Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Frequency source setting0U32BE1
Run command source setting2U32BE1
Base frequency setting4U32BE1
Maximum frequency setting6U32BE1
[AT] selection8U32BE1
[O]-[L] input active range start frequency20U32BE1
[O]-[L] input active range end frequency22U32BE1
[O]-[L] input active range start voltage24U32BE1
[O]-[L] input active range end voltage26U32BE1
[O]-[L] input start frequency select28U32BE1
Analog input filter time constant30U32BE1
Multi-speed frequency 038U32BE1
Multi-speed frequency 140U32BE1
Multi-speed frequency 242U32BE1
Multi-speed frequency 344U32BE1
Multi-speed frequency 446U32BE1
Multi-speed frequency 548U32BE1
Multi-speed frequency 650U32BE1
Multi-speed frequency 752U32BE1
Multi-speed frequency 854U32BE1
Multi-speed frequency 956U32BE1
Multi-speed frequency 1058U32BE1
Multi-speed frequency 1160U32BE1
Multi-speed frequency 1262U32BE1
Multi-speed frequency 1364U32BE1
Multi-speed frequency 1466U32BE1
Multi-speed frequency 1568U32BE1
Jog frequency setting74U32BE1
Jog stop mode76U32BE1
Torque boost method selection80U32BE1
Manual torque boost value82U32BE1
Manual torque boost frequency adjustment84U32BE1
V/f characteristic curve selection, 1st motor86U32BE1
V/f gain setting88U32BE1
Auto torque boost voltage comp. gain (SJ200 only)90U32BE1
Auto torque boost slip comp. gain (SJ200 only)92U32BE1
DC braking enable100U32BE1
DC braking frequency setting102U32BE1
DC braking wait time104U32BE1
DC braking force during deceleration106U32BE1
DC braking time for deceleration108U32BE1
Selection of edge/level action of DC braking input [DB]110U32BE1
Frequency upper limit setting120U32BE1
Frequency lower limit setting122U32BE1
Jump frequency 1124U32BE1
Width of jump frequency 1126U32BE1
Jump frequency 2128U32BE1
Width of jump frequency 2130U32BE1
Jump frequency 3132U32BE1
Width of jump frequency 3134U32BE1
PID Enable140U32BE1
PID Proportional(P) gain142U32BE1
PID Integral (I) time constant144U32BE1
PID Derivative (D) time constant146U32BE1
PID PV Scale conversion148U32BE1
PID PV source setting150U32BE1
Reverse-acting PID select152U32BE1
PID Output Limiter154U32BE1
AVR function select160U32BE1
AVR voltage select162U32BE1
Acceleration time (2)182U32BE1
Deceleration time (2)184U32BE1
Select method to switch to acc2/dec2 profile186U32BE1
Acc1 to Acc2 frequency transition point188U32BE1
Dec1 to Dec2 frequency transition point190U32BE1
Acceleration curve selection192U32BE1
Deceleration curve selection194U32BE1
[OI]-[L] input active range start frequency200U32BE1
[OI]-[L] input active range end frequency202U32BE1
[OI]-[L] input active range start current204U32BE1
[OI]-[L] input active range end current206U32BE1
[OI]-[L] input start frequency enable208U32BE1
Input Select for Calculate Func. 1280U32BE1
Input Select for Calculate Func. 2282U32BE1
Calculation Operator Select284U32BE1
ADD Frequency288U32BE1
ADD Sign Select290U32BE1
Base frequency setting, 2nd motor404U32BE1
Maximum frequency setting, 2nd motor406U32BE1
Multi-speed frequency 0, 2nd motor438U32BE1
Torque boost method, 2nd motor (SJ100 only)480U32BE1
Manual torque boost value, 2nd motor (except L100)482U32BE1
Manual torque boost frequency adjustment, 2nd motor (except L100)484U32BE1
V/f characteristic curve selection, 2nd motor (except L100)486U32BE1
Auto torque boost voltage comp. gain, 2nd motor (SJ200 only)490U32BE1
Auto torque boost slip comp. gain, 2nd motor (SJ200 only)492U32BE1
Frequency upper limit setting, 2nd motor520U32BE1
Frequency lower limit setting, 2nd motor522U32BE1
Acceleration time (2), 2nd motor582U32BE1
Deceleration time (2), 2nd motor584U32BE1
Select method to switch to acc2/dec2 profile, 2nd motor (except L100)586U32BE1
Acc1 to Acc2 frequency transition point, 2nd motor588U32BE1
Dec1 to Dec2 frequency transition point, 2nd motor590U32BE1
Selection of automatic restart mode1000U32BE1
Allowable under-voltage power failure time1002U32BE1
