device library

Fuji PXR temperature controller

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
Write in non-volatile memory (FIX execution)0U161
PID/FUZZY/SELF selection1U161
SV value set on face panel2U161
Control RUN/standby3U161
Alarm 2 ON/OFF4U161
P5U161
I6U161
D7U161
Alarm 1 output8U161
Alarm 2 output9U161
Dead band10I161
HB alarm relay output11U161
Alarm 1 ON/OFF12U161
Alarm 2 ON/OFF13U161
SV offset14I161
HB alarm relay output15U161
Temperature unit16U161
Input scale lower limit17I161
Input scale upper limit18I161
Decimal point place19U161
Input filter time constant21U161
RCJ yes/no22U161
MV limit kind23U161
Output 1 lower limit24I161
Output 1 upper limit25I161
Output 2 lower limit26I161
Output 2 upper limit27I161
Set value (SV) lower limit30U161
Set value (SV) upper limit31U161
Heater burnout alarm set value38U161
Setting lock39U161
Alarm 1 type40U161
Alarm 2 type41U161
Alarm 1 set value or alarm 1 lower limit set value43I161
Alarm 2 set value or alarm 2 lower limit set value44I161
Alarm 1 upper limit set value46I161
Alarm 2 upper limit set value47I161
Alarm 1 hysteresis49U161
Alarm 2 hysteresis50U161
Alarm 1 ON-delay set value52U161
Alarm 2 ON-delay set value53U161
Ramp/soak No. 1 target value56U161
Ramp/soak No. 2 target value57U161
Ramp/soak No. 3 target value58U161
Ramp/soak No. 4 target value59U161
Ramp/soak No. 5 target value60U161
Ramp/soak No. 6 target value61U161
Ramp/soak No. 7 target value62U161
Ramp/soak No. 8 target value63U161
Ramp/soak No. 1 ramp time64U161
Ramp/soak No. 1 soak time65U161
Ramp/soak No. 2 ramp time66U161
Ramp/soak No. 2 soak time67U161
Ramp/soak No. 3 ramp time68U161
Ramp/soak No. 3 soak time69U161
Ramp/soak No. 4 ramp time70U161
Ramp/soak No. 4 soak time71U161
Ramp/soak No. 5 ramp time72U161
Ramp/soak No. 5 soak time73U161
Ramp/soak No. 6 ramp time74U161
Ramp/soak No. 6 soak time75U161
Ramp/soak No. 7 ramp time76U161
Ramp/soak No. 7 soak time77U161
Ramp/soak No. 8 ramp time78U161
Ramp/soak No. 8 soak time79U161
Ramp/soak mode80U161
Ramp/soak command81U161
Ramp/soak pattern selection82U161
PV stable range84U161
Communication DI action request86U161
Control action type code87U161
Output proportional cycle (output 1)88U161
Output proportional cycle (output 2)89U161
Alarm 1 option function91U161
Alarm 2 option function92U161
DI1 action setting94U161
Hysteresis mode setting96U161
User zero adjustment98I161
User span adjustment99I161
DSP1100U161
DSP2101U161
DSP3102U161
DSP4103U161
DSP5104U161
DSP6105U161
DSP7106U161
DSP8107U161
DSP9108U161
DSP10109U161
DSP11110U161
DSP12111U161
DSP13112U161
Non-volatile memory write-in (FIX execution)1000U161
Process value (PV)1000I161
PID/FUZZY/SELF selection1001U161
Currently used set value (SV)1001I161
SV value controlled on face panel1002I161
Currently used deviation (DV)1002I161
Control RUN/standby1003U161
MV (output 1)1003I160.01%
Auto tuning command1004U161
MV (output 2)1004I160.01%
P1005U160.1%
Station No.1005U161
I1006U160.1sec
Alarm status1006U161
D1007U160.1sec
Input/main unit abnormal status1007U161
Hysteresis range at two-position control1008U161
Ramp/soak current running position1008U161
COOL1009U161
Dead band1010I161
Anti-reset windup1011I161
Output convergence value1012I161
PV shift1013I161
SV offset1014I161
Input type code1015U161
Temperature unit1016U161
Input scale lower limit1017I161
Input scale upper limit1018I161
Decimal point place1019U161
Input filter time constant1021U161
RCJ yes/no1022U161
MV limit kind1023U161
Output 1 lower limit1024I161
Output 1 upper limit1025I161
Output 2 lower limit1026I161
Output 2 upper limit1027I161
Set value (SV) lower limit1030I161
Set value (SV) upper limit1031I161
Heater burnout alarm set value1038U161
Setting lock1039U161
Alarm 1 type1040U161
Alarm 2 type1041U161
Alarm 1 set value or alarm 1 lower limit set value1043I161
Alarm 2 set value or alarm 2 lower limit set value1044I161
Alarm 1 upper limit set value1046I161
Alarm 2 upper limit set value1047I161
Alarm 1 hysteresis1049U161
Alarm 2 hysteresis1050U161
Alarm 1 ON-delay set value1052U161
Alarm 2 ON-delay set value1053U161
Ramp/soak No. 1 target value1056I161
Ramp/soak No. 2 target value1057I161
Ramp/soak No. 3 target value1058I161
Ramp/soak No. 4 target value1059I161
Ramp/soak No. 5 target value1060I161
Ramp/soak No. 6 target value1061I161
Ramp/soak No. 7 target value1062I161
Ramp/soak No. 8 target value1063I161
Ramp/soak No. 1 ramp time1064U161
Ramp/soak No. 1 soak time1065U161
Ramp/soak No. 2 ramp time1066U161
Ramp/soak No. 2 soak time1067U161
Ramp/soak No. 3 ramp time1068U161
Ramp/soak No. 3 soak time1069U161
Ramp/soak No. 4 ramp time1070U161
Ramp/soak No. 4 soak time1071U161
Ramp/soak No. 5 ramp time1072U161
Ramp/soak No. 5 soak time1073U161
Ramp/soak No. 6 ramp time1074U161
Ramp/soak No. 6 soak time1075U161
Ramp/soak No. 7 ramp time1076U161
Ramp/soak No. 7 soak time1077U161
Ramp/soak No. 8 ramp time1078U161
Ramp/soak No. 8 soak time1079U161
Ramp/soak mode1080U161
Ramp/soak command1081U161
Ramp/soak pattern selection1082U161
PV stable range1084I161
Communication DI action request1086U161
Control action type code1087U161
Output proportional cycle (output 1)1088U161
Output proportional cycle (output 2)1089U161
Alarm 1 option function1091U161
Alarm 2 option function1092U161
DI1 action setting1094U161
Hysteresis mode setting1096U161
User zero adjustment1098I161
User span adjustment1099I161
DSP11100U161
DSP21101U161
DSP31102U161
DSP41103U161
DSP51104U161
DSP61105U161
DSP71106U161
DSP81107U161
DSP91108U161
DSP101109U161
DSP111110U161
DSP121111U161
DSP131112U161

