device library

Grundfos CUE drive

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
parameter_index8U161
configuration_mode_1_00999U161
motor_current_1_241239U32BE0.01A
control_word_28102809U161
bus_reference_28112810I161%
status_word_29102909U161
main_actual_value_29112910I161%
maximum_reference_3_033029U32BE0.001RPM
status_word_16_0316029U161
main_actual_value_16_0516049I161%
motor_current_16_1416139U32BE0.01A
digital_inputs_16_6016599U161
control_word_5000049999U161
bus_reference_5001050009I161%
status_word_5020050199U161
main_actual_value_5021050209I161%

link settings as documented (unverified): RTU; baud 2400/4800/9600/19200; FC 01,03,05,06,08,11,15,16,17; If the baud rate is greater than 19200, then the 3.5 character time is replaced by a timeout time of 1.75 ms.

⚠ Grundfos recommends only using one of the three mentioned ways to control the frequency converter! Grundfos recommends register 2810-2873 and 2910-2973 to control the frequency converter ensuring compatibility with all controllers. Par. 200-52 Control Source Request is to be set to 1 Remote to control the CUE via Modbus. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
broadcastsupported
protocol notesModbus RTU messages addressed to zero are broadcast messages. No response is permitted for broadcast messages.
doc revision93525145 11.2025
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: baud_rates: [2400, 4800, 9600, 19200] — confirmed by Native Modbus RTU for CUE - Grundfos manual (parameter 8-32)
  • confirmed: framing: ['RTU'] — confirmed by Native Modbus RTU for CUE - Grundfos manual (parameter 8-30)
  • confirmed: function_codes: [1, 3, 5, 6, 8, 11, 15, 16, 17] — confirmed by Native Modbus RTU for CUE - Grundfos manual (section 3.10)
  • confirmed: parity: 'E', stop_bits: 1 — confirmed by Native Modbus RTU for CUE - Grundfos manual (parameter 8-33 default)
  • confirmed: timeout note: 'If the baud rate is greater than 19200, then the 3.5 character time is replaced by a timeout time of 1.75 ms.' — confirmed by Native Modbus RTU for CUE - Grundfos manual (section 3.2)
  • confirmed: control_warning: 'Grundfos recommends only using one of the three mentioned ways to control the frequency converter! Grundfos recommends register 2810-2873 and 2910-2973 to control the frequency converter ensuring compatibility with all controllers. Par. 200-52 Control Source Request is to be set to 1 Remote to control the CUE via Modbus.' — confirmed by Native Modbus RTU for CUE - Grundfos manual (section 4.1)
  • confirmed: doc_revision: '93525145 11.2025' — confirmed by Native Modbus RTU for CUE - Grundfos manual footer
  • confirmed: broadcast_supported: true, notes: 'Modbus RTU messages addressed to zero are broadcast messages. No response is permitted for broadcast messages.' — confirmed by Native Modbus RTU for CUE - Grundfos manual (section 3.5)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.