Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Status Change | 0 | U16 | 1 | |
| Configuration Change | 1 | U16 | 1 | |
| Digital I/O | 2 | U16 | 1 | |
| Annunciation I/O | 3 | U16 | 1 | |
| Limits | 4 | U16 | 1 | |
| Program Module (PM) status | 5 | U16 | 1 | |
| Demand source | 6 | U16 | 1 | |
| Outlet (S3S4) or Outlet limit (S3) sensor | 7 | U16 | 0.1 | °C |
| Firing rate | 8 | U16 | 1 | % or RPM |
| Fan speed | 9 | U16 | 1 | RPM |
| Flame signal | 10 | U16 | 0.01 | V or μA |
| Inlet (S1) sensor | 11 | U16 | 0.1 | °C |
| DHW (S6S7) or DHW limit (S6) sensor | 12 | U16 | 0.1 | °C |
| S5 sensor | 13 | U16 | 0.1 | °C |
| Stack (S8S9) or Stack limit (S8) sensor | 14 | U16 | 0.1 | °C |
| 4-20 mA remote control input (S2) terminal | 15 | U16 | 0.1 | mA |
| Active CH setpoint | 16 | U16 | 0.1 | °C |
| Active DHW setpoint | 17 | U16 | 0.1 | °C |
| Active LL setpoint | 18 | U16 | 0.1 | °C |
| Register Access Status | 19 | U16 | 1 | |
| Steam pressure | 20 | U16 | 0.1 | psi |
| Analog modulation input | 21 | U16 | 0.1 | mA |
| Active CH pressure setpoint | 22 | U16 | 0.1 | psi |
| Extended Status Change | 23 | U16 | 1 | |
| Active CH operating point | 25 | U16 | 0.1 | °C |
| Active DHW operating point | 26 | U16 | 0.1 | °C |
| Active Lead Lag operating point | 27 | U16 | 0.1 | °C |
| Active system operating point | 28 | U16 | 0.1 | °C |
| Active system setpoint | 29 | U16 | 0.1 | °C |
| Active system on hysteresis | 30 | U16 | 0.1 | °C |
| Active system off hysteresis | 31 | U16 | 0.1 | °C |
| Burner control status | 32 | U16 | 1 | |
| Burner control state | 33 | U16 | 1 | |
| Lockout code | 34 | U16 | 1 | |
| Alarm reason | 35 | U16 | 1 | |
| Annunciator first out | 36 | U16 | 1 | |
| Annunciator hold | 37 | U16 | 1 | |
| Sequence time | 38 | U16 | 1 | s |
| Delay time | 39 | U16 | 1 | s |
| Hold code | 40 | U16 | 1 | |
| Burner control flags | 41 | U16 | 1 | |
| CH remote Stat | 42 | U16 | 1 | |
| Outlet operation (S4=J8-10) terminal | 43 | U16 | 0.1 | °C |
| DHW operation (S7=J9-3) terminal | 44 | U16 | 0.1 | °C |
| Stack or Heat exchanger operation (S9=J9-6) terminal | 45 | U16 | 0.1 | °C |
| Outlet operation sensor (S4=J8-10) state | 46 | U16 | 1 | |
| DHW operation sensor (S7=J9-3) state | 47 | U16 | 1 | |
| Outlet limit sensor (S3=J8-8) state | 48 | U16 | 1 | |
| Inlet sensor (S1=J8-4) state | 49 | U16 | 1 | |
| DHW limit sensor (S7=J9-1) state | 50 | U16 | 1 | |
| Stack limit sensor (S8=J9-4) state | 51 | U16 | 1 | |
| S5 (J8-11) sensor state | 52 | U16 | 1 | |
| 4-20mA remote control input (S2=J8-6) state | 53 | U16 | 1 | |
| Pressure sensor (S1=J8-4) state | 54 | U16 | 1 | |
| Stack operation or Heat exchanger sensor (S9=J9-6) state | 55 | U16 | 1 | |
| Active rate limiter | 56 | U16 | 1 | |
| Limited rate | 57 | U16 | 1 | RPM or % |
| Active rate override | 58 | U16 | 1 | |
| Override rate | 59 | U16 | 1 | RPM or % |
| Demand rate | 60 | U16 | 1 | RPM or % |
| Active system sensor | 61 | U16 | 1 | |
| Active Lead Lag sensor | 62 | U16 | 1 | |
| CH status | 64 | U16 | 1 | |
| CH setpoint source | 65 | U16 | 1 | |
| CH heat demand | 66 | U16 | 1 | |
| CH burner demand | 67 | U16 | 1 | |
| CH requested rate | 68 | U16 | 1 | RPM or % |
| CH frost heat demand | 69 | U16 | 1 | |
| CH frost burner demand | 70 | U16 | 1 | |
| Active CH on hysteresis | 71 | U16 | 0.1 | °C |
| Active CH off hysteresis | 72 | U16 | 0.1 | °C |
| Active CH pressure on hysteresis | 73 | U16 | 0.1 | psi |
| Active CH pressure off hysteresis | 74 | U16 | 0.1 | psi |
| Active CH pressure operating point | 75 | U16 | 0.1 | psi |
| Active CH sensor | 76 | U16 | 1 | |
| Heat Demand | 77 | U16 | 1 | |
| BURNER DEMAND | 78 | U16 | 1 | |
