_power_dc_input_2 | 1113 | F32LE | 1 | W |
| voltage_dc_input_2 | 1115 | F32LE | 1 | V |
| current_dc_input_2 | 1117 | F32LE | 1 | A |
| internal_temperature | 1119 | F32LE | 1 | °C |
| inverter_temperature | 1121 | F32LE | 1 | °C |
| isolation_resistance | 1125 | F32LE | 1 | MΩ |
| max_leakage_current | 1127 | F32LE | 1 | A |
| active_power_dc_input_3 | 1129 | F32LE | 1 | W |
| voltage_dc_input_3 | 1131 | F32LE | 1 | V |
| current_dc_input_3 | 1133 | F32LE | 1 | A |
| terminals | RS485-1, RS485-2 |
| wiring notes | Interface: RS-485 (half duplex) |
| response timeout | 100 ms |
| broadcast | supported |
| protocol notes | Any Modbus request on 32 bit data type (SF32 and U32) must include both registers otherwise the inverter will trigger an exception with code 2. Any Modbus request on Ascii String must include all registers of the block. |
| model register | 1021 |
| serial register | 1008 |
| firmware register | 3651 |
| identification notes | Model register is 1021 (Data Address 1022), Serial register is 1008 (Data Address 1009), Firmware registers are 3651-3653 (Data Addresses 3652-3654) |
| power | Nominal apparent power: 50 kVA / 60 kVA, Nominal Active Power: 50 kW / 60 kW |
| environment | Ambiente Temperature: <= 50°C (TRIO-50), <= 45°C (TRIO-60) |
| doc revision | Version Gt03.0, Effective: 31/01/2018 Rev. 3.0 |
| firmware applicability | Minimum inverter update version: 1711C for Europe, 1711D for USA, 1708B for Japan |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.