device library

IME Nemo 96HD/HD+ meter (needs IF96001 RS485 module)

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Current transformer ratio (KTA)256U161
Voltage transformer ratio (KTV)258U160.1
Device configuration260U32BE1
Voltage transformer ratio (KTV)262U160.01
Device identifier768U161
Phase 1 : phase voltage769U32BE1mV
Phase 2 : phase voltage773U32BE1mV
Phase 3 : phase voltage777U32BE1mV
Phase 1 : current781U32BE1mA
Phase 2 : current785U32BE1mA
Phase 3 : current789U32BE1mA
3-phase : active power793U32BE1
3-phase : reactive power797U32BE1
3-phase : apparent power801U32BE1
3-phase : positive active energy805U32BE1
Chained voltage : L1-L2809U32BE1mV
Chained voltage : L2-L3813U32BE1mV
Chained voltage : L3-L1817U32BE1mV
3-phase : negative active energy821U32BE1
Frequency825U160.1Hz
Operating timer counter827U161h
3-phase : power factor829I160.01
3-phase : sector of power factor831U161
Voltages sequence diagnostic832U161
Output relay status833U161
3-phase : positive reactive energy835U32BE1
3-phase : sign of active power839U161
3-phase : negative reactive energy840U32BE1
3-phase : sign of reactive power844U161
3-phase : average power848U32BE1
3-phase : peak maximum demand852U32BE1
Time counter for average power856U161minutes
Neutral current857U32BE1mA
Phase 1 : active power861U32BE1
Phase 2 : active power865U32BE1
Phase 3 : active power869U32BE1
Phase 1 : sign of active power873U161
Phase 2 : sign of active power874U161
Phase 3 : sign of active power875U161
Phase 1 : reactive power876U32BE1
Phase 2 : reactive power880U32BE1
Phase 3 : reactive power884U32BE1
Phase 1 : sign of reactive power888U161
Phase 2 : sign of reactive power889U161
Phase 3 : sign of reactive power890U161
Phase 1 : apparent power891U32BE1
Phase 2 : apparent power895U32BE1
Phase 3 : apparent power899U32BE1
Phase 1 : power factor903I160.01
Phase 2 : power factor905I160.01
Phase 3 : power factor907I160.01
Phase 1 : power factor sector909U161
Phase 2 : power factor sector910U161
Phase 3 : power factor sector911U161
Phase 1 : THD V1912U161%
Phase 2 : THD V2914U161%
Phase 3 : THD V3916U161%
Phase 1 : THD I1918U161%
Phase 2 : THD I2920U161%
Phase 3 : THD I3922U161%
Phase 1 : I1 average924U32BE1mA
Phase 2 : I2 average928U32BE1mA
Phase 3 : I3 average932U32BE1mA
Phase 1 : I1 peak maximum936U32BE1mA
Phase 2 : I2 peak maximum940U32BE1mA
Phase 3 : I3 peak maximum944U32BE1mA
(I1+I2+I3)/3948U32BE1mA
Phase 1 : V1 min952U32BE1mV
Phase 2 : V2 min956U32BE1mV
Phase 3 : V3 min960U32BE1mV
Phase 1 : V1 max964U32BE1mV
Phase 2 : V2 max968U32BE1mV
Phase 3 : V3 max972U32BE1mV
3-phase : active partial energy976U32BE1
3-phase : reactive partial energy980U32BE1
3-phase : active average power984U32BE1
3-phase : reactive average power988U32BE1
3-phase : apparent average power992U32BE1
3-phase : active PMD power996U32BE1
3-phase : reactive PMD power1000U32BE1
3-phase : apparent PMD power1004U32BE1
Pulse counting 1 on IO Module1008U32BE1
Pulse counting 2 on IO Module1012U32BE1
Pulse counting 3 on IO Module / Temperature First Channel1016U32BE0.01°C
Pulse counting 4 on IO Module / Temperature Second Channel1020U32BE0.01°C
Status of input 1 on IO Module1024U161
Status of input 2 on IO Module1025U161
Status of input 3 on IO Module / Sign Temperature First Channel1026U161
Status of input 4 on IO Module / Sign Temperature Second Channel1027U161
