Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Program status | 31 | U16 | 1 | |
| Controller status | 32 | U16 | 1 | |
| Binary outputs 1 - 10 | 33 | U16 | 1 | |
| Binary inputs 1 - 6 | 35 | U16 | 1 | |
| Limit comparator | 36 | U16 | 1 | |
| Control contacts 1-4 | 37 | U16 | 1 | |
| Binary signals | 38 | U16 | 1 | |
| Control of the binary outputs | 39 | U16 | 1 | |
| Analog input 1 | 40 | F32LE | 1 | mV |
| Analog input 2 | 42 | F32LE | 1 | mV |
| Internal Pt100 | 48 | F32LE | 1 | Ohm |
| Sampling cycle time | 52 | U16 | 1 | |
| Analog input 1 | 53 | F32LE | 1 | degree |
| Analog input 2 | 55 | F32LE | 1 | degree |
| Math 1 | 61 | F32LE | 1 | |
| Math 2 | 63 | F32LE | 1 | |
| Ramp end value (W) | 65 | F32LE | 1 | |
| Filtered process value | 67 | F32LE | 1 | |
| Unfiltered process value | 69 | F32LE | 1 | |
| Setpoint | 71 | F32LE | 1 | |
| Output -100 to 100% (displayed value) | 73 | F32LE | 1 | % |
| Output, heating 0 to 100% | 75 | F32LE | 1 | % |
| Output, cooling -100 to 0% | 77 | F32LE | 1 | % |
| Control difference | 79 | F32LE | 1 | |
| Switching status, heating (1 = contact closed/ON) | 83 | U16 | 1 | |
| Switching status, cooling (1 = contact closed/ON) | 84 | U16 | 1 | |
| Parameter set number 0 - 1 | 85 | U16 | 1 | |
| Manual output | 86 | U16 | 1 | |
| Segment number (1 - 8) | 87 | U16 | 1 | |
| Number of segments (1- 8) | 88 | U16 | 1 | |
| Program setpoint | 89 | F32LE | 1 | |
| Program run time | 91 | U32LE | 1 | seconds |
| Residual program time | 93 | U32LE | 1 | seconds |
| Segment run time | 97 | U32LE | 1 | |
| Residual segment time | 99 | U32LE | 1 | |
| Timer run time, timer 1 | 103 | U32LE | 1 | |
| Timer run time, timer 2 | 105 | U32LE | 1 | |
| Timer run time, timer 3 | 107 | U32LE | 1 | |
| Timer run time, timer 4 | 109 | U32LE | 1 | |
| Binary functions "Program controller" | 111 | U16 | 1 | |
| Binary functions "Controller" | 112 | U16 | 1 | |
| Binary functions "Operation" | 113 | U16 | 1 | |
| Binary functions "Timer" | 114 | U16 | 1 | |
| Setpoint switching | 115 | U16 | 1 | |
| Parameter set switching | 116 | U16 | 1 | |
| Limit comparator 1, limit AL | 119 | F32LE | 1 | |
| Limit comparator 1, switching differential | 121 | F32LE | 1 | |
| Limit comparator 1, switch-on delay | 123 | U16 | 1 | |
| Limit comparator 1, switch-off delay | 124 | U16 | 1 | |
| Limit comparator 2, limit AL | 125 | F32LE | 1 | |
| Limit comparator 2, switching differential | 127 | F32LE | 1 | |
| Limit comparator 2, switch-on delay | 129 | U16 | 1 | |
| Limit comparator 2, switch-off delay | 130 | U16 | 1 | |
| Limit comparator 3, limit AL | 131 | F32LE | 1 | |
| Limit comparator 3, switching differential | 133 | F32LE | 1 | |
| Limit comparator 3, switch-on delay | 135 | U16 | 1 | |
| Limit comparator 3, switch-off delay | 136 | U16 | 1 | |
| Limit comparator 4, limit AL | 137 | F32LE | 1 | |
| Limit comparator 4, switching differential | 139 | F32LE | 1 | |