Retry wait time before motor restart1004U32BE1
Instantaneous power failure/under-voltage trip alarm enable1006U32BE1
Number of restarts on power failure/under-voltage events1008U32BE1
Level of electronic thermal setting, 1st motor1022U32BE1
Electronic thermal characteristic, 1st motor1024U32BE1
Overload restriction operation mode1040U32BE1
Overload restriction setting1042U32BE1
Deceleration rate at overload restriction1044U32BE1
Software lock mode selection1060U32BE1
No Load Current Setting (L100 Only)1062U32BE1
[AM] terminal analog meter adjustment1158U32BE1
[FM] terminal analog meter adjustment1160U32BE1
Start frequency adjustment1162U32BE1
Carrier frequency setting1164U32BE1
Initialization mode1166U32BE1
Country code for initialization1168U32BE1
Frequency scaling factor1170U32BE1
STOP key enable1172U32BE1
Restart mode after FRS1174U32BE1
Data select for operator when operating on network1176U32BE1
Dynamic braking usage ratio1178U32BE1
Stop mode selection (except L100)1180U32BE1
Cooling fan control1182U32BE1
Dynamic braking control1188U32BE1
Dynamic braking activation level1190U32BE1
OV LADSTOP Selection1258U32BE1
Overcurrent Trip Suppression1278U32BE1
Carrier Frequency Mode1298U32BE1
Level of electronic thermal setting, 2nd motor1422U32BE1
Electronic thermal characteristic, 2nd motor1424U32BE1
Intelligent input 1 function2000U32BE1
Intelligent input 2 function2002U32BE1
Intelligent input 3 function2004U32BE1
Intelligent input 4 function2006U32BE1
Intelligent input 5 function2008U32BE1
Intelligent input 6 function2010U32BE1
Intelligent input 1 active state2020U32BE1
Intelligent input 2 active state2022U32BE1
Intelligent input 3 active state2024U32BE1
Intelligent input 4 active state2026U32BE1
Intelligent input 5 active state2028U32BE1
Intelligent input 6 active state2030U32BE1
Intelligent output 11 function2040U32BE1
Intelligent output 12 function2042U32BE1
[FM] signal selection2044U32BE1
Alarm relay function2046U32BE1
Alarm relay output function2050U32BE1
[AM] signal function2054U32BE1
Intelligent output 11 active state2060U32BE1
Intelligent output 12 active state2062U32BE1
Alarm relay active state2064U32BE1
Alarm relay output active state2070U32BE1
Overload level setting2080U32BE1
Frequency arrival setting for acceleration2082U32BE1
Arrival frequency setting for deceleration2084U32BE1
PID deviation level setting2086U32BE1
PID FBV Function High Limit2102U32BE1
PID FBV Function Low Limit2104U32BE1
Communication speed selection2140U32BE1
Node allocation2142U32BE1
Communication parity selection2146U32BE1
Communication stop bit selection2148U32BE1
Communication error select2150U32BE1
Communication time-out2152U32BE1
Communication wait time2154U32BE1
[O] input span calibration2160U32BE1
[OI] input span calibration2162U32BE1
Thermistor input tuning2168U32BE1
[AM] output offset2170U32BE1
Debug mode enable2180U32BE1
UP/DOWN memory mode2200U32BE1
RESET mode selection2202U32BE1
Input A Select for Logic Output2280U32BE1
Input B Select for Logic Output2282U32BE1
Logic Function Select2284U32BE1
Terminal 11 ON Delay2286U32BE1
Terminal 11 OFF Delay2288U32BE1
Terminal 12 ON Delay2290U32BE1
Terminal 12 OFF Delay2292U32BE1
Relay Output ON Delay2294U32BE1
Relay Output OFF Delay2296U32BE1
Capacity code selection2390U32BE1
Voltage code selection2392U32BE1
Output frequency monitor3000U32BE1
Output current monitor3002U32BE1
Rotation direction monitor3004U32BE1
Process Variable (PV) PID feedback monitor3006U32BE1
Intelligent input terminal status3008U32BE1
Intelligent output terminal status3010U32BE1
Scaled output frequency monitor3012U32BE1
Trip counter3158U32BE1
Error Code of Trip 13160U32BE1
Error Code of Trip23162U32BE1
Error Code of Trip 33164U32BE1
Output Frequency Setting by using Volume of the Inverter3198U32BE1
Output Frequency Monitor (L100/SJ100 ONLY)3200U32BE1
Frequency Setpoint (L100/SJ100 ONLY)3202U32BE1
MCU Version3210U32BE1
Output frequency setting(Hz) / PID Setpoint (%)4000U32BE1
Acceleration time 14002U32BE1
