Fireye MicroM flame safeguard

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
status0U161
msgn1U161
gstat2U161
timer3U161
flame4U161
logstat5U161
inputs6U161
outputs7U161
sysmins8U32BE1minutes
bnrmins10U32BE1minutes
cycles12U32BE1cycles
lockout_count14U161
lockout_history15U161
devtyp21U161
amptyp22U161
progtyp23U161
flame_signal_average_ptfi24U161
flame_signal_average_auto25U161

link settings as documented (unverified): RTU; default 4800 8N1; unit ID 0; FC 03; The format of the data is 4800, N, 8, 1 meaning 4800 baud, no parity, and 1 stop bit. Due to the RS485 format, the communication format is considered half-duplex.

⚠ WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state or other government. Inappropriate application of this product could result in an unsafe condition hazardous to life and property. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminationThe shield at the source end of the cable of the multi-drop connection can then be terminated to ground.
shield/groundProper twisted shielded pair cable must be utilized. In a multi-drop system, the shields should be tied together within a cabinet and not to any ground point.
wiring notesWhen interfacing Fireye controls to a communication system, be it an E500, PLC or other microprocessor based device, ferrite cores should also be utilized.
protocol notesIt is suggested that repeated polling interval not be less than 200 mSec per request. Requesting data such as burner minutes, system minutes and burner cycles be kept at a minimum due to the amount of processing time required to gather that data.
model register21
identification notesMessage 21 (DEVTYP) returns programmer device type (5=EP, 6=EPD, 7=MicroM). Message 23 (PROGTYP) returns programmer type.
power120 VAC (min. 102, max. 132) 50/60 Hz for MEC1XX, MEC3XX; 230 VAC (min. 196, max. 253) 50/60 Hz for MEC2XX, MEC4XX. Power Consumption: 12 VA (Operating)
environmentOperating Temperature: -40°F (-40°C) to 140°F (60°C)
certificationscULus Listed, FM Approved
doc revisionMC-5000, MAY 9, 2008
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms defaults (4800 baud, no parity, 1 stop bit, half-duplex RS485) — confirmed by Fireye MicroM Manual (MC-5000, May 9, 2008) [2.2.1] and Modbus Memory Map document
  • confirmed: default unit ID is 0 — confirmed by Fireye MicroM Manual (MC-5000, May 9, 2008) stating 'As shipped the default address is 0'
  • confirmed: operating temperature range (-40°F to 140°F) — confirmed by Fireye MicroM Manual (MC-5000, May 9, 2008)
  • confirmed: power supply specifications (120 VAC for MEC1XX/MEC3XX, 230 VAC for MEC2XX/MEC4XX, 12 VA consumption) — confirmed by Fireye MicroM Manual (MC-5000, May 9, 2008)
  • confirmed: physical installation notes (use of ferrite cores, twisted shielded pair cable, shield grounding at source end only) — confirmed by Fireye MicroM Manual (MC-5000, May 9, 2008)
  • confirmed: polling interval recommendation (not less than 200 mSec per request) — confirmed by Fireye MicroM Manual (MC-5000, May 9, 2008)
  • confirmed: register map addresses (0-based addresses for status, msgn, gstat, timer, flame, logstat, inputs, outputs, sysmins, bnrmins, cycles, lockout_count, lockout_history, devtyp, amptyp, progtyp, flame_signal_average_ptfi, flame_signal_average_auto) — confirmed by Fireye Modbus Memory Map document

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.