link settings as documented (unverified): RTU; default 9600 8O1; unit ID 1; FC 01,02,03,04,05,06,16; Transmission speed, data length, and stop bit are fixed.

⚠ For avoiding electric shock and malfunctions, do not turn on the power supply until all wiring have been completed. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminals7 (+), 8 (-)
A/B polarity7 is +, 8 is -
terminationBoth ends of the cable should be terminated with terminating resistors 100 ohm 1/2W
connectorTerminal block
isolationFunctional isolation between transmission circuit and others (withstand voltage: 500V AC)
shield/groundThe shield wire of the cable should be grounded at one place on the master station unit side.
wiring notesRecommended cable: UL2464, UL2448, etc. Recommended noise filter: ZRAC2203-11/TDK
max registers/read60
broadcastnot supported
protocol notesWhile the data is being written in non-volatile memory after write via communication, the next write is attempted and will result in no response.
FC 43 device IDnot supported
doc revisionINP-TN512642a-E

⚠ disputed: terminals: "7 (+), 8 (-)" and polarity: "7 is +, 8 is -" — disputed by the official manual [3.4.1]. This terminal allocation is only correct for the PXR4 model. The PXR3 uses terminals 15 (+) and 14 (-), while the PXR5 and PXR9 use terminals 1 (+) and 2 (-).

field reports — community-sourced, unverified (checked 2026-06-11)
  • The Process Value (PV) at register 31001 (relative address 1000) is located in the read-only Input Register space (3xxxx) and must be read using Modbus Function Code 04H. Attempting to read it using Function Code 03H (Read Holding Registers) is a common integration pitfall that will result in a Modbus exception response. [source]
  • During the non-volatile memory write-in (FIX) process triggered by writing 1 to register 40001/41001, the controller will not respond to any incoming Modbus commands for approximately 5 seconds. [source]
  • confirmed: Document revision INP-TN512642a-E matches the Fuji Electric Micro Controller X (PXR) RS-485 Modbus Communication Manual [1.2.3].
  • confirmed: Default communication settings are 9600 bps, 8 data bits, 1 stop bit, and Odd parity (CoM = 0), with a default station number (unit ID) of 1.
  • confirmed: Modbus RTU communication is prohibited if the station number is set to 0, meaning broadcast is not supported.

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.