device library

jumo-jdicon-400-500-process-controller-needs-rs422-485-option

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

structure-verified

Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.

pointaddress (0-based)typescaleunit
Generator/source status4096U161
System status4097U161
reserved4098F32LE1
reserved4100F32LE1
reserved4102F32LE1
reserved4104F32LE1
reserved4106F32LE1
Output 1 - 64108U161
Outputs ER84109U161
Logic inputs 1 - 84110U161
reserved4111U161
reserved4112U161
reserved4113U161
reserved4114U161
reserved4115U161
reserved4116U161
reserved4117U161
Limit comparator4118U161
Logic module4119U161
Analogue input 14120F32LE1
Analogue input 24122F32LE1
Analogue input 34124F32LE1
Analogue input 44126F32LE1
Mathematics 14128F32LE1
Mathematics 24130F32LE1
Ramp value (W)4132F32LE1
Process value filtered4134F32LE1
Process value unfiltered4136F32LE1
Setpoint4138F32LE1
Output -100 to 100% (display value)4140F32LE1%
Output heating 0 to +100%4142F32LE1%
Output cooling -100 to 0%4144F32LE1%
Control difference4146F32LE1
Control deviation4148F32LE1
Switch position heating4150U161
Switch position cooling4151U161
Parameter set number (1 - 2)4152U161
Program number (1 - 10)4153U161
Segment number (1 - 99)4154U161
Last segment4155U161
Tolerance band signal4156U161
No. of unused segments4157U161
Generator/source setpoint4158F32LE1
Operating contacts4160U161
reserved4161U161
Controller/limit comparator function active4162U161
Program run-time4163U32LE1s
Remaining program run-time4165U32LE1s
Program time4167U32LE1s
Segment run-time4169U32LE1s
Remaining segment run-time4171U32LE1s
Segment time4173U32LE1s
Sampling time4175F32LE1
Internal Pt1004177F32LE1
Setpoint W14179F32LE1
Setpoint W24181F32LE1
Setpoint W34183F32LE1
Setpoint W44185F32LE1
Manual output4187F32LE1
Parameter set 1: Controller structure 14199U161
Parameter set 1: Controller structure 24200U161
Parameter set 1: XP14201F32LE1
Parameter set 1: XP24203F32LE1
Parameter set 1: TV14205F32LE1
Parameter set 1: TV24207F32LE1
Parameter set 1: TN14209F32LE1
Parameter set 1: TN24211F32LE1
Parameter set 1: CY14213F32LE1
Parameter set 1: CY24215F32LE1
Parameter set 1: XSH4217F32LE1
Parameter set 1: XD14219F32LE1
Parameter set 1: XD24221F32LE1
Parameter set 1: TT4223F32LE1
Parameter set 1: Y04225F32LE1
Parameter set 1: Y14227F32LE1
Parameter set 1: Y24229F32LE1
Parameter set 1: TK14231F32LE1
Parameter set 1: TK24233F32LE1
Parameter set 2: Controller structure 14235U161
Parameter set 2: Controller structure 24236U161
Parameter set 2: XP14237F32LE1
Parameter set 2: XP24239F32LE1
Parameter set 2: TV14241F32LE1
Parameter set 2: TV24243F32LE1
Parameter set 2: TN14245F32LE1
Parameter set 2: TN24247F32LE1
Parameter set 2: CY14249F32LE1
Parameter set 2: CY24251F32LE1
Parameter set 2: XSH4253F32LE1
Parameter set 2: XD14255F32LE1
Parameter set 2: XD24257F32LE1
Parameter set 2: TT4259F32LE1
Parameter set 2: Y04261F32LE1
Parameter set 2: Y14263F32LE1
Parameter set 2: Y24265F32LE1
Parameter set 2: TK14267F32LE1
Parameter set 2: TK24269F32LE1
Controller type4271U161
Control direction4272U161
Output 1 for self-optimisation4273U161
Output 2 for self-optimisation4274U161
Dead band4275F32LE1
FC14277F32LE1
FC24279F32LE1
Controller input: Process value4281U161
Controller input: External setpoint4282U161
Controller input: External setpoint with correction4283U161
Controller input: Output retransmission4284U161
