Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| frequency_command_pu | 1793 | I16 | 1 | |
| frequency_command_hz | 1797 | U16 | 0.01 | |
| operation_command | 1798 | U16 | 1 | |
| frequency_reference_pu | 2049 | I16 | 1 | |
| frequency_reference_hz | 2053 | U16 | 0.01 | Hz |
| output_frequency_pu | 2054 | I16 | 1 | |
| torque_real_value | 2055 | I16 | 0.01 | % |
| torque_current | 2056 | I16 | 0.01 | % |
| output_frequency_hz | 2057 | U16 | 0.01 | Hz |
| input_power | 2058 | U16 | 0.01 | % |
| output_current_effective_value | 2059 | U16 | 0.01 | % |
| output_voltage_effective_value | 2060 | U16 | 1 | V |
| operation_command_m | 2061 | U16 | 1 | |
| operation_status | 2062 | U16 | 1 | |
| cumulative_operation_time | 2068 | U16 | 1 | h |
| dc_link_circuit_voltage | 2069 | U16 | 1 | V |
| motor_temperature | 2070 | I16 | 1 | °C |
| heat_sink_temperature | 2110 | U16 | 1 | °C |
| load_factor | 2111 | I16 | 0.01 | % |
| motor_output | 2112 | I16 | 0.01 | % |
| operation_status_w | 3841 | U16 | 1 | |
| frequency_reference_w | 3842 | U16 | 0.01 | Hz |
| output_frequency_before_slip_compensation | 3843 | U16 | 0.01 | Hz |
| output_frequency_after_slip_compensation | 3844 | U16 | 0.01 | Hz |
| output_voltage_w | 3846 | U16 | 0.1 | V |
| torque_w | 3847 | I16 | 1 | % |
| dc_link_circuit_voltage_w | 3911 | U16 | 1 | |
| heat_sink_maximum_temperature | 3913 | U16 | 1 |
⚠ If alarm resetting is performed with the operation command (S06) uncleared, the inverter will start to operate just upon alarm resetting. Before alarm resetting, confirm that the operation command is cleared. Otherwise, an accident may result. — Starkest reads only; we never write a control register.
| terminals | RJ-45 connector or terminal block |
| A/B polarity | DX+ is positive, DX- is negative |
| termination | A terminating resistor of 112 ohms is incorporated. Connection/release is switched by switch. |
| connector | 8-wire RJ-45 connector or terminal block |
| isolation | The RS-232C side of the converter must be isolated from the RS-485 side. |
| shield/ground | SD terminal for relaying the shield of the shielded cable, insulated from other circuits. |
| max registers/read | 50 |
| broadcast | supported |
| model register | M23 |
| firmware register | M25 |
| power | Vcc 5V power source for the keypad is connected to the RJ-45 connector (via pins 1, 2, 7, and 8). |
| certifications | Compliant with EMC Directives (when using KB-STP-01K) |
| doc revision | 24A7-E-0082 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.