Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
output_frequency1000I160.1
actual_current1030U160.1
motor_voltage1060U161
dc_bus_voltage1050U161
heatsink_temperature1171I160.1
error_code1500U161

link settings as documented (unverified): RTU/TCP; For Modbus RTU, the baud rate and parity are detected automatically when DIP switches are in the OFF position. Otherwise, node address and baud rate can be set via DIP switches or parameters P510.01 and P510.02.

⚠ Improper installation of the safety engineering system can cause an uncontrolled starting action of the drives. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsSpring terminal, pluggable
terminationDIP switch 'R' to ON at the first and last physical node
connectorX216
wiring notesMax. cable cross-section: 2.5 mm², Stripping length: 10 mm, Required tool: 0.4 x 2.5 screwdriver
power0.25 ... 132 kW, 1-phase 120 V (90 V ... 132 V, 45 Hz ... 65 Hz), 1-phase 230/240 V, 3-phase 230/240 V, 3-phase 400 V, 3-phase 480 V
certificationsLow-Voltage Directive 2014/35/EU, EN IEC 61800-5-1, UL 61800-5-1, CAN/CSA C22.2 No.274, EMC Directive 2014/30/EU, EN IEC 61800-3
doc revision01/2023 · EN
field reports — community-sourced, unverified (checked 2026-06-11)
  • Users attempting to integrate the Lenze i550 via Modbus RTU often encounter communication failures (such as warning code W81a2 'Modbus: incorrect request by master' or exception code 8602) due to address offset confusion. The device requires a -1 offset from the documented register number when using native Modbus PDU addressing. [source]
  • confirmed: For Modbus RTU, the baud rate and parity are detected automatically when DIP switches are in the OFF position. Otherwise, node address and baud rate can be set via DIP switches or parameters P510.01 and P510.02. — confirmed by Lenze i550 Cabinet Frequency Inverter User Guide
  • confirmed: Connector X216, spring terminal, pluggable, max cable cross-section 2.5 mm², stripping length 10 mm, required tool 0.4 x 2.5 screwdriver, termination DIP switch 'R' to ON — confirmed by Lenze i550 Cabinet Frequency Inverter User Guide
  • confirmed: Power range 0.25 ... 132 kW, 1-phase 120 V, 1-phase 230/240 V, 3-phase 230/240 V, 3-phase 400 V, 3-phase 480 V — confirmed by Lenze i550 Cabinet Frequency Inverter User Guide
  • confirmed: Register map: output_frequency @ 1000, actual_current @ 1030, motor_voltage @ 1060, dc_bus_voltage @ 1050, heatsink_temperature @ 1171, error_code @ 1500 — confirmed by Lenze parameter-to-Modbus mapping formula: Register = (Parameter * 10) + Subindex (e.g., P100.00 = 1000, P117.01 = 1171)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.