Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Write in non-volatile memory (FIX execution) | 0 | U16 | 1 | |
| PID/FUZZY/SELF selection | 1 | U16 | 1 | |
| SV value set on face panel | 2 | U16 | 1 | |
| Control RUN/standby | 3 | U16 | 1 | |
| Alarm 2 ON/OFF | 4 | U16 | 1 | |
| P | 5 | U16 | 1 | |
| I | 6 | U16 | 1 | |
| D | 7 | U16 | 1 | |
| Alarm 1 output | 8 | U16 | 1 | |
| Alarm 2 output | 9 | U16 | 1 | |
| Dead band | 10 | I16 | 1 | |
| HB alarm relay output | 11 | U16 | 1 | |
| Alarm 1 ON/OFF | 12 | U16 | 1 | |
| Alarm 2 ON/OFF | 13 | U16 | 1 | |
| SV offset | 14 | I16 | 1 | |
| HB alarm relay output | 15 | U16 | 1 | |
| Temperature unit | 16 | U16 | 1 | |
| Input scale lower limit | 17 | I16 | 1 | |
| Input scale upper limit | 18 | I16 | 1 | |
| Decimal point place | 19 | U16 | 1 | |
| Input filter time constant | 21 | U16 | 1 | |
| RCJ yes/no | 22 | U16 | 1 | |
| MV limit kind | 23 | U16 | 1 | |
| Output 1 lower limit | 24 | I16 | 1 | |
| Output 1 upper limit | 25 | I16 | 1 | |
| Output 2 lower limit | 26 | I16 | 1 | |
| Output 2 upper limit | 27 | I16 | 1 | |
| Set value (SV) lower limit | 30 | U16 | 1 | |
| Set value (SV) upper limit | 31 | U16 | 1 | |
| Heater burnout alarm set value | 38 | U16 | 1 | |
| Setting lock | 39 | U16 | 1 | |
| Alarm 1 type | 40 | U16 | 1 | |
| Alarm 2 type | 41 | U16 | 1 | |
| Alarm 1 set value or alarm 1 lower limit set value | 43 | I16 | 1 | |
| Alarm 2 set value or alarm 2 lower limit set value | 44 | I16 | 1 | |
| Alarm 1 upper limit set value | 46 | I16 | 1 | |
| Alarm 2 upper limit set value | 47 | I16 | 1 | |
| Alarm 1 hysteresis | 49 | U16 | 1 | |
| Alarm 2 hysteresis | 50 | U16 | 1 | |
| Alarm 1 ON-delay set value | 52 | U16 | 1 | |
| Alarm 2 ON-delay set value | 53 | U16 | 1 | |
| Ramp/soak No. 1 target value | 56 | U16 | 1 | |
| Ramp/soak No. 2 target value | 57 | U16 | 1 | |
| Ramp/soak No. 3 target value | 58 | U16 | 1 | |
| Ramp/soak No. 4 target value | 59 | U16 | 1 | |
| Ramp/soak No. 5 target value | 60 | U16 | 1 | |
| Ramp/soak No. 6 target value | 61 | U16 | 1 | |
| Ramp/soak No. 7 target value | 62 | U16 | 1 | |
| Ramp/soak No. 8 target value | 63 | U16 | 1 | |
| Ramp/soak No. 1 ramp time | 64 | U16 | 1 | |
| Ramp/soak No. 1 soak time | 65 | U16 | 1 | |
| Ramp/soak No. 2 ramp time | 66 | U16 | 1 | |
| Ramp/soak No. 2 soak time | 67 | U16 | 1 | |
| Ramp/soak No. 3 ramp time | 68 | U16 | 1 | |
| Ramp/soak No. 3 soak time | 69 | U16 | 1 | |
| Ramp/soak No. 4 ramp time | 70 | U16 | 1 | |
| Ramp/soak No. 4 soak time | 71 | U16 | 1 | |
| Ramp/soak No. 5 ramp time | 72 | U16 | 1 | |
| Ramp/soak No. 5 soak time | 73 | U16 | 1 | |
| Ramp/soak No. 6 ramp time | 74 | U16 | 1 | |
| Ramp/soak No. 6 soak time | 75 | U16 | 1 | |
| Ramp/soak No. 7 ramp time | 76 | U16 | 1 | |
| Ramp/soak No. 7 soak time | 77 | U16 | 1 | |
| Ramp/soak No. 8 ramp time | 78 | U16 | 1 | |
| Ramp/soak No. 8 soak time | 79 | U16 | 1 | |
| Ramp/soak mode | 80 | U16 | 1 | |
| Ramp/soak command | 81 | U16 | 1 | |
| Ramp/soak pattern selection | 82 | U16 | 1 | |
| PV stable range | 84 | U16 | 1 | |
| Communication DI action request | 86 | U16 | 1 | |
| Control action type code | 87 | U16 | 1 | |
| Output proportional cycle (output 1) | 88 | U16 | 1 | |
