Onicon System-10 BTU meter (needs MOD interface card)

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Meter Operating Mode Indicator0U161
Mode Status Indicator1U161
Energy Rate – Btu/Hr2U161Btu/Hr
Energy Rate – kBtu/Hr3U161kBtu/Hr
Energy Rate – MBtu/Hr4U161MBtu/Hr
Energy Rate – kW5U161kW
Energy Rate – kW x 106U161kW x 10
Energy Rate – Tons7U161Tons
Volume Rate – GPM8U161GPM
Volume Rate – GPM x 109U161GPM x 10
Volume Rate – GPH10U161GPH
Volume Rate – MGD11U161MGD
Volume Rate – L/S12U161L/S
Volume Rate – L/M13U161L/M
Volume Rate – L/Hr14U161L/Hr
Volume Rate – M³/Hr15U161M³/Hr
Volume Rate – M³/Hr x 1016U161M³/Hr x 10
Mass Rate – Lb/Hr17U161Lb/Hr
Mass Rate – Lb/Hr x 1018U161Lb/Hr x 10
Mass Rate – kg/Hr19U161kg/Hr
Mass Rate – kg/Hr x 1020U161kg/Hr x 10
Supply Temperature – °F21U160.01°F
Return Temperature – °F22U160.01°F
Supply Temperature – °C23I160.01°C
Return Temperature – °C24I160.01°C
Energy Total Mode 1 - kBtu25U161kBtu
Energy Total Mode 1 - MBtu26U161MBtu
Energy Total Mode 1 – GBtu27U161GBtu
Energy Total Mode 2 – kBtu28U161kBtu
Energy Total Mode 2 – MBtu29U161MBtu
Energy Total Mode 2 – GBtu30U161GBtu
Energy Total Mode 1 – TonHr31U161TonHr
Energy Total Mode 1 – kTonHr32U161kTonHr
Energy Total Mode 2 – TonHr33U161TonHr
Energy Total Mode 2 – kTonHr34U161kTonHr
Energy Total Mode 1 – kWHr35U161kWHr
Energy Total Mode 1 – MWHr36U161MWHr
Energy Total Mode 1 – GWHr37U161GWHr
Energy Total Mode 2 – kWHr38U161kWHr
Energy Total Mode 2 – MWHr39U161MWHr
Energy Total Mode 2 – GWHr40U161GWHr
Volume Total Mode 1 - kGal41U161kGal
Volume Total Mode 1 - MGal42U161MGal
Volume Total Mode 1 – GGal43U161GGal
Volume Total Mode 2 – kGal44U161kGal
Volume Total Mode 2 – MGal45U161MGal
Volume Total Mode 2 – GGal46U161GGal
Volume Total Mode 1 – kLiters47U161kLiters
Volume Total Mode 1 – MLiters48U161MLiters
Volume Total Mode 1 – GLiters49U161GLiters
Volume Total Mode 2 – kLiters50U161kLiters
Volume Total Mode 2 – MLiters51U161MLiters
Volume Total Mode 2 – GLiters52U161GLiters
Volume Total Mode 1 –M³53U161M³
Volume Total Mode 1 – kM³54U161kM³
Volume Total Mode 2 –M³55U161M³
Volume Total Mode 2 – kM³56U161kM³
Mass Total – kLbs57U161kLbs
Mass Total – MLbs58U161MLbs
Mass Total – Kkgs59U161Kkgs
Mass Total – Mkgs60U161Mkgs
Auxiliary Input Total (Di3)61U161
Auxiliary Input Total (x1000)62U161
Zero Mode 1 Energy Total63U161
Zero Mode 1 Volume Total64U161
Zero Mode 2 Energy Total65U161
Zero Mode 2 Volume Total66U161
Zero Auxiliary Input Total (Di3)67U161
Meter Operating Mode Indicator1000U161
Mode Status Indicator1001U161
Energy Rate – Btu/Hr1002F32BE1Btu/Hr
Energy Rate – kW1004F32BE1kW
Energy Rate – Tons1006F32BE1Tons
Volume Rate – GPM1008F32BE1GPM
Volume Rate – GPH1010F32BE1GPH
Volume Rate – MGD1012F32BE1MGD
Volume Rate – L/S1014F32BE1L/S
Volume Rate – L/M1016F32BE1L/M
Volume Rate – L/H1018F32BE1L/H
Volume Rate – M³/Hr1020F32BE1M³/Hr
Mass Rate – Lb/Hr1022F32BE1Lb/Hr
Mass Rate – Kg/Hr1024F32BE1Kg/Hr
Supply Temperature – °F1026F32BE1°F
Return Temperature – °F1028F32BE1°F
Supply Temperature – °C1030F32BE1°C
Return Temperature – °C1032F32BE1°C
Energy Total Mode 1 –Btu1034F32BE1Btu
Energy Total Mode 2 –Btu1036F32BE1Btu
Energy Total Mode 1 – TonHr1038F32BE1TonHr
Energy Total Mode 2 – TonHr1040F32BE1TonHr
Energy Total Mode 1 – kWHr1042F32BE1kWHr
Energy Total Mode 2 – kWHr1044F32BE1kWHr
Volume Total Mode 1 –Gal1046F32BE1Gal
Volume Total Mode 2 –Gal1048F32BE1Gal
Volume Total Mode 1 – Liters1050F32BE1Liters
Volume Total Mode 2 – Liters1052F32BE1Liters
Volume Total Mode 1 – M³1054F32BE1M³
Volume Total Mode 2 – M³1056F32BE1M³
Mass Total –Lbs1058F32BE1Lbs
Mass Total –kg1060F32BE1kg
Auxiliary Input Total (Di3)1062F32BE1
Zero Mode 1 Energy Total1064U161
Zero Mode 1 Volume Total1065U161
Zero Mode 2 Energy Total1066U161
Zero Mode 2 Volume Total1067U161
Zero Auxiliary Input Total (Di3)1068U161
Volume Rate - Ft³/S1070F32BE1Ft³/S
Volume Rate - Ft³/M1072F32BE1Ft³/M
Volume Total Mode 1 – Ft³1078F32BE1Ft³
Volume Total Mode 2 – Ft³1080F32BE1Ft³