Deceleration time 14004U32BE1
Keypad RUN key routing4006U32BE1
Acceleration time 1, 2nd motor4402U32BE1
Deceleration time 1, 2nd motor4404U32BE1
Auto-tuning setting (SJ100 only)5000U32BE1
Motor data selection, 1st motor5002U32BE1
Motor capacity, 1st motor5004U32BE1
Motor poles, 1st motor5006U32BE1
Motor speed constant, 1st motor5008U32BE1
Motor stabilization constant, 1st motor5010U32BE1
Motor Voltage Select5012U32BE1
Motor constant R1, 1st motor5038U32BE1
Motor constant R2, 1st motor5040U32BE1
Inductance L, 1st motor5042U32BE1
Io, 1st motor5044U32BE1
Inertia J, 1st motor5046U32BE1
Motor constant R1, 1st motor (Auto)5058U32BE1
Motor constant R2, 1st motor (Auto)5060U32BE1
Inductance L, 1st motor (Auto)5062U32BE1
Io, 1st motor (Auto)5064U32BE1
Inertia J, 1st motor (Auto)5066U32BE1
Motor data selection, 2nd motor5402U32BE1
Motor capacity, 2nd motor5404U32BE1
Motor poles, 2nd motor5406U32BE1
Motor speed constant, 2nd motor5408U32BE1
Motor stabilization constant, 2nd motor5410U32BE1
Motor Voltage Select, 2nd motor5412U32BE1
Motor constant R1, 2nd motor5438U32BE1
Motor constant R2, 2nd motor5440U32BE1
Inductance L, 2nd motor5442U32BE1
Io, 2nd motor5444U32BE1
Inertia J, 2nd motor5446U32BE1
Motor constant R1, 2nd motor (Auto)5458U32BE1
Motor constant R2, 2nd motor (Auto)5460U32BE1
Inductance L, 2nd motor (Auto)5462U32BE1
Io, 2nd motor (Auto)5464U32BE1
Inertia J, 1st motor (Auto)5466U32BE1
Run Mode [0=Stop, 1=Forward, 2=Reverse]8000U32BE1
TRIP Counter8002U32BE1
TRIP History 1 Time8004U32BE1
TRIP History 1 Cause8006U32BE1
TRIP History 1 Freq8008U32BE1
TRIP History 1 Current8010U32BE1
TRIP History 1 Voltage8012U32BE1
TRIP History 2 Time8014U32BE1
TRIP History 2 Cause8016U32BE1
TRIP History 2 Freq8018U32BE1
TRIP History 2 Current8020U32BE1
TRIP History 2 Voltage8022U32BE1
TRIP History 3 Time8024U32BE1
TRIP History 3 Cause8026U32BE1
TRIP History 3 Freq8028U32BE1
TRIP History 3 Current8030U32BE1
TRIP History 3 Voltage8032U32BE1
Voltage Class8034U32BE1
Inverter Type [1=L100, 2=SJ100, 6=L200, 7=SJ200]8036U32BE1
EEPROM Store flag8038U32BE1
Reset Trip8042U32BE1
Serial Data Watchdog Timeout (ms)8044U32BE1

link settings as documented (unverified): TCP; FC 03,04,06,16; Supports MODBUS/TCP communication protocol.

bench facts as documented (unverified)
terminalsPower Alm Rly +24V- GNDC CM NC NO
connectorRJ45 Jack (marked ETHERNET), RJ11 Jack (marked SERIAL)
wiring notesConnects to inverter via RJ11 to RJ45 cable.
max registers/read125
powerRequires 24 VDC via terminals marked '+ 24 V -'.
doc revisionHAL1052, December 2005
field reports — community-sourced, unverified (checked 2026-06-11)
  • Register address offset: Users must use 0-based addressing (subtracting 1 from the documentation's 1-based start addresses) to avoid reading/writing incorrect registers. [source]
  • Coil mapping / Alarm trip issue: Writing to the third coil (thinking it is a direction command) actually triggers an external trip command (alarm) on the VFD because of a mismatch/inconsistency in register/coil numbering. [source]
  • confirmed: Supports MODBUS/TCP communication protocol with function codes 3, 4, 6, 16 — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052) [1.2.9]
  • confirmed: Physical connectors include RJ45 (marked ETHERNET) and RJ11 (marked SERIAL) with RJ11-to-RJ45 connection to the inverter — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052)
  • confirmed: Requires 24 VDC via terminals marked '+ 24 V -' — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052)
  • confirmed: Terminals are marked 'Power Alm Rly +24V- GNDC CM NC NO' — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052)
  • confirmed: Max read registers is 125 — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052)
  • confirmed: Register map matches 0-based start addresses of 32-bit parameters (e.g., output_frequency_monitor at 3000, run_mode at 8000) — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.