device library

Greystone CHTDT CO2/RH/T sensor

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
co20U161
relative_humidity1U160.1
temperature_c2I160.1
temperature_f3I160.1

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; CRC polynomial is configurable (A001, 1021, 8005, 8408). Slave response delay is configurable (MI, 50, 100, 150, 200, 250, 300, 350ms).

⚠ Do not use in an explosive or hazardous environment, with combustible or flammable gases, as a safety or emergency stop device or in any other application where failure of the product could result in personal injury. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsScrew terminal block (14 to 22 AWG)
A/B polarityA(-), B(+)
termination121 ohm termination resistor selectable via jumper
connectorScrew terminal block
isolationRelay output is completely isolated
shield/groundThe ground wire of the shielded pair should be connected to earth ground at the end of the network and the master is not grounded.
wiring notesUse 22 AWG shielded wiring for all connections
protocol notesSlave response delay is configurable from MI (minimum, >3.5 character times) to 350ms.
identification notesOn start-up, the LCD will indicate the software version number, the slave address and the baud rate.
power20 - 28 Vac/dc (non-isolated half-wave rectified), 120 mA max @ 24 Vdc, 212 mA max @ 24 Vac
environmentOperating Conditions: 0 to 50°C (32 to 122°F), 0-95 %RH non-condensing. Storage Temperature: -20 to 60°C (-4 to 140°F). Enclosure: Polycarbonate, UL94-V0, IP65 (NEMA 4X)
accuracyCO2: ± (30ppm + 3% of measured value). RH: ±2 %RH (5 to 95 %RH). Temp: ±0.2°C
certificationsCE
doc revisionIN-GE-CHTDTXXXMOD-04

⚠ disputed: register_map: co2 @ 0, relative_humidity @ 1, temperature_c @ 2, temperature_f @ 3 — disputed by CHT Series Modbus Setup Guide (SG-CHTXXXMOD-02) which maps Relay/Unit Status @ 0 (40001), CO2 @ 1 (40002), RH @ 2 (40003), and Temperature @ 3 (40004)

field reports — community-sourced, unverified (checked 2026-06-11)
  • Depending on the firmware version of the CHT Series Modbus Setup Guide (e.g., SG-CHTXXXMod-01-01 vs SG-CHTXXXMOD-02), the register map offsets differ. In version 01-01, register 40001 is Relay Status, 40002 is CO2, 40003 is Temperature, and 40004 is RH. In version 02, register 40001 is Unit Status, 40002 is CO2, 40003 is RH, and 40004 is Temperature. This swap of RH and Temperature registers can cause integration issues if the wrong guide version is used. [source]
  • confirmed: comms.baud_rates: [9600, 19200, 38400, 57600, 76800, 115200] — confirmed by CHT Series Modbus Setup Guide (SG-CHTXXXMOD-02)
  • confirmed: comms.default_baud: 9600 — confirmed by CHTDT Modbus Series Installation Instructions (IN-GE-CHTDTXXXMOD-04)
  • confirmed: comms.default_unit_id: 1 — confirmed by CHTDT Modbus Series Installation Instructions (IN-GE-CHTDTXXXMOD-04)
  • confirmed: comms.notes: CRC polynomial is configurable (A001, 1021, 8005, 8408) and Slave response delay is configurable (MI, 50, 100, 150, 200, 250, 300, 350ms) — confirmed by CHTDT Modbus Series Installation Instructions (IN-GE-CHTDTXXXMOD-04)
  • confirmed: facts.accuracy: CO2: ± (30ppm + 3% of measured value). RH: ±2 %RH (5 to 95 %RH). Temp: ±0.2°C — confirmed by CHTDT Series Datasheet
  • confirmed: facts.doc_revision: IN-GE-CHTDTXXXMOD-04 — confirmed by CHTDT Modbus Series Installation Instructions
  • confirmed: physical.polarity: A(-), B(+) — confirmed by CHTDT Modbus Series Installation Instructions (IN-GE-CHTDTXXXMOD-04)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.