Mitsubishi Electric A/C via Intesis ME-AC-MBS interface

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
AC unit On/Off0U161
AC unit Mode1U161
AC unit Fan Speed2U161
AC unit Vane Position3U161
AC unit Temperature Setpoint4U161ºC/ºF
AC unit Ambient Temperature5U161ºC/ºF
Window Contact6U161
Device Disablement7U161
IR Remote Command Disablement8U161
AC unit Operation Time9U161hours
AC unit Alarm Status10U161
Error Code11U161
AC Model12U161
Open Window switch-off timeout13U161minutes
Modbus RTU baud-rate14U161
Device's Modbus slave address15U161
Software version50U161

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 0; FC 03,04,06,16; Although function 16 is allowed, the interface does not allow write operations on more than 1 register with the same request, this means that length field should always be 1 when using this function for writes.

bench facts as documented (unverified)
terminalsplug-in terminal block of 2 poles
A/B polarityA B
terminationon-board terminator resistor of 120Ω selectable via DIP-switch P5
connectorplug-in terminal block
isolation1000 VDC isolation voltage, 1000 MΩ isolation resistance
wiring notesDirect connection to the AC indoor unit via CN92 (Mr.Slim) or CN105 (other models).
broadcastsupported
protocol notesWrite operations on more than 1 register with the same request are not allowed.
firmware register50
powerExternal power not required.
environmentOperating Temperature: -40 ... 85ºC, Operating Humidity: <95% RH, non-condensing
doc revisionrev.8
firmware applicabilityv.1.13
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Baud rates [2400, 9600, 19200, 57600] with default 9600, 8N1 framing — confirmed by IntesisBox ME-AC-MBS-1 v.1.13 User Manual (rev.8)
  • confirmed: Function codes 3, 4, 6, 16 supported, but writes with function 16 are restricted to a length of 1 register — confirmed by IntesisBox ME-AC-MBS-1 v.1.13 User Manual (rev.8)
  • confirmed: Direct connection to the AC indoor unit via CN92 or CN105 — confirmed by IntesisBox ME-AC-MBS-1 v.1.13 User Manual (rev.8)
  • confirmed: Register map addresses (ac_unit_on_off @ 0, ac_unit_alarm_status @ 10, error_code @ 11, software_version @ 50) — confirmed by IntesisBox ME-AC-MBS-1 v.1.13 User Manual (rev.8)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.