Mitsubishi FR-E800 drive

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Inverter reset1U161
Parameter clear2U161
All parameter clear3U161
Parameter clear5U161
All parameter clear6U161
Inverter status / control input command (extended)7U161
Inverter status / control input command8U161
Operation mode / inverter setting9U161
Running frequency (RAM value) / Set frequency (RAM value)13U161
Running frequency (EEPROM value) / Set frequency (EEPROM value)14U161
Fault record 1500U161
Fault record 2501U161
Fault record 3502U161
Fault record 4503U161
Fault record 5504U161
Fault record 6505U161
Fault record 7506U161
Fault record 8507U161
Fault record 9508U161
Fault record 10509U161
Terminal 2 frequency setting bias frequency1901U161
Terminal 2 frequency setting gain frequency1902U161
Terminal 4 frequency setting bias frequency1903U161
Terminal 4 frequency setting gain frequency1904U161
Terminal 1 bias frequency (speed)1916U161
Terminal 1 gain frequency (speed)1917U161
Terminal 1 bias command (torque)1918U161
Terminal 1 gain command (torque)1919U161
Terminal 4 bias command (torque)1931U161
Terminal 4 gain command (torque)1932U161
PID display bias coefficient1933U161
PID display gain coefficient1934U161
Terminal 2 frequency setting bias (analog value)2091U161
Terminal 2 frequency setting gain (analog value)2092U161
Terminal 4 frequency setting bias (analog value)2093U161
Terminal 4 frequency setting gain (analog value)2094U161
Terminal 1 bias (speed) (analog value)2106U161
Terminal 1 gain (speed) (analog value)2107U161
Terminal 1 bias (torque) (analog value)2108U161
Terminal 1 gain (torque) (analog value)2109U161
Terminal 4 bias (torque) (analog value)2121U161
Terminal 4 gain (torque) (analog value)2122U161
PID display bias analog value2123U161
PID display gain analog value2124U161
Terminal 2 frequency setting bias (terminal analog value)3901U161
Terminal 2 frequency setting gain (terminal analog value)3902U161
Terminal 4 frequency setting bias (terminal analog value)3903U161
Terminal 4 frequency setting gain (terminal analog value)3904U161
Terminal 1 bias (speed) (terminal analog value)3916U161
Terminal 1 gain (speed) (terminal analog value)3917U161
Terminal 1 bias (torque) (terminal analog value)3918U161
Terminal 1 gain (torque) (terminal analog value)3919U161
Terminal 4 bias (torque) (terminal analog value)3931U161
Terminal 4 gain (torque) (terminal analog value)3932U161
PID display bias analog value (terminal analog value)3933U161
PID display gain analog value (terminal analog value)3934U161
Model (1st and 2nd characters)4000U161
Model (3rd and 4th characters)4001U161
Model (5th and 6th characters)4002U161
Model (7th and 8th characters)4003U161
Model (9th and 10th characters)4004U161
Model (11th and 12th characters)4005U161
Model (13th and 14th characters)4006U161
Model (15th and 16th characters)4007U161
Model (17th and 18th characters)4008U161
Model (19th and 20th characters)4009U161
Capacity (1st and 2nd characters)4010U161
Capacity (3rd and 4th characters)4011U161
Capacity (5th and 6th characters)4012U161

link settings as documented (unverified): RTU/TCP; default 19200 8E1; unit ID 0; FC 03,06,08,16,70; Supports MODBUS RTU and MODBUS/TCP. Station number 0 is for broadcast.

⚠ Always set the communication check time interval before starting operation to prevent hazardous conditions. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsPU connector (RJ-45)
A/B polarityRDA, RDB, SDA, SDB
terminationConnect a 100 Ohm 1/2 W terminating resistor between RDA (pin 3) and RDB (pin 6)
connectorRJ-45
shield/groundSG (pins 1 and 7) connected to terminal 5
wiring notesPins 2 and 8 provide power to the operation panel or parameter unit. Do not use these pins for RS-485 communication.
max registers/read125
response timeout50 ms
broadcastsupported
protocol notesNo response is returned in the case of broadcast communication.
model register44001
identification notesModel name can be read in ASCII code from registers 44001 to 44010.
powerPins 2 and 8 of PU connector provide power to the operation panel or parameter unit.
field reports — community-sourced, unverified (checked 2026-06-11)
  • The FR-E800 contains gaps in holding register allocation at addresses 40011, 40012, and 40013. Attempting continuous block reads across these gaps causes communication failure (e.g., Error Code 7360 on QJ71MB91 module). Workaround: Split block reads into multiple parameter sets (e.g., read 40001-40010 in one block, then 40014-400XX in a second block). [source]
  • confirmed: Baud rates [4800, 9600, 19200, 38400, 57600, 76800, 115200] — confirmed by FR-E800 Instruction Manual (Communication) Pr.118 setting range
  • confirmed: Default baud rate 19200 — confirmed by FR-E800 Instruction Manual (Communication) Pr.118 initial value of 192
  • confirmed: Default unit ID 0 — confirmed by FR-E800 Instruction Manual (Communication) Pr.117 initial value of 0
  • confirmed: Framing [RTU, TCP] — confirmed by FR-E800 Instruction Manual (Communication) which details both MODBUS RTU and MODBUS/TCP protocols
  • confirmed: Function codes [3, 6, 8, 16, 70] — confirmed by FR-E800 Instruction Manual (Communication) which lists H03, H06, H08, H10, and H46 (70 decimal) as supported
  • confirmed: Station number 0 is for broadcast — confirmed by FR-E800 Instruction Manual (Communication) stating that address 0 is broadcast and returns no reply
  • confirmed: Parity 'E' and Stop bits 1 — confirmed by FR-E800 Instruction Manual (Communication) Pr.120 default (Even) and Pr.119 default (1 stop bit)
  • confirmed: Control warning regarding setting communication check time interval — confirmed by FR-E800 Instruction Manual (Communication) safety warnings

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.