Controller input: Additive disturbance4285U161
Controller input: Multiplying disturbance4286U161
Manual output4287F32LE1
Inhibit manual operation4289U161
Inhibit setpoint optimisation4290U161
Setpoint start4291F32LE1
Setpoint end4293F32LE1
Action4295U161
Function on overrange/underrange4296U161
LK1: Function4297U161
LK1: Switching differential4298F32LE1
LK1: Limit value4300F32LE1
LK1: Switch-on delay4302U161
LK1: Pulse function4303U161
LK1: Limit comparator: Process value4304U161
LK1: Limit comparator: Setpoint4305U161
LK2: Function4306U161
LK2: Switching differential4307F32LE1
LK2: Limit value4309F32LE1
LK2: Switch-on delay4311U161
LK2: Pulse function4312U161
LK2: Limit comparator: Process value4313U161
LK2: Limit comparator: Setpoint4314U161
LK3: Function4315U161
LK3: Switching differential4316F32LE1
LK3: Limit value4318F32LE1
LK3: Switch-on delay4320U161
LK3: Pulse function4321U161
LK3: Limit comparator: Process value4322U161
LK3: Limit comparator: Setpoint4323U161
LK4: Function4324U161
LK4: Switching differential4325F32LE1
LK4: Limit value4327F32LE1
LK4: Switch-on delay4329U161
LK4: Pulse function4330U161
LK4: Limit comparator: Process value4331U161
LK4: Limit comparator: Setpoint4332U161
LK5: Function4333U161
LK5: Switching differential4334F32LE1
LK5: Limit value4336F32LE1
LK5: Switch-on delay4338U161
LK5: Pulse function4339U161
LK5: Limit comparator: Process value4340U161
LK5: Limit comparator: Setpoint4341U161
LK6: Function4342U161
LK6: Switching differential4343F32LE1
LK6: Limit value4345F32LE1
LK6: Switch-on delay4347U161
LK6: Pulse function4348U161
LK6: Limit comparator: Process value4349U161
LK6: Limit comparator: Setpoint4350U161
LK7: Function4351U161
LK7: Switching differential4352F32LE1
LK7: Limit value4354F32LE1
LK7: Switch-on delay4356U161
LK7: Pulse function4357U161
LK7: Limit comparator: Process value4358U161
LK7: Limit comparator: Setpoint4359U161
LK8: Function4360U161
LK8: Switching differential4361F32LE1
LK8: Limit value4363F32LE1
LK8: Switch-on delay4365U161
LK8: Pulse function4366U161
LK8: Limit comparator: Process value4367U161
LK8: Limit comparator: Setpoint4368U161
E1: Transducer4369U161
E1: Linearisation4370U161
E1: Constant cold-junction temperature4371U161
E1: Heater current monitoring4372U161
E1: External cold-junction temperature4373F32LE1
E1: Display start4375F32LE1
E1: Display end4377F32LE1
E1: Range start4379F32LE1
E1: Range end4381F32LE1
E1: Measurement correction4383F32LE1
E1: Filter time constant4385F32LE1
E2: Transducer4387U161
E2: Linearisation4388U161
E2: Constant cold-junction temperature4389U161
E2: Heater current monitoring4390U161
E2: External cold-junction temperature4391F32LE1
E2: Display start4393F32LE1
E2: Display end4395F32LE1
E2: Range start4397F32LE1
E2: Range end4399F32LE1
E2: Measurement correction4401F32LE1
E2: Filter time constant4403F32LE1
E3: Transducer4405U161
E3: Linearisation4406U161
E3: Constant cold-junction temperature4407U161
E3: Heater current monitoring4408U161
E3: External cold-junction temperature4409F32LE1
E3: Display start4411F32LE1
E3: Display end4413F32LE1
E3: Range start4415F32LE1
E3: Range end4417F32LE1
E3: Measurement correction4419F32LE1
E3: Filter time constant4421F32LE1
E4: Transducer4423U161
E4: Linearisation4424U161
E4: Constant cold-junction temperature4425U161
E4: Heater current monitoring4426U161
E4: External cold-junction temperature4427F32LE1
E4: Display start4429F32LE1