| Active DHW sensor | 79 | U16 | 1 | |
| DHW status | 80 | U16 | 1 | |
| DHW setpoint source | 81 | U16 | 1 | |
| DHW priority count | 82 | U16 | 1 | s |
| DHW heat demand | 83 | U16 | 1 | |
| DHW burner demand | 84 | U16 | 1 | |
| DHW requested rate | 85 | U16 | 1 | RPM or % |
| DHW frost heat demand | 86 | U16 | 1 | |
| DHW frost burner demand | 87 | U16 | 1 | |
| Active DHW on hysteresis | 88 | U16 | 0.1 | °C |
| Active DHW off hysteresis | 89 | U16 | 0.1 | °C |
| DHW storage time | 90 | U16 | 1 | s |
| DHW storage heat demand | 91 | U16 | 1 | |
| DHW storage burner demand | 92 | U16 | 1 | |
| Pump A status | 93 | U16 | 1 | |
| Pump B status | 94 | U16 | 1 | |
| CH pump start delay time | 95 | U16 | 1 | s |
| CH pump status | 96 | U16 | 1 | |
| CH pump overrun time | 97 | U16 | 1 | s |
| CH FP overrun time | 98 | U16 | 1 | s |
| CH pump idle days count | 99 | U16 | 1 | days |
| DHW pump status | 100 | U16 | 1 | |
| DHW pump start delay time | 101 | U16 | 1 | s |
| DHW pump overrun time | 102 | U16 | 1 | s |
| DHW FP overrun time | 103 | U16 | 1 | s |
| DHW pump idle days count | 104 | U16 | 1 | days |
| System pump status | 105 | U16 | 1 | |
| System pump overrun time | 106 | U16 | 1 | s |
| System pump idle days count | 107 | U16 | 1 | days |
| Boiler pump status | 108 | U16 | 1 | |
| Boiler pump overrun time | 109 | U16 | 1 | s |
| Boiler pump idle days count | 110 | U16 | 1 | days |
| Auxiliary 1 pump status | 111 | U16 | 1 | |
| Auxiliary 1 pump idle days count | 112 | U16 | 1 | days |
| Auxiliary 2 pump status | 113 | U16 | 1 | |
| Auxiliary 2 pump overrun time | 114 | U16 | 1 | s |
| Auxiliary 2 pump idle days count | 115 | U16 | 1 | days |
| Auxiliary 1 pump overrun time | 119 | U16 | 1 | s |
| Burner cycle count | 128 | U32BE | 1 | |
| Burner run time | 130 | U32BE | 1 | h |
| CH pump cycle count | 132 | U32BE | 1 | |
| DHW pump cycle count | 134 | U32BE | 1 | |
| System pump cycle count | 136 | U32BE | 1 | |
| Boiler pump cycle count | 138 | U32BE | 1 | |
| Auxiliary pump cycle count | 140 | U32BE | 1 | |
| Controller cycle count | 142 | U32BE | 1 | |
| Controller run time | 144 | U32BE | 1 | h |
| Auxiliary 2 pump cycle count | 146 | U32BE | 1 | |
| Auxiliary 2 pump start delay time | 148 | U16 | 1 | s |
| Boiler pump start delay time | 149 | U16 | 1 | s |
| System pump start delay time | 150 | U16 | 1 | s |
| Auxiliary 1 pump start delay time | 151 | U16 | 1 | s |
| DHW tap heat demand | 152 | U16 | 1 | |
| DHW preheat demand | 153 | U16 | 1 | |
| DHW change rate | 154 | U16 | 0.1 | °C/s |
| DHW tap on recognition time | 155 | U16 | 1 | s |
| DHW tap on time | 156 | U16 | 1 | s |
| DHW preheat delay after tap time | 157 | U16 | 1 | s |
| DHW preheat on recognition time | 158 | U16 | 1 | s |
| DHW preheat on time | 159 | U16 | 1 | s |
| Lead Lag master status | 160 | U16 | 1 | |
| Lead Lag slave status | 161 | U16 | 1 | |
| Lead Lag master setpoint source | 162 | U16 | 1 | |
| Lead Lag master heat demand | 163 | U16 | 1 | |
| Lead Lag slave burner demand | 164 | U16 | 1 | |
| Lead Lag slave requested rate | 165 | U16 | 1 | RPM or % |
| Active Lead Lag on hysteresis | 166 | U16 | 0.1 | °C |
| Active Lead Lag off hysteresis | 167 | U16 | 0.1 | °C |
| Pump C status | 168 | U16 | 1 | |
| Outdoor temperature | 170 | U16 | 0.1 | °C |
| Outdoor sensor state | 171 | U16 | 1 | |
| Outlet T-rise rate | 172 | U16 | 0.1 | °C/s |
| Exchanger T-rise rate | 173 | U16 | 0.1 | °C/s |
| S10 sensor reading | 174 | U16 | 0.1 | °C |
| S10 sensor state | 175 | U16 | 1 | |
| Product type | 176 | U16 | 1 | |
| Password | 177 | U16 | 1 | |
| Temperature units | 178 | U16 | 1 | |
| Antishort cycle time | 179 | U16 | 1 | s |