| Output proportional cycle (output 2) | 89 | U16 | 1 | |
| Alarm 1 option function | 91 | U16 | 1 | |
| Alarm 2 option function | 92 | U16 | 1 | |
| DI1 action setting | 94 | U16 | 1 | |
| Hysteresis mode setting | 96 | U16 | 1 | |
| User zero adjustment | 98 | I16 | 1 | |
| User span adjustment | 99 | I16 | 1 | |
| DSP1 | 100 | U16 | 1 | |
| DSP2 | 101 | U16 | 1 | |
| DSP3 | 102 | U16 | 1 | |
| DSP4 | 103 | U16 | 1 | |
| DSP5 | 104 | U16 | 1 | |
| DSP6 | 105 | U16 | 1 | |
| DSP7 | 106 | U16 | 1 | |
| DSP8 | 107 | U16 | 1 | |
| DSP9 | 108 | U16 | 1 | |
| DSP10 | 109 | U16 | 1 | |
| DSP11 | 110 | U16 | 1 | |
| DSP12 | 111 | U16 | 1 | |
| DSP13 | 112 | U16 | 1 | |
| Non-volatile memory write-in (FIX execution) | 1000 | U16 | 1 | |
| Process value (PV) | 1000 | I16 | 1 | |
| PID/FUZZY/SELF selection | 1001 | U16 | 1 | |
| Currently used set value (SV) | 1001 | I16 | 1 | |
| SV value controlled on face panel | 1002 | I16 | 1 | |
| Currently used deviation (DV) | 1002 | I16 | 1 | |
| Control RUN/standby | 1003 | U16 | 1 | |
| MV (output 1) | 1003 | I16 | 0.01 | % |
| Auto tuning command | 1004 | U16 | 1 | |
| MV (output 2) | 1004 | I16 | 0.01 | % |
| P | 1005 | U16 | 0.1 | % |
| Station No. | 1005 | U16 | 1 | |
| I | 1006 | U16 | 0.1 | sec |
| Alarm status | 1006 | U16 | 1 | |
| D | 1007 | U16 | 0.1 | sec |
| Input/main unit abnormal status | 1007 | U16 | 1 | |
| Hysteresis range at two-position control | 1008 | U16 | 1 | |
| Ramp/soak current running position | 1008 | U16 | 1 | |
| COOL | 1009 | U16 | 1 | |
| Dead band | 1010 | I16 | 1 | |
| Anti-reset windup | 1011 | I16 | 1 | |
| Output convergence value | 1012 | I16 | 1 | |
| PV shift | 1013 | I16 | 1 | |
| SV offset | 1014 | I16 | 1 | |
| Input type code | 1015 | U16 | 1 | |
| Temperature unit | 1016 | U16 | 1 | |
| Input scale lower limit | 1017 | I16 | 1 | |
| Input scale upper limit | 1018 | I16 | 1 | |
| Decimal point place | 1019 | U16 | 1 | |
| Input filter time constant | 1021 | U16 | 1 | |
| RCJ yes/no | 1022 | U16 | 1 | |
| MV limit kind | 1023 | U16 | 1 | |
| Output 1 lower limit | 1024 | I16 | 1 | |
| Output 1 upper limit | 1025 | I16 | 1 | |
| Output 2 lower limit | 1026 | I16 | 1 | |
| Output 2 upper limit | 1027 | I16 | 1 | |
| Set value (SV) lower limit | 1030 | I16 | 1 | |
| Set value (SV) upper limit | 1031 | I16 | 1 | |
| Heater burnout alarm set value | 1038 | U16 | 1 | |
| Setting lock | 1039 | U16 | 1 | |
| Alarm 1 type | 1040 | U16 | 1 | |
| Alarm 2 type | 1041 | U16 | 1 | |
| Alarm 1 set value or alarm 1 lower limit set value | 1043 | I16 | 1 | |
| Alarm 2 set value or alarm 2 lower limit set value | 1044 | I16 | 1 | |
| Alarm 1 upper limit set value | 1046 | I16 | 1 | |
| Alarm 2 upper limit set value | 1047 | I16 | 1 | |
| Alarm 1 hysteresis | 1049 | U16 | 1 | |
| Alarm 2 hysteresis | 1050 | U16 | 1 | |
| Alarm 1 ON-delay set value | 1052 | U16 | 1 | |
| Alarm 2 ON-delay set value | 1053 | U16 | 1 | |
| Ramp/soak No. 1 target value | 1056 | I16 | 1 | |
| Ramp/soak No. 2 target value | 1057 | I16 | 1 | |
| Ramp/soak No. 3 target value | 1058 | I16 | 1 | |
| Ramp/soak No. 4 target value | 1059 | I16 | 1 | |
| Ramp/soak No. 5 target value | 1060 | I16 | 1 | |
| Ramp/soak No. 6 target value | 1061 | I16 | 1 | |
