Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| Instrument Modbus Address | 0 | U16 | 1 | |
| Humidity Parameter (1 decimal place mode) | 1 | I16 | 0.1 | |
| Ambient Temperature (1 decimal place mode) | 2 | I16 | 0.1 | |
| Status/Fault Indication | 3 | U16 | 1 | |
| Output Configuration | 4 | U16 | 1 | |
| Ambient Temperature (4 decimal place mode) | 7 | I16 | 0.1 | |
| Transmitter Firmware Version | 8 | U16 | 1 | |
| Measurement Range Low | 10 | I16 | 0.1 | |
| Measurement Range High | 11 | I16 | 0.1 | |
| Sensor Batch Number | 15 | U16 | 1 | |
| Sensor Serial Number | 16 | U16 | 1 | |
| Year of Calibration | 17 | U16 | 1 | |
| Month & Day of Calibration | 18 | U16 | 1 | |
| Pressure value for ppmV (barg) | 54 | I16 | 0.1 | |
| Natural Gas Configuration & Precision Select | 78 | U16 | 1 |
⚠ Incorrect wiring of the transmitter may result in permanent damage. — Starkest reads only; we never write a control register.
| terminals | M12 5-way A coded connector or MiniDIN 43650 form C |
| A/B polarity | Modbus A, Modbus B |
| connector | M12 5-pin (A coded) or MiniDIN 43650 form C |
| shield/ground | Pin 5 (Grey) / GND (Blue) directly connects to the metal casing of the transmitter, but not to the transmitter electronics, and is intended for cable screening only. |
| wiring notes | Recommended to use 3-core screened cable. |
| serial register | 16 |
| firmware register | 8 |
| identification notes | Sensor Batch Number is at register 15. |
| power | 12...28 V DC, 23 mA max |
| environment | Operating temperature: -40...+60 °C, Compensated temperature range: -20...+50 °C, Storage temperature: -40...+60 °C, Operating pressure: 45 MPa (450 barg) maximum |
| accuracy | ±2°C dew point |
| certifications | CE, UKCA, UL approved (UL61010-1 & CAN/CSA C22.2 No. 61010-1), ATEX/UKCA: II 1 G Ex ia IIC T4 Ga (-20...+70 °C), IECEx: EX ia IIC T4 Ga (-20...+70 °C), TR CU@ 0Ex ia IICT4 Ga (-20...+70 °C), cQPSus: Class I, Division 1, Groups A B C D, T4 |
| doc revision | 97504 Issue 3.3, March 2022 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.