| Alarm silence time | 180 | U16 | 1 | min |
| Power up with lockout | 181 | U16 | 1 | |
| Reset and restart | 182 | U16 | 1 | |
| Burner name | 183 | U16 | 1 | |
| Installation data | 184 | U16 | 1 | |
| OEM ID | 185 | U16 | 1 | |
| OS number | 186 | U16 | 1 | |
| Date code | 187 | U16 | 1 | |
| Safety microprocessor build | 188 | U16 | 1 | |
| Application microprocessor build | 189 | U16 | 1 | |
| Installer password | 190 | U16 | 1 | |
| OEM password | 191 | U16 | 1 | |
| Modulation output | 192 | U16 | 1 | |
| CH maximum modulation rate | 193 | U16 | 1 | RPM or % |
| DHW maximum modulation rate | 194 | U16 | 1 | RPM or % |
| Minimum modulation rate | 195 | U16 | 1 | RPM or % |
| Prepurge rate | 196 | U16 | 1 | RPM or % |
| Lightoff rate | 197 | U16 | 1 | RPM or % |
| Postpurge rate | 198 | U16 | 1 | RPM or % |
| CH forced rate | 199 | U16 | 1 | RPM or % |
| CH forced rate time | 200 | U16 | 1 | s |
| DHW forced rate | 201 | U16 | 1 | RPM or % |
| DHW forced rate time | 202 | U16 | 1 | s |
| Burner switch | 203 | U16 | 1 | |
| Firing rate control | 204 | U16 | 1 | |
| Manual firing rate | 205 | U16 | 1 | RPM or % |
| Analog output hysteresis | 206 | U16 | 1 | |
| Standby rate | 207 | U16 | 1 | RPM or % |
| CH enable | 208 | U16 | 1 | |
| CH demand switch | 209 | U16 | 1 | |
| CH modulation sensor | 210 | U16 | 1 | |
| CH setpoint | 211 | U16 | 0.1 | °C |
| CH time of day setpoint | 212 | U16 | 0.1 | °C |
| CH on hysteresis | 213 | U16 | 0.1 | °C |
| CH off hysteresis | 214 | U16 | 0.1 | °C |
| CH outdoor reset enable | 215 | U16 | 1 | |
| CH P-gain | 216 | U16 | 1 | |
| CH I-gain | 217 | U16 | 1 | |
| CH D-gain | 218 | U16 | 1 | |
| CH hysteresis step time | 219 | U16 | 1 | s |
| CH pressure setpoint | 220 | U16 | 0.1 | psi |
| CH pressure on hysteresis | 221 | U16 | 0.1 | psi |
| CH pressure off hysteresis | 222 | U16 | 0.1 | psi |
| Ignition source | 224 | U16 | 1 | |
| BLR/HSI function | 225 | U16 | 1 | |
| Igniter on during | 226 | U16 | 1 | |
| Pilot type | 227 | U16 | 1 | |
| Flame sensor type | 228 | U16 | 1 | |
| Purge rate proving | 229 | U16 | 1 | |
| Lightoff rate proving | 230 | U16 | 1 | |
| Prepurge time | 231 | U16 | 1 | s |
| Pre-ignition time | 232 | U16 | 1 | s |
| Pilot flame establishing period (PFEP) | 233 | U16 | 1 | |
| Main flame establishing period (MFEP) | 234 | U16 | 1 | s |
| Run stabilization time | 235 | U16 | 1 | s |
| Postpurge time | 236 | U16 | 1 | s |
| Interlock start check enable | 237 | U16 | 1 | |
| Interlock open response | 238 | U16 | 1 | |
| Ignite failure response | 239 | U16 | 1 | |
| Ignite failure retries | 240 | U16 | 1 | |
| Ignite failure delay | 241 | U16 | 1 | s |
| MFEP flame failure response | 242 | U16 | 1 | |
| Run flame failure response | 243 | U16 | 1 | |
| Pilot test hold | 244 | U16 | 1 | |
| Interrupted air switch (IAS) enable | 246 | U16 | 1 | |
| IAS start check enable | 247 | U16 | 1 | |
| LCI enable | 248 | U16 | 1 | |
| PII enable | 249 | U16 | 1 | |
| Flame threshold | 250 | U16 | 0.1 | μA |
| ILK/LCI bounce detection | 253 | U16 | 1 | |
| Forced recycle interval time | 254 | U16 | 1 | min |
| Fan speed error response | 255 | U16 | 1 | |
| Absolute maximum fan speed | 256 | U16 | 1 | RPM |
| Absolute minimum fan speed | 257 | U16 | 1 | RPM |
| Fan PWM frequency | 258 | U16 | 1 | |
| Fan pulses per revolution | 259 | U16 | 1 | |
| Fan speed-up ramp | 260 | U16 | 1 | RPM/s |
| Fan slow-down ramp | 261 | U16 | 1 | RPM/s |
| Fan gain up | 262 | U16 | 1 | |
| Fan gain down | 263 | U16 | 1 | |
| Fan minimum duty cycle | 264 | U16 | 1 | % |
| DHW upper modulation sensor | 270 | U16 | 1 | |
| DHW lower modulation sensor | 271 | U16 | 1 | |
| CH pump output | 272 | U16 | 1 | |
