device library

Krohne IFC300 flow converter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
flow_speed30000F32BE1m/s
volume_flow30002F32BE1m3/s
mass_flow30004F32BE1kg/s
coil_temperature30006F32BE1K
conductivity30008F32BE1S/m
diagnosis_value30010F32BE1
display_channel_130012F32BE1
display_channel_230014F32BE1
operating_time30016F32BE1s

link settings as documented (unverified): RTU; default 19200 8E1; unit ID 1; FC 01,03,04,05,08,16; Transmission delay range 0..40ms (default 0ms). Data format Big Endian (default) or Little Endian.

bench facts as documented (unverified)
terminalsD- (Signal A / D0), D (Signal B / D1), C- (Common 0 V), C (Not connected)
A/B polarityD- is Signal A, D is Signal B
termination120 Ohm / 560 Ohm termination/polarization resistors activated by jumpers X5/X6
connectorTerminals A and B of the converter are dependent on options selected at order
isolationRS485, galvanically isolated
shield/groundScreened twisted pair cable
wiring notesMaximum 1.2 km / 3937 ft without repeater
max registers/read125
broadcastsupported
protocol notesAddress 0 is reserved for broadcast
identification notesSupports Modbus Device Identification (FC43/14) with objects VendorName, ProductCode, MajorMinorRevision, Vendor URL, ProductName, ModelName, UserApplicationName
FC 43 device IDsupported
doc revisionAD Modbus IFC 300 R02 en
firmware applicabilityER 3.2.xx (SW.REV. 3.2x)
field reports — community-sourced, unverified (checked 2026-06-11)
  • RS-485 polarity naming mismatch: The IFC 300 labels D- as Signal A (D0) and D as Signal B (D1). When integrating with other devices (e.g., Eaton Elpro 415U-2), the lines must be crossed (A to D- and B to D) to establish communication. [source]
  • Double Float (LREAL) Support: Cumulative counters (Counter 1, Counter 2, Counter 3) are only available as 64-bit double-precision floats (LREAL / double float), which are not supported by some older PLCs (e.g., Oven PLC100) and require custom parsing or truncation. [source]
  • confirmed: Transmission delay range 0..40ms (default 0ms). Data format Big Endian (default) or Little Endian. — confirmed by Krohne Modbus Interface Guide for IFC 300 (AD Modbus IFC 300 R02 en) [4.4.1]
  • confirmed: Baud rates [1200, 2400, 3600, 4800, 9600, 19200, 38400, 57600, 115200] with default 19200 — confirmed by Krohne Modbus Interface Guide for IFC 300 (AD Modbus IFC 300 R02 en)
  • confirmed: Default unit ID is 1 — confirmed by Krohne Modbus Interface Guide for IFC 300 (AD Modbus IFC 300 R02 en)
  • confirmed: Parity is E (Even) and Stop bits is 1 — confirmed by Krohne Modbus Interface Guide for IFC 300 (AD Modbus IFC 300 R02 en)
  • confirmed: Function codes [1, 3, 4, 5, 8, 16] are supported — confirmed by Krohne Modbus Interface Guide for IFC 300 (AD Modbus IFC 300 R02 en)
  • confirmed: Supports Modbus Device Identification (FC43/14) with objects VendorName, ProductCode, MajorMinorRevision, Vendor URL, ProductName, ModelName, UserApplicationName — confirmed by Krohne Modbus Interface Guide for IFC 300 (AD Modbus IFC 300 R02 en)
  • confirmed: Terminals: D- (Signal A / D0), D (Signal B / D1), C- (Common 0 V), C (Not connected) — confirmed by Krohne Modbus Interface Guide for IFC 300 (AD Modbus IFC 300 R02 en)
  • confirmed: Termination: 120 Ohm / 560 Ohm termination/polarization resistors activated by jumpers X5/X6 — confirmed by Krohne Modbus Interface Guide for IFC 300 (AD Modbus IFC 300 R02 en)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.