device library

GE Multilin 750/760 feeder management relay

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
general_status_alarm512U161
contact_1516U161
close_coil_monitor517U161
output_relay_status_1_trip518U161
neutral_voltage766U160.01
phase_a_rms_current768U161
phase_b_rms_current769U161
phase_c_rms_current770U161
ground_current772U161
a_n_rms_voltage773U160.01
b_n_rms_voltage774U160.01
c_n_rms_voltage775U160.01

link settings as documented (unverified): RTU/TCP; default 9600 8N1; unit ID 1; Supports Modbus RTU on serial ports (COM1, COM2, Front RS232) and Modbus TCP/IP over Ethernet (up to 4 sessions).

⚠ Relay contacts must be considered unsafe to touch when the 750/760 is energized! — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsScrew terminals on rear panel (slotted, pan head nickel plated #8-32x0.375")
A/B polarityCorrect polarity must be observed on RS485/RS422 (B1 for +, B2 for -) and logic inputs.
terminationTerminating impedance at each end typically 120 Ohms and 1 nF.
connectorRJ45 for Ethernet, 9-pin D-connector for front RS232, screw terminals for rear serial ports.
isolationAnalog outputs are fully isolated. Opto-coupled data interface for serial ports.
shield/groundShield (Ground) terminal B9 for serial, G12 for Safety Ground, G11 for Filter Ground. Shield should be grounded at one point only.
wiring notesFully drawout unit with automatic CT shorts.
protocol notesEEPROM DATA ERROR message may be displayed after upgrading/downgrading firmware due to Modbus address rearrangement.
identification notesThe label found on the left side of the relay specifies its order code or model number.
powerLO: 20 to 60 V DC or 20 to 48 V AC; HI: 88 to 300 V DC or 70 to 265 V AC
environmentOperating temperature: -40°C to +60°C. Storage/Shipping: -40°C to +80°C. Humidity: up to 90% non-condensing. Pollution degree: 2. IP Rating: 40-X.
accuracyAnalog outputs accuracy: ±1% of full scale.
certificationsMeets CE drawout specifications, UL registered (UL # A3775), ISO9001:2000 registered.
doc revisionManual P/N: 1601-0120-AE, Manual Order Code: GEK-106471N, September 2011
firmware applicabilitySoftware Revision: 7.4x
field reports — community-sourced, unverified (checked 2026-06-11)
  • A user reported a Modbus communication issue where they were only able to receive one bit of data instead of the expected block of registers, indicating potential firmware or configuration mismatch issues. [source]
  • confirmed: comms defaults and framing — confirmed by GE Multilin 750/760 Instruction Manual
  • confirmed: EEPROM DATA ERROR message after firmware upgrade/downgrade — confirmed by GE Multilin 750/760 Instruction Manual
  • confirmed: Modbus register map addresses (e.g., Phase A RMS Current @ 768, Ground Current @ 772, Neutral Voltage @ 766) — confirmed by GE Multilin 750/760 Modbus Memory Map

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.