| CH pump control | 273 | U16 | 1 | |
| CH pump overrun time | 274 | U16 | 1 | s |
| CH FP pump overrun time | 275 | U16 | 1 | s |
| DHW pump output | 276 | U16 | 1 | |
| DHW pump control | 277 | U16 | 1 | |
| DHW pump overrun time | 278 | U16 | 1 | s |
| DHW FP pump overrun time | 279 | U16 | 1 | s |
| DHW pump start delay | 280 | U16 | 1 | s |
| Boiler pump output | 281 | U16 | 1 | |
| Boiler pump control | 282 | U16 | 1 | |
| Boiler pump overrun time | 283 | U16 | 1 | s |
| Auxiliary 1 pump output | 284 | U16 | 1 | |
| Auxiliary 1 pump control | 285 | U16 | 1 | |
| System pump output | 287 | U16 | 1 | |
| System pump control | 288 | U16 | 1 | |
| System pump overrun time | 289 | U16 | 1 | s |
| Pump exercise interval | 290 | U16 | 1 | days |
| Pump exercise time | 291 | U16 | 1 | s |
| CH pump start delay | 292 | U16 | 1 | s |
| Boiler pump start delay | 293 | U16 | 1 | s |
| System pump start delay | 294 | U16 | 1 | s |
| Auxiliary 1 pump start delay | 295 | U16 | 1 | s |
| CH pump options 1 | 296 | U16 | 1 | |
| CH pump options 2 | 297 | U16 | 1 | |
| DHW pump options 1 | 298 | U16 | 1 | |
| DHW pump options 2 | 299 | U16 | 1 | |
| Boiler pump options 1 | 300 | U16 | 1 | |
| Boiler pump options 2 | 301 | U16 | 1 | |
| System pump options 1 | 302 | U16 | 1 | |
| System pump options 2 | 303 | U16 | 1 | |
| Annunciation enable | 304 | U16 | 1 | |
| Annunciator mode | 305 | U16 | 1 | |
| Annunciator 1 configuration | 306 | U16 | 1 | |
| Annunciator 2 configuration | 319 | U16 | 1 | |
| Annunciator 3 configuration | 332 | U16 | 1 | |
| Annunciator 4 configuration | 345 | U16 | 1 | |
| Annunciator 5 configuration | 358 | U16 | 1 | |
| Annunciator 6 configuration | 371 | U16 | 1 | |
| Annunciator 7 configuration | 384 | U16 | 1 | |
| Annunciator 8 configuration | 397 | U16 | 1 | |
| PII configuration | 410 | U16 | 1 | |
| LCI configuration | 422 | U16 | 1 | |
| ILK configuration | 434 | U16 | 1 | |
| DHW enable | 448 | U16 | 1 | |
| DHW demand switch | 449 | U16 | 1 | |
| DHW priority vs CH | 450 | U16 | 1 | |
| DHW priority vs LL | 451 | U16 | 1 | |
| DHW priority time | 452 | U16 | 1 | s |
| DHW setpoint | 453 | U16 | 0.1 | °C |
| DHW time of day setpoint | 454 | U16 | 0.1 | °C |
| DHW on hysteresis | 455 | U16 | 0.1 | °C |
| DHW off hysteresis | 456 | U16 | 0.1 | °C |
| DHW P-gain | 457 | U16 | 1 | |
| DHW I-gain | 458 | U16 | 1 | |
| DHW D-gain | 459 | U16 | 1 | |
| DHW hysteresis step time | 460 | U16 | 1 | s |
| DHW modulation sensor | 461 | U16 | 1 | |
| DHW priority source | 463 | U16 | 1 | |
| Outlet high limit setpoint | 464 | U16 | 0.1 | °C |
| Outlet high limit response | 465 | U16 | 1 | |
| Stack limit enable | 466 | U16 | 1 | |
| Stack limit setpoint | 467 | U16 | 0.1 | °C |
| Stack limit response | 468 | U16 | 1 | |
| Stack limit delay | 469 | U16 | 1 | s |
| Delta-T inlet/outlet enable | 470 | U16 | 1 | |
| Delta-T inlet/outlet degrees | 471 | U16 | 0.1 | °C |
| Delta-T response | 472 | U16 | 1 | |
| Delta-T delay | 473 | U16 | 1 | s |
| DHW high limit enable | 474 | U16 | 1 | |
| DHW high limit setpoint | 475 | U16 | 0.1 | °C |
| DHW high limit response | 476 | U16 | 1 | |
| CH slow start enable | 477 | U16 | 1 | |
| DHW slow start enable | 478 | U16 | 1 | |
| Slow start ramp | 479 | U16 | 1 | |
| Slow start setpoint | 480 | U16 | 0.1 | °C |
| Outlet T-rise enable | 481 | U16 | 1 | |
| Outlet T-rise degrees | 482 | U16 | 0.1 | °C/min |
| Outlet T-rise delay | 483 | U16 | 1 | s |
| Outlet high limit enable | 484 | U16 | 1 | |
| Delta-T retry limit | 485 | U16 | 1 | |
| Delta-T rate limit enable | 486 | U16 | 1 | |
| Delta-T inverse limit time | 487 | U16 | 1 | s |
| Delta-T inverse limit response | 488 | U16 | 1 | |
