Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| co2 | 0 | U16 | 1 | |
| relative_humidity | 1 | U16 | 0.1 | |
| temperature_c | 2 | I16 | 0.1 | |
| temperature_f | 3 | I16 | 0.1 |
⚠ Do not use in an explosive or hazardous environment, with combustible or flammable gases, as a safety or emergency stop device or in any other application where failure of the product could result in personal injury. — Starkest reads only; we never write a control register.
| terminals | Screw terminal block (14 to 22 AWG) |
| A/B polarity | A(-), B(+) |
| termination | 121 ohm termination resistor selectable via jumper |
| connector | Screw terminal block |
| isolation | Relay output is completely isolated |
| shield/ground | The ground wire of the shielded pair should be connected to earth ground at the end of the network and the master is not grounded. |
| wiring notes | Use 22 AWG shielded wiring for all connections |
| protocol notes | Slave response delay is configurable from MI (minimum, >3.5 character times) to 350ms. |
| identification notes | On start-up, the LCD will indicate the software version number, the slave address and the baud rate. |
| power | 20 - 28 Vac/dc (non-isolated half-wave rectified), 120 mA max @ 24 Vdc, 212 mA max @ 24 Vac |
| environment | Operating Conditions: 0 to 50°C (32 to 122°F), 0-95 %RH non-condensing. Storage Temperature: -20 to 60°C (-4 to 140°F). Enclosure: Polycarbonate, UL94-V0, IP65 (NEMA 4X) |
| accuracy | CO2: ± (30ppm + 3% of measured value). RH: ±2 %RH (5 to 95 %RH). Temp: ±0.2°C |
| certifications | CE |
| doc revision | IN-GE-CHTDTXXXMOD-04 |
⚠ disputed: register_map: co2 @ 0, relative_humidity @ 1, temperature_c @ 2, temperature_f @ 3 — disputed by CHT Series Modbus Setup Guide (SG-CHTXXXMOD-02) which maps Relay/Unit Status @ 0 (40001), CO2 @ 1 (40002), RH @ 2 (40003), and Temperature @ 3 (40004)
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.