device library

LS Electric M100 drive

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Inverter model0U161
Inverter capacity1U161
Inverter input voltage2U161
Version3U161
Parameter setting4U161
Command Frequency5U160.01Hz
Operation command (Advanced)6U161
Acceleration time7U160.1sec
Deceleration time8U160.1sec
Current9U160.1A
Output frequency10U160.01Hz
Output voltage11U161V
DC Link voltage12U161V
Output power13U160.1kW
Operation status14U161
Fault trip information-A15U161
Input terminal information16U161
Output terminal information17U161
V118U161
V219U161
I20U161
RPM21U161
Unit display26U161
Number of poles27U161
Custom Version28U161
Fault trip information-B29U161
PID Feedback30U160.1%
Read address registration 1256U161
Read address registration 2257U161
Read address registration 3258U161
Read address registration 4259U161
Read address registration 5260U161
Read address registration 6261U161
Read address registration 7262U161
Read address registration 8263U161
Write address registration 1264U161
Write address registration 2265U161
Write address registration 3266U161
Write address registration 4267U161
Write address registration 5268U161
Write address registration 6269U161
Write address registration 7270U161
Write address registration 8271U161

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 03,04,06,16; RS-485 half duplex system. Supports up to 16 connected inverters.

bench facts as documented (unverified)
terminalsRJ45 connector (pin 1: S+, pin 8: S-, pin 7: SG)
A/B polaritypin 1: S+, pin 8: S-
terminationTerminating resistor selection switch (SW3)
connectorRJ45
isolationinsulated power source from the inverter's power circuit
shield/groundSG (pin 7)
model register0x0000
firmware register0x0003
power0.1-2.2kW [200V]
field reports — community-sourced, unverified (checked 2026-06-11)
  • LS Electric documents a known 'Addressing Decrement' issue where an offset of -1 (decrementing the register address by 1) may be required depending on the Modbus master software/PLC configuration. [source]
  • confirmed: comms.baud_rates [1200, 2400, 4800, 9600, 19200, 38400] — confirmed by LS M100 Inverter Operation Manual
  • confirmed: comms.default_baud 9600 — confirmed by LS M100 Inverter Operation Manual (CM03 default is 3: 9600 bps)
  • confirmed: comms.default_unit_id 1 — confirmed by LS M100 Inverter Operation Manual (CM01 default is 1)
  • confirmed: physical.connector RJ45 — confirmed by LS M100 Inverter Operation Manual
  • confirmed: physical.polarity pin 1: S+, pin 8: S- — confirmed by LS M100 Inverter Operation Manual
  • confirmed: physical.shield_ground SG (pin 7) — confirmed by LS M100 Inverter Operation Manual
  • confirmed: physical.termination Terminating resistor selection switch (SW3) — confirmed by LS M100 Inverter Operation Manual
  • confirmed: register_map (inverter_model @ 0, version @ 3, command_frequency @ 5, operation_command @ 6, current @ 9, output_frequency @ 10, fault_trip_information_b @ 29, pid_feedback @ 30) — confirmed by LS M100 Inverter Operation Manual

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.