| Delta-T exchanger/outlet enable | 489 | U16 | 1 | |
| Delta-T exchanger/outlet degrees | 490 | U16 | 0.1 | °C |
| Exchanger T-rise enable | 491 | U16 | 1 | |
| T-rise response | 492 | U16 | 1 | |
| T-rise retry limit | 493 | U16 | 1 | |
| Delta-T inlet/exchanger enable | 494 | U16 | 1 | |
| Delta-T inlet/exchanger degrees | 495 | U16 | 0.1 | °C |
| CH anticondensation enable | 496 | U16 | 1 | |
| CH anticondensation setpoint | 497 | U16 | 0.1 | °C |
| DHW anticondensation enable | 499 | U16 | 1 | |
| DHW anticondensation setpoint | 500 | U16 | 0.1 | °C |
| Anticondensation priority | 502 | U16 | 1 | |
| Frost protection anticondensation enable | 503 | U16 | 1 | |
| DHW storage enable | 504 | U16 | 1 | |
| DHW storage time | 505 | U16 | 1 | s |
| DHW storage setpoint | 506 | U16 | 0.1 | °C |
| DHW storage on hysteresis | 507 | U16 | 0.1 | °C |
| DHW storage off hysteresis | 508 | U16 | 0.1 | °C |
| DHW priority method | 509 | U16 | 1 | |
| DHW DEMAND ON TEMPERATURE | 510 | U16 | 1 | |
| DHW DEMAND OFF TEMPERATURE | 511 | U16 | 1 | |
| CH ODR maximum outdoor temperature | 512 | U16 | 0.1 | °C |
| CH ODR minimum outdoor temperature | 513 | U16 | 0.1 | °C |
| CH ODR low water temperature | 514 | U16 | 0.1 | °C |
| CH ODR boost time | 515 | U16 | 1 | s |
| CH ODR boost maximum off point | 516 | U16 | 0.1 | °C |
| Lead Lag CH ODR maximum outdoor temperature | 517 | U16 | 0.1 | °C |
| Lead Lag CH ODR minimum outdoor temperature | 518 | U16 | 0.1 | °C |
| Lead Lag CH ODR low water temperature | 519 | U16 | 0.1 | °C |
| Lead Lag CH ODR boost time | 520 | U16 | 1 | s |
| Lead Lag CH ODR boost maximum off point | 521 | U16 | 0.1 | °C |
| CH ODR boost step | 522 | U16 | 0.1 | °C |
| Minimum boiler water temperature | 526 | U16 | 0.1 | °C |
| Lead Lag CH ODR minimum water temperature | 527 | U16 | 0.1 | °C |
| CH frost protection enable | 528 | U16 | 1 | |
| DHW frost protection enable | 529 | U16 | 1 | |
| Outdoor frost protection setpoint | 530 | U16 | 0.1 | °C |
| Lead Lag frost protection enable | 532 | U16 | 1 | |
| Lead Lag frost protection rate | 533 | U16 | 0.1 | % |
| IAS open modulation enable | 536 | U16 | 1 | |
| IAS open rate differential | 537 | U16 | 1 | |
| IAS open modulation step rate | 538 | U16 | 1 | |
| IAS open modulation step time | 539 | U16 | 1 | s |
| IAS closed response | 540 | U16 | 1 | |
| CH minimum pressure | 541 | U16 | 0.1 | psi |
| CH time of day pressure setpoint | 542 | U16 | 0.1 | psi |
| Analog input hysteresis | 543 | U16 | 0.1 | mA |
| Lead Lag slave enable | 544 | U16 | 1 | |
| Lead Lag master enable | 545 | U16 | 1 | |
| Lead Lag setpoint | 546 | U16 | 0.1 | °C |
| Lead Lag time of day setpoint | 547 | U16 | 0.1 | °C |
| Lead Lag outdoor reset enable | 548 | U16 | 1 | |
| Lead Lag on hysteresis | 549 | U16 | 0.1 | °C |
| Lead Lag off hysteresis | 550 | U16 | 0.1 | °C |
| Lead Lag hysteresis step time | 551 | U16 | 1 | s |
| Lead Lag P-gain | 552 | U16 | 1 | |
| Lead Lag I-gain | 553 | U16 | 1 | |
| Lead Lag D-gain | 554 | U16 | 1 | |
| Lead Lag operation switch | 555 | U16 | 1 | |
| Lead Lag CH demand switch | 556 | U16 | 1 | |
| Lead Lag CH setpoint source | 557 | U16 | 1 | |
| Lead Lag modulation sensor | 558 | U16 | 1 | |
| Lead Lag modulation backup sensor | 559 | U16 | 1 | |
| Lead Lag CH 4 mA water temperature | 560 | U16 | 0.1 | °C |
| Lead Lag CH 20 mA water temperature | 561 | U16 | 0.1 | °C |
| Lead Lag CH Modbus setpoint | 562 | U16 | 0.1 | °C |
| Lead Lag CH Modbus STAT | 563 | U16 | 1 | |
| Slave mode | 564 | U16 | 1 | |
| Slave command | 565 | U16 | 1 | |
| Base load rate | 566 | U16 | 1 | |
| Fan during off cycle rate | 567 | U16 | 1 | |