Code to reset one Pulse Counting1296U161
Phase 1 : phase voltage4096U32BE1mV
Phase 2 : phase voltage4098U32BE1mV
Phase 3 : phase voltage4100U32BE1mV
Phase 1 : current4102U32BE1mA
Phase 2 : current4104U32BE1mA
Phase 3 : current4106U32BE1mA
Neutral current4108U32BE1mA
Chained voltage : L1-L24110U32BE1mV
Chained voltage : L2-L34112U32BE1mV
Chained voltage : L3-L14114U32BE1mV
3-phase : active power4116U32BE1
3-phase : reactive power4118U32BE1
3-phase : apparent power4120U32BE1
3-phase : sign of active power4122U161
3-phase : sign of reactive power4123U161
3-phase : positive active energy4124U32BE1
3-phase : positive reactive energy4126U32BE1
3-phase : negative active energy4128U32BE1
3-phase : negative reactive energy4130U32BE1
3-phase : power factor4132I160.01
3-phase : sector of power factor4133U161
Frequency4134U160.1Hz
3-phase : average power4135U32BE1
3-phase : peak maximum demand4137U32BE1
Time counter for average power4139U161minutes
Phase 1 : active power4140U32BE1
Phase 2 : active power4142U32BE1
Phase 3 : active power4144U32BE1
Phase 1 : sign of active power4146U161
Phase 2 : sign of active power4147U161
Phase 3 : sign of active power4148U161
Phase 1 : reactive power4149U32BE1
Phase 2 : reactive power4151U32BE1
Phase 3 : reactive power4153U32BE1
Phase 1 : sign of reactive power4155U161
Phase 2 : sign of reactive power4156U161
Phase 3 : sign of reactive power4157U161
Phase 1 : apparent power4158U32BE1
Phase 2 : apparent power4160U32BE1
Phase 3 : apparent power4162U32BE1
Phase 1 : power factor4164I160.01
Phase 2 : power factor4165I160.01
Phase 3 : power factor4166I160.01
Phase 1 : power factor sector4167U161
Phase 2 : power factor sector4168U161
Phase 3 : power factor sector4169U161
Phase 1 : THD V14170U160.1%
Phase 2 : THD V24171U160.1%
Phase 3 : THD V34172U160.1%
Phase 1 : THD I14173U160.1%
Phase 2 : THD I24174U160.1%
Phase 3 : THD I34175U160.1%
Phase 1 : I1 average4176U32BE1mA
Phase 2 : I2 average4178U32BE1mA
Phase 3 : I3 average4180U32BE1mA
Phase 1 : I1 peak maximum4182U32BE1mA
Phase 2 : I2 peak maximum4184U32BE1mA
Phase 3 : I3 peak maximum4186U32BE1mA
(I1+I2+I3)/34188U32BE1mA
Phase 1 : V1 min4190U32BE1mV
Phase 2 : V2 min4192U32BE1mV
Phase 3 : V3 min4194U32BE1mV
Phase 1 : V1 max4196U32BE1mV
Phase 2 : V2 max4198U32BE1mV
Phase 3 : V3 max4200U32BE1mV
3-phase : active partial energy4202U32BE1
3-phase : reactive partial energy4204U32BE1
Operating timer counter4206U161H
Output relay status4207U161
3-phase : active average power4208U32BE1
3-phase : reactive average power4210U32BE1
3-phase : apparent average power4212U32BE1
3-phase : active PMD power4214U32BE1
3-phase : reactive PMD power4216U32BE1
3-phase : apparent PMD power4218U32BE1
Signed temperature First Channel4352I161°C
Signed temperature Second Channel4353I161°C
Current transformer ratio (KTA)4608U161
Voltage transformer ratio (KTV)4609U160.1
Device configuration4610U32BE1
Device identifier4612U161
Voltages sequence diagnostic4613U161
RFU4614U161
Voltage transformer ratio (KTV)4615U160.01
Low Positive Active Energy5376U32BE1
High Positive Active Energy5378U32BE1
Low Positive Reactive Energy5380U32BE1
High Positive Reactive Energy5382U32BE1
Low Negative Active Energy5384U32BE1
High Negative Active Energy5386U32BE1
Low Negative Reactive Energy5388U32BE1
High Negative Reactive Energy5390U32BE1
