Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| mdb_prot_cfg | 24320 | U16 | 1 | |
| mdb_slave_addr_op | 24321 | U16 | 1 | |
| mdb_map_start_addr_rd | 24322 | U16 | 1 | |
| mdb_map_start_addr_wr | 24323 | U16 | 1 | |
| mdb_map_nr_rd | 24324 | U16 | 1 | |
| mdb_map_nr_wr | 24325 | U16 | 1 | |
| watchdog_inhibit | 24326 | U16 | 1 | |
| watchdog_activation | 24327 | U16 | 1 | |
| mdb_command | 24369 | U16 | 1 | |
| mdb_mapping_rd_0 | 24370 | U32BE | 1 | |
| mdb_mapping_wr_0 | 24470 | U32BE | 1 |
| terminals | SUBD9 (Female) connector X6C |
| A/B polarity | Pin 4: RS485_RxD(A), Pin 5: RS485_RxD(B), Pin 8: RS485_TxD(A), Pin 9: RS485_TxD(B) |
| connector | SUBD9 Female |
| shield/ground | Pin 7: GND (Reference potential of the serial interface) |
| wiring notes | Supports RS232 or alternatively RS485 transmission standard. |
| max registers/read | 100 |
| broadcast | supported |
| protocol notes | At KEB functions 3 and 4 are completely identical. Two additional user-defined ModBus functions are supported: 100 (Read Registers32) and 101 (Write Registers32). |
| identification notes | Operator Type (0180h) and Software date (0182h) are only available via COMBIVIS / diagnosis interface, not via Modbus. |
| FC 43 device ID | not supported |
| power | VCC on Pin 6 of SUBD9 connector. Red LED (ERROR) is constantly off if there is no power supply. |
| doc revision | 12/2003 (CM.F5.010-K000) |
⚠ disputed: Framing ["RTU", "ASCII"] — disputed by KEB Combicom ModBus Manual Section 3, which states that ModBus ASCII protocol is 'not yet adjustable' (not supported in the firmware)
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.