| Slave sequence order | 568 | U16 | 1 | |
| Lead Lag Modbus port | 569 | U16 | 1 | |
| Slave demand to firing delay | 570 | U16 | 1 | s |
| Slave capacity | 571 | U16 | 1 | MBH |
| Base load common rate | 572 | U16 | 0.1 | % |
| Rate allocation method | 573 | U16 | 1 | |
| Lead allocation method | 574 | U16 | 1 | |
| Lag allocation method | 575 | U16 | 1 | |
| CH Modbus STAT | 577 | U16 | 1 | |
| CH setpoint source | 578 | U16 | 1 | |
| CH Modbus setpoint | 579 | U16 | 0.1 | °C |
| CH modulation rate source | 580 | U16 | 1 | |
| CH Modbus rate | 581 | U16 | 1 | |
| CH priority vs. Lead Lag | 582 | U16 | 1 | |
| CH 4mA water temperature | 583 | U16 | 0.1 | °C |
| CH 20mA water temperature | 584 | U16 | 0.1 | °C |
| CH 4mA steam pressure | 585 | U16 | 0.1 | psi |
| CH 20mA steam pressure | 586 | U16 | 0.1 | psi |
| CH MODBUS STEAM SETPOINT | 587 | U16 | 1 | |
| CH HOT STANDBY ENABLE | 588 | U16 | 1 | |
| Heat exchanger high limit enable | 592 | U16 | 1 | |
| Heat exchanger high limit setpoint | 593 | U16 | 0.1 | °C |
| Heat exchanger high limit response | 594 | U16 | 1 | |
| Heat exchanger high limit delay | 595 | U16 | 1 | s |
| Heat exchanger retry limit | 596 | U16 | 1 | |
| PREFERRED OUTLET HIGH LIMIT | 597 | U16 | 1 | |
| PREFERRED STACK LIMIT SETPOINT | 598 | U16 | 1 | |
| FLAME FAILURE RESPONSE TIME | 599 | U16 | 1 | s |
| DBI External Igniter On Time | 600 | U16 | 1 | s |
| Flow Switch Enable | 601 | U16 | 1 | |
| Flow Switch Debounce Time | 602 | U16 | 0.1 | s |
| Damper Proving Enable | 603 | U16 | 1 | |
| Damper Proving Debounce Time | 604 | U16 | 1 | s |
| S1 (J8-4) connector type | 608 | U16 | 1 | |
| S2 (J8-6) connector type | 609 | U16 | 1 | |
| S3S4 (J8-8, 10) connector type | 610 | U16 | 1 | |
| S5 (J8-11) connector type | 611 | U16 | 1 | |
| S6S7 (J9-1, 3) connector type | 612 | U16 | 1 | |
| S8S9 (J9-4, 6) connector type | 613 | U16 | 1 | |
| S10 (J10-7) connector type | 614 | U16 | 1 | |
| Outdoor temperature correction offset | 615 | U16 | 1 | |
| Pressure correction offset | 616 | U16 | 1 | |
| Low fire cutoff time | 617 | U16 | 1 | |
| DOE Energy Saving | 618 | U16 | 1 | |
| Modbus Heartbeat | 619 | U16 | 1 | |
| Modbus Heartbeat Timeout | 620 | U16 | 1 | s |
| Modbus Lockout | 621 | U16 | 1 | |
| Modbus Blower/HSI Output | 622 | U16 | 1 | |
| Modbus Blower/HIS Output Control | 623 | U16 | 1 | |
| Installer passcode | 624 | U16 | 1 | |
| OEM passcode | 625 | U16 | 1 | |
| Outdoor temperature source | 626 | U16 | 1 | |
| Warm weather shutdown enable | 627 | U16 | 1 | |
| Warm weather shutdown setpoint | 628 | U16 | 0.1 | °C |
| Use STAT with EnviraCOM remote stat | 629 | U16 | 1 | |
| Line frequency | 630 | U16 | 1 | |
| Safety configuration options | 631 | U16 | 1 | |
| Controller interaction enable | 632 | U16 | 1 | |
| Blocked condensate enable | 633 | U16 | 1 | |
| Flap valve controller ID | 634 | U16 | 1 | |
| Number of controllers in flap valve system | 635 | U16 | 1 | |
| Maximum firing rate when neighbor starts up | 636 | U16 | 1 | |
| Stack fault from neighbor enable | 637 | U16 | 1 | |
| SOFT LOCKOUT ENABLE | 638 | U16 | 1 | |
| BURNER OFF INHIBIT TIME | 639 | U16 | 1 | |
| Modbus Analog Output | 668 | U16 | 0.1 | % |
| Modbus Analog Output Control | 669 | U16 | 1 | |
| IAS Open Modulation Step Down | 670 | U16 | 1 | |
| IAS Open Modulation Step Down Time | 671 | U16 | 1 | s |
| Plate preheat delay after tap | 688 | U16 | 1 | s |
| Plate preheat setpoint | 689 | U16 | 0.1 | °C |
| Plate preheat on recognition time | 690 | U16 | 1 | s |
| Plate preheat on hysteresis | 691 | U16 | 0.1 | °C |
| Plate preheat off hysteresis | 692 | U16 | 0.1 | °C |
| Plate preheat minimum on time | 693 | U16 | 1 | s |
