Parker AC10 inverter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
output_frequency4096U160.01Hz
output_voltage4097U161V
output_current4098U160.01A
bus_voltage4100U161V
output_torque_percent4102U160.1%
radiator_temperature4103U161°C
pid_given_value4104U160.1
pid_feedback_value4105U160.1
integer_power_value4106U161kW
di_terminal_status4107U161
terminal_output_status4108U161
ai1_value4109U161
ai2_value4110U161
ao1_percent4117U160.01%
current_speed4119U161rpm
accurate_power_value4120U160.1kW

link settings as documented (unverified): RTU/ASCII; default 9600 8N1; unit ID 1; FC 03,06; RS485 Half-duplex communication mode. Daisy chain structure is adopted by 485 Bus-line.

⚠ FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsA+ and B-
A/B polarityA+ positive polarity of differential signal, B- negative polarity of differential signal
terminationTerminal resistance of 120 Ohm will be adopted for terminal of RS485 network
connectorControl terminals
shield/groundNo direct grounding shall be allowed for any point of RS485 network. All the equipment in the network shall be well grounded via their own grounding terminal.
max registers/read9
broadcastsupported
protocol notesAllows to read six function codes and write only one function code.
firmware register0x0105
powerInput terminals of three-phase 400V AC voltage (R/L1 and S/L2 terminals for single-phase)
doc revisionHA502320U001 Issue 1

⚠ disputed: default stop_bits 1 — disputed by HA502320U001 manual parameter F902 default value which is 2 (2 stop bits)

⚠ disputed: default framing RTU — disputed by HA502320U001 manual parameter F901 default value which is 1 (ASCII)

field reports — community-sourced, unverified (checked 2026-06-11)
  • Modbus control commands (start/stop/frequency) are ignored unless parameters F200, F201, and F203 are explicitly configured to Modbus control (value 3 or 10). [source]
  • Writing frequency references directly to parameter F113 (0xF10D) risks wearing out the EEPROM. Users must write to the RAM-only mirror address (0x010D) for continuous speed adjustments. [source]
  • confirmed: baud_rates [1200, 2400, 4800, 9600, 19200, 38400, 57600] — confirmed by HA502320U001 manual parameter F904
  • confirmed: default_baud 9600 — confirmed by HA502320U001 manual parameter F904 default value 3
  • confirmed: default_unit_id 1 — confirmed by HA502320U001 manual parameter F900 default value 1
  • confirmed: max_read_registers 9 — confirmed by HA502320U001 manual Section 12.5.1 (Less than 10 registers once time)
  • confirmed: register map offsets (4096 to 4120) — confirmed by HA502320U001 manual Section 12.6.2 (1000H to 1018H)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.