link settings as documented (unverified): RTU/TCP; default 9600 8N1; unit ID 17; FC 03,06,16,17; RS485 transceiver is 2-wire, half-duplex. TCP/IP transceiver is 10Base T, 10Mbps, RJ45 connection.

bench facts as documented (unverified)
terminalsTerminal T1 for RS485, Terminal T2 for Aux Pulse Input (Di3)
A/B polarityRS485 network cable connections are polarity sensitive (+ to + and - to -)
terminationJumper selectable 120 Ohm resistor
connectorRJ45 for TCP/IP, screw terminals for RS485
shield/groundIncoming and outgoing RS485 cable shield wires should be connected together, but must not be connected to the Btu meter.
protocol notesResetting totals requires writing a 1 to a register, which takes longer to accomplish than reading registers and can lead to timeout issues.
power24 VAC input
doc revision07-18
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Baud rates [1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200] and default baud 9600 — confirmed by System-10-MOD Network Interface Installation Guide
  • confirmed: Default unit ID 17 (represented as 017) — confirmed by System-10-MOD Network Interface Installation Guide
  • confirmed: Framing RTU and TCP, and supported function codes 3, 6, 16, 17 — confirmed by System-10-MOD Network Interface Installation Guide
  • confirmed: RS485 transceiver is 2-wire half-duplex, and TCP/IP is 10Base T, 10Mbps, RJ45 — confirmed by System-10-MOD Network Interface Installation Guide
  • confirmed: Parity N and Stop bits 1 — confirmed by System-10-MOD Network Interface Installation Guide
  • confirmed: Shield ground wires must be connected together but not to the Btu meter — confirmed by System-10-MOD Network Interface Installation Guide
  • confirmed: Terminal T1 for RS485 and Terminal T2 for Aux Pulse Input (Di3) — confirmed by System-10-MOD Network Interface Installation Guide
  • confirmed: Jumper selectable 120 Ohm termination resistor — confirmed by System-10-MOD Network Interface Installation Guide

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.