| Tap detect degrees | 694 | U16 | 0.1 | °C/s |
| Tap detect on hysteresis | 695 | U16 | 0.1 | °C |
| Tap detect on recognition time | 696 | U16 | 1 | s |
| Tap stop DHW-Inlet degrees | 697 | U16 | 0.1 | °C |
| Tap stop Outlet-Inlet degrees | 698 | U16 | 0.1 | °C |
| Tap minimum on time | 699 | U16 | 1 | s |
| Tap detect on threshold | 700 | U16 | 0.1 | °C |
| Preheat detect on threshold | 701 | U16 | 0.1 | °C |
| Preheat detect off threshold | 702 | U16 | 0.1 | °C |
| Lead Lag DHW demand switch | 704 | U16 | 1 | |
| Lead Lag DHW setpoint | 705 | U16 | 0.1 | °C |
| Lead Lag DHW priority vs. CH | 706 | U16 | 1 | |
| Slave dropout/return compensation | 713 | U16 | 1 | |
| Add stage method | 714 | U16 | 1 | |
| Add stage detection time | 716 | U16 | 1 | s |
| Add stage error threshold | 718 | U16 | 0.1 | °C |
| Add stage rate offset | 719 | U16 | 0.1 | % |
| Add stage error gain | 720 | U16 | 1 | |
| Add stage rate gain | 721 | U16 | 1 | |
| Add stage inter-stage delay | 722 | U16 | 1 | s |
| Drop stage method | 723 | U16 | 1 | |
| Drop stage detection time | 725 | U16 | 1 | s |
| Drop stage error threshold | 727 | U16 | 0.1 | °C |
| Drop stage rate offset | 728 | U16 | 0.1 | % |
| Drop stage error gain | 729 | U16 | 1 | |
| Drop stage rate gain | 730 | U16 | 1 | |
| Drop stage inter-stage delay | 731 | U16 | 1 | s |
| Lead rotation time | 733 | U16 | 1 | min |
| Force lead rotation time | 734 | U16 | 1 | min |
| Lead Lag DHW time of day setpoint | 735 | U16 | 0.1 | °C |
| Boiler off options | 736 | U16 | 1 | |
| All boilers off threshold | 737 | U16 | 0.1 | °C |
| Lead Lag pressure setpoint | 738 | U16 | 0.1 | psi |
| Lead Lag pressure TOD setpoint | 739 | U16 | 0.1 | psi |
| Lead Lag pressure on hysteresis | 740 | U16 | 0.1 | psi |
| Lead Lag pressure off hysteresis | 741 | U16 | 0.1 | psi |
| Add stage pressure error threshold | 742 | U16 | 0.1 | psi |
| Drop stage pressure error threshold | 743 | U16 | 0.1 | psi |
| Lead Lag minimum pressure | 744 | U16 | 0.1 | psi |
| Lead Lag 4 mA steam pressure | 745 | U16 | 0.1 | psi |
| Lead Lag 20 mA steam pressure | 746 | U16 | 0.1 | psi |
| Lead Lag Modbus pressure setpoint | 747 | U16 | 0.1 | psi |
| Lead Lag manual slave request | 748 | U16 | 1 | |
| Lead Lag manual slave rate | 749 | U16 | 1 | |
| Auxiliary 1 pump overrun time | 752 | U16 | 1 | s |
| Auxiliary 1 pump options 1 | 753 | U16 | 1 | |
| Auxiliary 1 pump options 2 | 754 | U16 | 1 | |
| Auxiliary 2 pump output | 755 | U16 | 1 | |
| Auxiliary 2 pump control | 756 | U16 | 1 | |
| Auxiliary 2 pump start delay | 757 | U16 | 1 | s |
| Auxiliary 2 pump overrun time | 758 | U16 | 1 | s |
| Auxiliary 2 pump options 1 | 759 | U16 | 1 | |
| Auxiliary 2 pump options 2 | 760 | U16 | 1 | |
| Lead Lag active service | 768 | U16 | 1 | |
| Slave 1 address | 769 | U16 | 1 | |
| Slave 1 state | 770 | U16 | 1 | |
| Slave 1 stage order | 771 | U16 | 1 | |
| Slave 1 firing rate | 772 | U16 | 1 | |
| Slave 2 address | 773 | U16 | 1 | |
| Slave 2 state | 774 | U16 | 1 | |
| Slave 2 stage order | 775 | U16 | 1 | |
| Slave 2 firing rate | 776 | U16 | 1 | |
| Slave 3 address | 777 | U16 | 1 | |
| Slave 3 state | 778 | U16 | 1 | |
| Slave 3 stage order | 779 | U16 | 1 | |
| Slave 3 firing rate | 780 | U16 | 1 | |
| Slave 4 address | 781 | U16 | 1 | |
| Slave 4 state | 782 | U16 | 1 | |
| Slave 4 stage order | 783 | U16 | 1 | |
| Slave 4 firing rate | 784 | U16 | 1 | |
| Slave 5 address | 785 | U16 | 1 | |
| Slave 5 state | 786 | U16 | 1 | |
| Slave 5 stage order | 787 | U16 | 1 | |
| Slave 5 firing rate | 788 | U16 | 1 | |
| Slave 6 address | 789 | U16 | 1 | |
| Slave 6 state | 790 | U16 | 1 | |
| Slave 6 stage order | 791 | U16 | 1 | |