| Limit comparator 4, switch-on delay | 141 | U16 | 1 | |
| Limit comparator 4, switch-off delay | 142 | U16 | 1 | |
| Ramp function, slope | 143 | F32LE | 1 | |
| Segment setpoint 1 | 145 | F32LE | 1 | |
| Segment time 1 | 147 | U32LE | 1 | |
| Segment setpoint 2 | 149 | F32LE | 1 | |
| Segment time 2 | 151 | U32LE | 1 | |
| Segment setpoint 3 | 153 | F32LE | 1 | |
| Segment time 3 | 155 | U32LE | 1 | |
| Segment setpoint 4 | 157 | F32LE | 1 | |
| Segment time 4 | 159 | U32LE | 1 | |
| Segment setpoint 5 | 161 | F32LE | 1 | |
| Segment time 5 | 163 | U32LE | 1 | |
| Segment setpoint 6 | 165 | F32LE | 1 | |
| Segment time 6 | 167 | U32LE | 1 | |
| Segment setpoint 7 | 169 | F32LE | 1 | |
| Segment time 7 | 171 | U32LE | 1 | |
| Segment setpoint 8 | 173 | F32LE | 1 | |
| Segment time 8 | 175 | U32LE | 1 | |
| Control contacts, segment 1 | 177 | U16 | 1 | |
| Control contacts, segment 2 | 178 | U16 | 1 | |
| Control contacts, segment 3 | 179 | U16 | 1 | |
| Control contacts, segment 4 | 180 | U16 | 1 | |
| Control contacts, segment 5 | 181 | U16 | 1 | |
| Control contacts, segment 6 | 182 | U16 | 1 | |
| Control contacts, segment 7 | 183 | U16 | 1 | |
| Control contacts, segment 8 | 184 | U16 | 1 | |
| Alarm text (1-2) | 185 | U16 | 1 | |
| Alarm text (3-4) | 186 | U16 | 1 | |
| Parameter set 1: Pb1 | 12288 | F32LE | 1 | |
| Parameter set 1: Pb2 | 12290 | F32LE | 1 | |
| Parameter set 1: dt | 12292 | U16 | 1 | |
| Parameter set 1: rt | 12293 | U16 | 1 | |
| Parameter set 1: Cy1 | 12294 | F32LE | 1 | |
| Parameter set 1: Cy2 | 12296 | F32LE | 1 | |
| Parameter set 1: db | 12298 | F32LE | 1 | |
| Parameter set 1: HyS1 | 12300 | F32LE | 1 | |
| Parameter set 1: HyS2 | 12302 | F32LE | 1 | |
| Parameter set 1: tt | 12304 | U16 | 1 | |
| Parameter set 1: y0 | 12305 | U16 | 1 | |
| Parameter set 1: y1 | 12306 | U16 | 1 | |
| Parameter set 1: y2 | 12307 | U16 | 1 | |
| Parameter set 2: Pb1 | 12308 | F32LE | 1 | |
| Parameter set 2: Pb2 | 12310 | F32LE | 1 | |
| Parameter set 2: dt | 12312 | U16 | 1 | |
| Parameter set 2: rt | 12313 | U16 | 1 | |
| Parameter set 2: Cy1 | 12314 | F32LE | 1 | |
| Parameter set 2: Cy2 | 12316 | F32LE | 1 | |
| Parameter set 2: db | 12318 | F32LE | 1 | |
| Parameter set 2: HyS1 | 12320 | F32LE | 1 | |
| Parameter set 2: HyS2 | 12322 | F32LE | 1 | |
| Parameter set 2: tt | 12324 | U16 | 1 | |
| Parameter set 2: y0 | 12325 | U16 | 1 | |
| Parameter set 2: y1 | 12326 | U16 | 1 | |
| Parameter set 2: y2 | 12327 | U16 | 1 | |
| Setpoint W1 | 12544 | F32LE | 1 | |
| Setpoint W2 | 12546 | F32LE | 1 | |
| Setpoint W3 | 12548 | F32LE | 1 | |
| Setpoint W4 | 12550 | F32LE | 1 | |
| Setpoint | 12800 | F32LE | 1 | |
| Process value | 12802 | F32LE | 1 | |
| Option slot 1+2 | 16384 | U16 | 1 | |
| Option slot 3 | 16385 | U16 | 1 | |
| Device format | 16393 | U16 | 1 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.