| Ramp/soak No. 7 target value | 1062 | I16 | 1 | |
| Ramp/soak No. 8 target value | 1063 | I16 | 1 | |
| Ramp/soak No. 1 ramp time | 1064 | U16 | 1 | |
| Ramp/soak No. 1 soak time | 1065 | U16 | 1 | |
| Ramp/soak No. 2 ramp time | 1066 | U16 | 1 | |
| Ramp/soak No. 2 soak time | 1067 | U16 | 1 | |
| Ramp/soak No. 3 ramp time | 1068 | U16 | 1 | |
| Ramp/soak No. 3 soak time | 1069 | U16 | 1 | |
| Ramp/soak No. 4 ramp time | 1070 | U16 | 1 | |
| Ramp/soak No. 4 soak time | 1071 | U16 | 1 | |
| Ramp/soak No. 5 ramp time | 1072 | U16 | 1 | |
| Ramp/soak No. 5 soak time | 1073 | U16 | 1 | |
| Ramp/soak No. 6 ramp time | 1074 | U16 | 1 | |
| Ramp/soak No. 6 soak time | 1075 | U16 | 1 | |
| Ramp/soak No. 7 ramp time | 1076 | U16 | 1 | |
| Ramp/soak No. 7 soak time | 1077 | U16 | 1 | |
| Ramp/soak No. 8 ramp time | 1078 | U16 | 1 | |
| Ramp/soak No. 8 soak time | 1079 | U16 | 1 | |
| Ramp/soak mode | 1080 | U16 | 1 | |
| Ramp/soak command | 1081 | U16 | 1 | |
| Ramp/soak pattern selection | 1082 | U16 | 1 | |
| PV stable range | 1084 | I16 | 1 | |
| Communication DI action request | 1086 | U16 | 1 | |
| Control action type code | 1087 | U16 | 1 | |
| Output proportional cycle (output 1) | 1088 | U16 | 1 | |
| Output proportional cycle (output 2) | 1089 | U16 | 1 | |
| Alarm 1 option function | 1091 | U16 | 1 | |
| Alarm 2 option function | 1092 | U16 | 1 | |
| DI1 action setting | 1094 | U16 | 1 | |
| Hysteresis mode setting | 1096 | U16 | 1 | |
| User zero adjustment | 1098 | I16 | 1 | |
| User span adjustment | 1099 | I16 | 1 | |
| DSP1 | 1100 | U16 | 1 | |
| DSP2 | 1101 | U16 | 1 | |
| DSP3 | 1102 | U16 | 1 | |
| DSP4 | 1103 | U16 | 1 | |
| DSP5 | 1104 | U16 | 1 | |
| DSP6 | 1105 | U16 | 1 | |
| DSP7 | 1106 | U16 | 1 | |
| DSP8 | 1107 | U16 | 1 | |
| DSP9 | 1108 | U16 | 1 | |
| DSP10 | 1109 | U16 | 1 | |
| DSP11 | 1110 | U16 | 1 | |
| DSP12 | 1111 | U16 | 1 | |
| DSP13 | 1112 | U16 | 1 |
⚠ For avoiding electric shock and malfunctions, do not turn on the power supply until all wiring have been completed. — Starkest reads only; we never write a control register.
| terminals | 7 (+), 8 (-) |
| A/B polarity | 7 is +, 8 is - |
| termination | Both ends of the cable should be terminated with terminating resistors 100 ohm 1/2W |
| connector | Terminal block |
| isolation | Functional isolation between transmission circuit and others (withstand voltage: 500V AC) |
| shield/ground | The shield wire of the cable should be grounded at one place on the master station unit side. |
| wiring notes | Recommended cable: UL2464, UL2448, etc. Recommended noise filter: ZRAC2203-11/TDK |
| max registers/read | 60 |
| broadcast | not supported |
| protocol notes | While the data is being written in non-volatile memory after write via communication, the next write is attempted and will result in no response. |
| FC 43 device ID | not supported |
| doc revision | INP-TN512642a-E |
⚠ disputed: terminals: "7 (+), 8 (-)" and polarity: "7 is +, 8 is -" — disputed by the official manual [3.4.1]. This terminal allocation is only correct for the PXR4 model. The PXR3 uses terminals 15 (+) and 14 (-), while the PXR5 and PXR9 use terminals 1 (+) and 2 (-).
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.