| Slave 6 firing rate | 792 | U16 | 1 | |
| Slave 7 address | 793 | U16 | 1 | |
| Slave 7 state | 794 | U16 | 1 | |
| Slave 7 stage order | 795 | U16 | 1 | |
| Slave 7 firing rate | 796 | U16 | 1 | |
| Slave 8 address | 797 | U16 | 1 | |
| Slave 8 state | 798 | U16 | 1 | |
| Slave 8 stage order | 799 | U16 | 1 | |
| Slave 8 firing rate | 800 | U16 | 1 | |
| Lead boiler address | 801 | U16 | 1 | |
| Master firing rate | 802 | U16 | 1 | |
| Active Lead Lag pressure setpoint | 803 | U16 | 0.1 | psi |
| Active Lead Lag pressure on hysteresis | 804 | U16 | 0.1 | psi |
| Active Lead Lag pressure off hysteresis | 805 | U16 | 0.1 | psi |
| Active Lead Lag pressure operating point | 806 | U16 | 0.1 | psi |
| Flap valve system state | 816 | U16 | 1 | |
| Lockout history record 1 | 864 | U16 | 1 | |
| Lockout history record 2 | 880 | U16 | 1 | |
| Lockout history record 3 | 898 | U16 | 1 | |
| Lockout history record 4 | 915 | U16 | 1 | |
| Lockout history record 5 | 932 | U16 | 1 | |
| Lockout history record 6 | 949 | U16 | 1 | |
| Lockout history record 7 | 966 | U16 | 1 | |
| Lockout history record 8 | 983 | U16 | 1 | |
| Lockout history record 9 | 1000 | U16 | 1 | |
| Lockout history record 10 | 1017 | U16 | 1 | |
| Lockout history record 11 | 1034 | U16 | 1 | |
| Lockout history record 12 | 1051 | U16 | 1 | |
| Lockout history record 13 | 1068 | U16 | 1 | |
| Lockout history record 14 | 1085 | U16 | 1 | |
| Lockout history record 15 | 1102 | U16 | 1 | |
| Alarm code | 1119 | U16 | 1 | |
| Alert log record 1 | 1120 | U16 | 1 | |
| Alert log record 2 | 1126 | U16 | 1 | |
| Alert log record 3 | 1132 | U16 | 1 | |
| Alert log record 4 | 1138 | U16 | 1 | |
| Alert log record 5 | 1144 | U16 | 1 | |
| Alert log record 6 | 1150 | U16 | 1 | |
| Alert log record 7 | 1156 | U16 | 1 | |
| Alert log record 8 | 1162 | U16 | 1 | |
| Alert log record 9 | 1168 | U16 | 1 | |
| Alert log record 10 | 1174 | U16 | 1 | |
| Alert log record 11 | 1180 | U16 | 1 | |
| Alert log record 12 | 1186 | U16 | 1 | |
| Alert log record 13 | 1192 | U16 | 1 | |
| Alert log record 14 | 1198 | U16 | 1 | |
| Alert log record 15 | 1204 | U16 | 1 | |
| Alert data 1 | 1210 | U16 | 1 | |
| Alert data 2 | 1211 | U16 | 1 | |
| Alert data 3 | 1212 | U16 | 1 | |
| Alert data 4 | 1213 | U16 | 1 | |
| Alert data 5 | 1214 | U16 | 1 | |
| Alert data 6 | 1215 | U16 | 1 | |
| Alert data 7 | 1216 | U16 | 1 | |
| Alert data 8 | 1217 | U16 | 1 | |
| Alert data 9 | 1218 | U16 | 1 | |
| Alert data 10 | 1219 | U16 | 1 | |
| Alert data 11 | 1220 | U16 | 1 | |
| Alert data 12 | 1221 | U16 | 1 | |
| Alert data 13 | 1222 | U16 | 1 | |
| Alert data 14 | 1223 | U16 | 1 | |
| Alert data 15 | 1224 | U16 | 1 |
| terminals | 3-pin connector |
| A/B polarity | Terminal 1: Data + (a), Terminal 2: Data - (b), Terminal 3: Common (c) |
| connector | 3-pin connector |
| wiring notes | MB1 or MB2 Modbus ports |
| max registers/read | 125 |
| sentinel values | 0x8FFF for unconfigured temperature parameters, 0x7FFF or 0x8200 for no sensor configured, 0x8000 for shorted, 0x8100 for open, 0x8300 for outside high range, 0x8400 for outside low range, 0x8500 for not reliable. |
| protocol notes | Except for variable length data items, registers can be accessed as a single register or up to 20 registers for writes and 125 registers for reads. Variable length data must be accessed individually. |
| model register | 176 |
| firmware register | 186 |
| identification notes | Report Slave ID (FC17) returns OS number and Burner name. OS number is also at register 186, Burner name is at 183. |
| FC 43 device ID | not supported |
| doc revision | 4.1.1 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.