Low Partial Active Energy5392U32BE1
High Partial Active Energy5394U32BE1
Low Partial Reactive Energy5396U32BE1
High Partial Reactive Energy5398U32BE1
Signed Total Active Power5400I32BE1
Signed Total Reactive Power5402I32BE1
Signed Phase1 Active Power5404I32BE1
Signed Phase2 Active Power5406I32BE1
Signed Phase3 Active Power5408I32BE1
Signed Phase1 Reactive Power5410I32BE1
Signed Phase2 Reactive Power5412I32BE1
Signed Phase3 Reactive Power5414I32BE1
Signed Total Power Factor5416I32BE0.01
Signed Phase1 Power Factor5418I32BE0.01
Signed Phase2 Power Factor5420I32BE0.01
Signed Phase3 Power Factor5422I32BE0.01
Apparent power5424U32BE1
Average active power5426U32BE1
Average reactive power5428U32BE1
Average apparent power5430U32BE1
Max active power5432U32BE1
Max reactive power5434U32BE1
Max apparent power5436U32BE1
W1 : custom page – line 18192U161
W2 : custom page – line 28193U161
W3 : custom page – line 38194U161
W4 : wiring8195U161
W5 : average maximum demand calculation8196U161
W6 : display contrast8197U161
W7 : backlight intensity8198U161
W8 : rated current8199U161
Programming parameters of Module on SLOT 18448U161
Programming parameters of Module on SLOT 28704U161
Programming parameters of Module on SLOT 38960U161
Reset Word9216U161
Saving in EEPROM parameters changed by Remote commands9728U161
Enable Remote Writing Operation (master Unlock Key)9984U161
Load previous setup parameters stored in EEPROM10240U161
To set relays on LOCAL or REMOTE control12544U161
To open or close relays on IO Module12800U161

link settings as documented (unverified): RTU; FC 03,16; MODBUS / JBUS compatible. Up to 255 different instruments can be managed by the protocol.

bench facts as documented (unverified)
terminals2-wire
wiring notesEIA-RS485 standard in half-duplex modality. Only 32 instruments can be attached on the same physical line (master included).
max registers/read120
broadcastsupported
protocol notesVariables or groups of variables may be required up to 100 BYTES (sw. version < 1.09) or up to 240 BYTES (sw. version >= 1.09).
identification notesDevice identifier register at 0x300 (value 0x10) or 0x1204 (value 0x10).
doc revisionB
firmware applicability3.18
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms framing: RTU, function codes: 3, 16, stop bits: 1 — confirmed by Rayleigh Instruments Nemo 96HD/HD+ MODBUS manual (PR 106 rev. 4) [1.2.7]
  • confirmed: Device identifier register at 0x300 (value 0x10) or 0x1204 (value 0x10) — confirmed by Rayleigh Instruments Nemo 96HD/HD+ MODBUS manual (PR 106 rev. 4)
  • confirmed: EIA-RS485 standard in half-duplex modality. Only 32 instruments can be attached on the same physical line (master included). — confirmed by Rayleigh Instruments Nemo 96HD/HD+ MODBUS manual (PR 106 rev. 4)
  • confirmed: Variables or groups of variables may be required up to 100 BYTES (sw. version < 1.09) or up to 240 BYTES (sw. version >= 1.09). — confirmed by BTicino/Legrand COMMUNICATION MODBUS PROTOCOL MF96001 / 021 NEMO 96HD manual
  • confirmed: Register map addresses (e.g., phase_1_phase_voltage @ 769, phase_1_current @ 781, three_phase_active_power @ 793) — confirmed by BTicino/Legrand COMMUNICATION MODBUS PROTOCOL MF96001 / 021 NEMO 96HD manual (where 0x301 = 769, 0x30d = 781, 0x319 = 793)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.