Mastervolt MasterBus-Modbus interface

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
idal_idb_hi0U161
idb_lo1U161
tab_nr2U161
index3U161
value4F32LE1

link settings as documented (unverified): RTU; default 19200 8E?; unit ID 1; FC 23; Uses Modbus function 23 (0x17) Read/Write Multiple Registers Protocol to bridge to MasterBus.

bench facts as documented (unverified)
terminalsScrew terminal
A/B polarityB line, A line, Ground
terminationMasterBus Terminating device included
connectorScrew terminal
wiring notesDin rail mounting: Yes, Din rail 30 mm [1.2 inch]
max registers/read6
response timeout3000 ms
protocol notesOnly supports Modbus function code 23 (0x17). Read Starting Address must be 0, Quantity to Read must be 6, Quantity to Write must be 6.
power350 mW
environmentProtection degree: IP 21
certificationsCE, 2004/108/EC (EMC directive), 2011/65/EU (RoHS directive)
doc revisionv 1.4 September 2014

⚠ disputed: Polarity: B line, A line, Ground — disputed by the March 2009 manual version (v1.0) which states '1. Modbus A line, 2. Modbus B line, 3. Modbus Ground' [1.1.2], whereas the September 2014 manual version (v1.4) and physical terminal labels state '1. Modbus B line, 2. Modbus A line, 3. Modbus Ground'.

field reports — community-sourced, unverified (checked 2026-06-11)
  • The MasterBus Modbus Interface uses a highly non-standard Modbus implementation relying exclusively on Function Code 23 (0x17) Read/Write Multiple Registers, making it incompatible out-of-the-box with many standard Modbus drivers and controllers (such as Victron Cerbo GX or standard PLCs) without custom scripting. [source]
  • Integrating the MasterBus Modbus Interface with home automation systems (like Jeedom or Node-RED) requires custom scripting or specialized plugins (e.g., plugin-mymodbus) to handle the non-standard Function Code 23 (0x17) polling and action commands. [source]
  • confirmed: Uses Modbus function 23 (0x17) Read/Write Multiple Registers Protocol to bridge to MasterBus. — confirmed by the MasterBus Modbus Interface User Manual (September 2014) which details the exclusive use of Function Code 23 (0x17) for reading and writing variables [1.2.3].
  • confirmed: Read Starting Address must be 0, Quantity to Read must be 6, Quantity to Write must be 6. — confirmed by the MasterBus Modbus Interface User Manual under the Modbus Exception Codes section (Exception Codes 02 and 03).
  • confirmed: Baud rates [9600, 19200, 115200] with default 19200, default unit ID 1, and Even parity. — confirmed by the configuration specifications in the MasterBus Modbus Interface User Manual.
  • confirmed: Protection degree: IP 21, power consumption 350 mW, and DIN rail mounting. — confirmed by the physical specifications in the MasterBus Modbus Interface User Manual.

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.