Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| status_register | 999 | U32BE | 1 | |
| error_flags_1 | 1001 | U32BE | 1 | |
| error_flags_2 | 1003 | U32BE | 1 | |
| warning_flags | 1005 | U32BE | 1 | |
| actual_stroke_rate | 1007 | U16 | 1 | strokes/h |
| actual_stroke_length | 1008 | F32BE | 1 | % |
| maximum_possible_stroke_rate | 1010 | U16 | 1 | strokes/h |
| actual_dosing_rate | 1017 | F32BE | 1 | |
| maximum_possible_dosing_rate | 1019 | F32BE | 1 | |
| actual_operating_mode | 1021 | U16 | 1 | |
| actual_sub_operating_mode | 1022 | U16 | 1 | |
| actual_concentration | 1023 | F32BE | 1 | ppm |
| switch_on_counter | 1025 | U32BE | 1 | |
| total_operating_time | 1027 | U32BE | 1 | h |
| total_stroke_counter | 1029 | U32BE | 1 | strokes |
| deletable_stroke_counter | 1031 | U32BE | 1 | strokes |
| total_metering_quantity_counter | 1033 | F32BE | 1 | l |
| deletable_metering_quantity_counter | 1035 | F32BE | 1 | l |
| remaining_strokes | 1037 | U32BE | 1 | strokes |
| remaining_metering_volume | 1039 | F32BE | 1 | l |
| metering_volume_of_last_stroke | 1041 | F32BE | 1 | |
| medium_system_pressure | 1043 | F32BE | 1 | bar |
| liquid_level_monitoring | 1045 | U16 | 1 | % |
| start_stop_pump | 1199 | U16 | 1 | |
| target_stroke_length | 1200 | F32BE | 1 | % |
| target_stroke_rate | 1202 | U16 | 1 | strokes/h |
| auxiliary_frequency | 1206 | U16 | 1 | strokes/h |
| auxiliary_stroke_length | 1208 | F32BE | 1 | % |
| target_dosing_rate | 1210 | F32BE | 1 | |
| batch_factor | 1212 | U32BE | 1 | strokes/contact |
| metering_volume_per_batch_mode_triggered | 1214 | F32BE | 1 | |
| dosing_time_for_batch | 1216 | U16 | 1 | sec |
| contact_factor | 1218 | U16 | 1 | strokes/contact |
| metering_volume_per_contact_mode_triggered | 1220 | F32BE | 1 | l/contact |
| auxiliary_dosing_rate | 1222 | F32BE | 1 | |
| activate_concentration_mode | 1224 | U16 | 1 | |
| desired_final_concentration | 1225 | F32BE | 1 | ppm |
| operating_mode | 1227 | U16 | 1 | |
| target_operating_mode | 1228 | U16 | 1 | |
| discharge_stroke_metering_type | 1230 | U16 | 1 | |
| suction_stroke_metering_type | 1231 | U16 | 1 | |
| duration_of_priming | 1232 | U16 | 1 | sec |
| pcb_temperature | 2999 | F32BE | 1 | 0.1 K |
| solenoid_current | 3005 | F32BE | 1 | A |
| intermediate_circuit_voltage | 3007 | F32BE | 1 | V |
| average_solenoid_output | 3011 | F32BE | 1 | W |
| fan_speed | 3013 | U16 | 1 | Rotations/second |
| effective_travel_last_stroke | 3014 | F32BE | 1 |
| terminals | Pin 3: blue GND, Pin 4: black A/+, Pin 5: grey B/- |
| A/B polarity | A/+, B/- |
| termination | Active termination (terminating resistor) integrated on the PCB, can be switched on via the metering pump's menu |
| connector | M12 5-pin |
| wiring notes | half-duplex, 2-wire technology, twisted pair cable, max cable length 1200 m, RS-485 (TIA-485-A), differential voltage level ± 5 V |
| max registers/read | 125 |
| protocol notes | Maximum message size for FC03 is 200 bytes at 19,200 baud (100 bytes at 9600, 400 bytes at 38,400). Device monitoring stops the pump if queries from master remain unanswered beyond a certain time. |
| model register | 8 |
| serial register | 3 |
| firmware register | 26 |
| identification notes | Product code is at register 1 (address 0). |
| environment | IP65 degree of protection (if CAN cable is correctly screwed in) |
| doc revision | BA_G_047_12/24_EN |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.