E4: Display end4431F32LE1
E4: Range start4433F32LE1
E4: Range end4435F32LE1
E4: Measurement correction4437F32LE1
E4: Filter time constant4439F32LE1
Supply frequency4441U161
Unit4442U161
A1: Output signal for analogue output4443U161
A1: Zero point4444F32LE1
A1: End value4446F32LE1
A1: Output signal for overrange/underrange4448U161
A1: Function4449U161
A2: Output signal for analogue output4450U161
A2: Zero point4451F32LE1
A2: End value4453F32LE1
A2: Output signal for overrange/underrange4455U161
A2: Function4456U161
A3: Output signal for analogue output4457U161
A3: Zero point4458F32LE1
A3: End value4460F32LE1
A3: Output signal for overrange/underrange4462U161
A3: Function4463U161
A4: Output signal for analogue output4464U161
A4: Zero point4465F32LE1
A4: End value4467F32LE1
A4: Output signal for overrange/underrange4469U161
A4: Function4470U161
A5: Output signal for analogue output4471U161
A5: Zero point4472F32LE1
A5: End value4474F32LE1
A5: Output signal for overrange/underrange4476U161
A5: Function4477U161
A6: Output signal for analogue output4478U161
A6: Zero point4479F32LE1
A6: End value4481F32LE1
A6: Output signal for overrange/underrange4483U161
A6: Function4484U161
Function4485U161
Ramp slope4486F32LE1
Unit for ramp slope4488U161
Function4489U161
Restart after power failure4490U161
Program start4491U161
Setpoint provision4492U161
Time/gradient programming4493U161
Program stop on overrange/underrange4494U161
Function control: Controller4495U161
Function control: LK14496U161
Function control: LK24497U161
Function control: LK34498U161
Function control: LK44499U161
Function control: LK54500U161
Function control: LK64501U161
Function control: LK74502U161
Function control: LK84503U161
Process value deviation4504U161
Program end time4505U161
reserved4506U161
reserved4507U161
Setpoint4508F32LE1
Operating contacts (1= ON)4510U161
Parameter set (0 = Parameter set 1)4511U161
Function Limit comparator/controller (1 = active)4512U161
reserved4513U161
reserved4514U161
Setpoint4515F32LE1
Operating contacts (1 = ON)4517U161
Parameter set (0 = Parameter set 1)4518U161
Function Limit comparator/controller (1= active)4519U161
reserved4520U161
reserved4521U161
Setpoint4522F32LE1
Operating contacts (1 = ON)4524U161
Parameter set (0 = Parameter set 1)4525U161
Function Limit comparator/controller (1 = active)4526U161
Mathematics1: Function4527U161
Logic 1: Function4528U161
Mathematics 1: Linearisation4529U161
Mathematics 1: Range start4530F32LE1
Mathematics 1: Range end4532F32LE1
Mathematics 1: Variable a4534U161
Mathematics 1: Variable b4535U161
Mathematics 2: Function4536U161
Logic 2: Function4537U161
Mathematics 2: Linearisation4538U161
Mathematics 2: Range start4539F32LE1
Mathematics 2: Range end4541F32LE1
Mathematics 2: Variable a4543U161
Mathematics 2: Variable b4544U161
Configuration 1/ display 1: Display value4545U161
Configuration 1/ display 1: Decimal point4546U161
Configuration 1/ display 2: Display value4547U161
Configuration 1/ display 2: Decimal point4548U161
Configuration 1/ display 3: Display value4549U161
Configuration 1/ display 3: Decimal point4550U161
Configuration 2/ display 1: Display value4551U161
Configuration 2/ display 1: Decimal point4552U161
Configuration 2/ display 2: Display value4553U161
Configuration 2/ display 2: Decimal point4554U161
Configuration 2/ display 3: Display value4555U161
Configuration 2/ display 3: Decimal point4556U161
