Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
L1 Phase Voltage1U32BE0.01V
L2 Phase Voltage3U32BE0.01V
L3 Phase Voltage5U32BE0.01V
L1 Current7U32BE0.0001A
L2 Current9U32BE0.0001A
L3 Current11U32BE0.0001A
L1-L2 Voltage13U32BE0.01V
L2-L3 Voltage15U32BE0.01V
L3-L1 Voltage17U32BE0.01V
L1 Active Power19I32BE0.01W
L2 Active Power21I32BE0.01W
L3 Active Power23I32BE0.01W
L1 Reactive Power25I32BE0.01Var
L2 Reactive Power27I32BE0.01Var
L3 Reactive Power29I32BE0.01Var
L1 Apparent Power31U32BE0.01VA
L2 Apparent Power33U32BE0.01VA
L3 Apparent Power35U32BE0.01VA
L1 Power Factor37I32BE0.0001
L2 Power Factor39I32BE0.0001
L3 Power Factor41I32BE0.0001
L1 CosPhi43I32BE0.0001
L2 CosPhi45I32BE0.0001
L3 CosPhi47I32BE0.0001
Frequency49U32BE0.001Hz
Eqv. Phase Voltage51U32BE0.01V
Eqv. Phase-To-Phase Voltage53U32BE0.01V
Eqv. Current55U32BE0.0001A
Eqv. Active Power57I32BE0.01W
Eqv. Reactive Power59I32BE0.01Var
Eqv. Apparent Power61U32BE0.01VA
Eqv Power Factor63I32BE0.0001
Phase-Phase Voltage Asymmetriy65U32BE0.01%
Phase-Neural Voltage Asymmetriy67U32BE0.01%
L1 Voltage Thd83U32BE0.01%
L1 Current Thd89U32BE0.01%
Neutral-Earth Voltage105U32BE0.01V
Neutral Current107U32BE0.0001A
KW L1-2111U32BE0.01W
L1 Phase Voltage (HI)1023U32BE0.01V
L1 Phase Voltage (LO)1535U32BE0.01V
L1 Phase Voltage (AV)2047U32BE0.01V
L1 Phase Voltage (MD)2559U32BE0.01V
2. Harmonic L1 Voltage3071U32BE0.1%
Analog Input 13919U32BE0.01
Analog Output 13935U32BE0.001
DIPS COUNTER6143U32BE1
Total imp. Active Energy6687U32BE0.01kWh
Total exported Active Energy6689U32BE0.01kWh
Total imp. Reactive Energy6691U32BE0.01kvarh
Total exp. Reactive Energy6693U32BE0.01kvarh
Total Apparent Energy6695U32BE0.01kVAh
Partial imp. Active Energy6697U32BE0.01kWh
Partial exp. Active Energy6699U32BE0.01kWh
Total imp. Active Energy (4 words)6943U64BE0.01kWh
Total exported Active Energy (4 words)6947U64BE0.01kWh
Total imp. Reactive Energy (4 words)6951U64BE0.01kvarh
Total exp. Reactive Energy (4 words)6955U64BE0.01kvarh
Total Apparent Energy (4 words)6959U64BE0.01kVAh
Counter 17423U32BE1Nr
Total Hour meter7679U32BE1s
Partial Hour meter7681U32BE1s
Phase sequence8307U161
OR of all Inputs8447U161
Input 18448U161
OR of all Outputs8463U161
Output 18464U161
EVENTS POINTER8655U161
EVENTS COUNTER8656U161
STOP/START LOGGER8690U161
RESET FLASH8691U161
RTC Year10479U161
RTC Month10480U161
RTC Day10481U161
RTC Hour10482U161
RTC Minutes10483U161
RTC Seconds10484U161
System reboot / Save to flash memory12032U161
Command Register12271U161
2. Harmonic L1 Voltage12543U160.1%
ACTUAL WEEK ENERGY QUALITY13279U160.1%
CT primary (DMG300/700/800/900) / Menu number selection (DMG110/6xx)20479U161
Submenu number selection (DMG110/6xx)20480U161
CT secondary (DMG300/700/800/900) / Parameter number selection (DMG110/6xx)20481U161
Rated voltage (DMG300/700/800/900) / Parameter value (DMG110/6xx)20483U32BE1V
Language20607U161
Enable passwords20735U161
Integration mode20863U161
Hour counters enable20991U161
Trend graph measure21119U161

link settings as documented (unverified): RTU/ASCII/TCP; default 9600 8N1; unit ID 1; FC 03,04,06,07,16,17,23; Supports Modbus RTU and ASCII on RS-485, and Modbus TCP on expansion modules.

bench facts as documented (unverified)
max registers/read80
identification notesFunction 17 (Report Slave ID) returns device type (e.g., AAh for DMG700), software revision, hardware revision, and parameter revision.
FC 43 device IDnot supported
doc revisionDoc. I317IGB02_22.doc

⚠ disputed: total_imported_active_energy @ 6688 — disputed by Lovato Modbus Protocol document I317 I GB 02_22 which lists Total Imported Active Energy at address 1A20H (6688 in decimal) but the actual register address is 1A20H (6688 decimal) while the document lists 6944 decimal in some third-party software maps. However, 1A20H is exactly 6688 decimal, so the address is correct but the other energy registers are offset: total_exported_active_energy is at 1A22H (6690 decimal), total_imported_reactive_energy is at 1A24H (6692 decimal), total_exported_reactive_energy is at 1A26H (6694 decimal), and total_apparent_energy is at 1A28H (6696 decimal).

field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Doc. I317IGB02_22.doc — confirmed by Lovato Modbus Protocol document I317 I GB 02_22
  • confirmed: Function 17 (Report Slave ID) returns AAh for DMG700 — confirmed by Lovato Modbus Protocol document I317 I GB 02_22
  • confirmed: Max read registers is 80 — confirmed by Lovato Modbus Protocol document I317 I GB 02_22
  • confirmed: Baud rates [1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200] — confirmed by Lovato Modbus Protocol document I317 I GB 02_22
  • confirmed: Default baud rate is 9600 — confirmed by Lovato Modbus Protocol document I317 I GB 02_22
  • confirmed: Default unit ID is 1 — confirmed by Lovato Modbus Protocol document I317 I GB 02_22
  • confirmed: l1_phase_voltage @ 2, l2_phase_voltage @ 4, l3_phase_voltage @ 6, l1_current @ 8, l2_current @ 10, l3_current @ 12 — confirmed by AGG Software Lovato Modbus Register Map and Lovato Modbus Protocol document I317 I GB 02_22

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.