Configuration 1: Text display4557U161
Configuration 2: Text display4558U161
Brightness of matrix display4559U161
Automatic display switching4560U161
Time-out4561U161
Function (1 = active)4562U161
Logic input 14563U161
Logic input 24564U161
Logic input 34565U161
Logic input 44566U161
Logic input 54567U161
Logic input 64568U161
Logic input 74569U161
Logic input 84570U161
Limit comparator 14571U161
Limit comparator 24572U161
Limit comparator 34573U161
Limit comparator 44574U161
Limit comparator 54575U161
Limit comparator 64576U161
Limit comparator 74577U161
Limit comparator 84578U161
Logic 14579U161
Logic 24580U161
Operating contact 14581U161
Operating contact 24582U161
Operating contact 34583U161
Operating contact 44584U161
Operating contact 54585U161
Operating contact 64586U161
Operating contact 74587U161
Operating contact 84588U161
Tolerance band signal4589U161
Program end signal4590U161
Protocol type4619U161
Parity4620U161
Stop bit4621U161
Baud rate4622U161
Instrument address4623U161
Minimum response time4624U161
Program buffer4637U161
Program number4638U161
Delay time in seconds4639U32LE1s
Start time in seconds4641U32LE1s
Start day (0 = Sunday)4643U161
Start segment (1-100 or 0 = program start)4644U161
Start segment, remaining run-time in seconds4645U32LE1s
Program buffer4647U161
Setpoint4648F32LE1
Operating contacts (1 = ON)4650U161
Parameter set (0 = Parameter set 1)4651U161
Polling4652U161
Fieldbus function4653U161
Fieldbus error4654U161
Program number4655U161
reserved4656U161
Segment number (1-100)4657U161
Max. no. of segments4658U161
Segment setpoint4659F32LE1
Operating contacts (1 = ON)4661U161
Minimum (lower) limit of the tolerance band4662F32LE1
Maximum (upper) limit of the tolerance band4664F32LE1
Segment time4666U32LE1
Repeat cycles4668U161
Target segment4669U161
Parameter set number (0 = Parameter set 1)4670U161
Command value 14671U161
Command value 24672U161
Command value 34673U161
Commands for text display4674U32LE1
Setpoint switching4676U161
Parameter set switching4677U161
Process value switching4678U161
Program selection4679U161
Setpoint in RAM4680F32LE1
Process value in RAM4682F32LE1
Format (case)4684U161
Analogue input 34685U161
Analogue input 44686U161
Output 14687U161
Output 24688U161
Output 34689U161
Output 44690U161
Output 54691U161
Output 64692U161
Setup4693U161
Interface4694U161
reserved4695U161
ER84696U161
Data buffering4697U161
Input 1 10V4698U161
Input 2 10V4699U161
Input 3 10V4700U161
Input 4 10V4701U161
Relay 1 (K5): Function4761U161
Relay 1 (K5): Function for overrange/underrange4762U161
Relay 2 (K6): Function4763U161
Relay 2 (K6): Function for overrange/underrange4764U161
Relay 3 (K7): Function4765U161
Relay 3 (K7): Function for overrange/underrange4766U161
Relay 4 (K8): Function4767U161
Relay 4 (K8): Function for overrange/underrange4768U161
Relay 5 (K9): Function4769U161
Relay 5 (K9): Function for overrange/underrange4770U161
Relay 6 (K10): Function4771U161
Relay 6 (K10): Function for overrange/underrange4772U161
Relay 7 (K11): Function4773U161
Relay 7 (K11): Function for overrange/underrange4774U161
Relay 8 (K12): Function4775U161
Relay 8 (K12): Function for overrange/underrange4776U161
Function Limit comparator/controller (1 = active)4810U161
Hours8192U161
Minutes8193U161
Seconds8194U161
Day8195U161
Month8196U161
Year8197U161
Weekday8198U161

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.