device library

Rayleigh RI-F200 multifunction energy meter

Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.

coherence-checked

Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.

pointaddress (0-based)typescaleunit
Voltage V1-N0F32LE1V
Network Selection1U161
Voltage V2-N2F32LE1V
CT Primary3U161A
Voltage V3-N4F32LE1V
PT Primary5U32LE1V
Average Voltage L-N6F32LE1V
Slave ID7U161
Voltage V1-28F32LE1V
Parity9U161
Voltage V2-310F32LE1V
Backlight OFF11U161sec
Voltage V3-112F32LE1V
Reset kWh13U161
Average Voltage L-L14F32LE1V
Reset kVArh15U161
Current I116F32LE1A
Page Address Sequence17U161
Current I218F32LE1A
Page Address Sequence19U161
Current I320F32LE1A
Page Address Sequence21U161
Average Current22F32LE1A
Page Address Sequence23U161
kW124F32LE1kW
Page Address Sequence25U161
kW226F32LE1kW
Page Address Sequence27U161
kW328F32LE1kW
Page Address Sequence29U161
kVA130F32LE1kVA
Page Address Sequence31U161
kVA232F32LE1kVA
Page Address Sequence33U161
kVA334F32LE1kVA
Demand Interval Duration35U161
kVAr136F32LE1kVAr
Reset Max kW37U161
kVAr238F32LE1kVAr
Reset Max kVAr39U161
kVAr340F32LE1kVAr
Reset Max kVA41U161
Total kW42F32LE1kW
Total kVA44F32LE1kVA
Total kVAr46F32LE1kVAr
PF148F32LE1
PF250F32LE1
PF352F32LE1
Average PF54F32LE1
Page Address Sequence55U161
Frequency56F32LE1Hz
Pulse Duration57U161sec
kWh58F32LE1kWh
Page Address Sequence59U161
kVAh60F32LE1kVAh
kVArh62F32LE1kVArh
kW Max Active Power64F32LE1kW
kW Min Active Power66F32LE1kW
kVAr Max Reactive Power68F32LE1kVAr
kVAr Min Reactive Power70F32LE1kVAr
kVA Max Apparent Power72F32LE1kVA
Neutral Current THD122F32LE1%
THD of Voltage V1N124F32LE1%
THD of Voltage V2N126F32LE1%
THD of Voltage V3N128F32LE1%
THD of Voltage V1-2130F32LE1%
THD of Voltage V2-3132F32LE1%
THD of Voltage V3-1134F32LE1%
THD of Current I1136F32LE1%
THD of Current I2138F32LE1%
THD of Current I3140F32LE1%
Serial No.684U32LE1
Max I1 Demand692F32LE1A
Max I2 Demand694F32LE1A
Max I3 Demand696F32LE1A
Max Average Current Demand698F32LE1A
Phase Sequence Indicator700U32LE1
Existing Max Active Power702F32LE1kW
Existing Min Active Power704F32LE1kW
Existing Max Reactive Power706F32LE1kVAr
Existing Min Reactive Power708F32LE1kVAr
Existing Max Apparent Power710F32LE1kVA
Existing Max I1 Demand712F32LE1A
Existing Max I2 Demand714F32LE1A
Existing Max I3 Demand716F32LE1A
Existing Max Avg. Current Demand718F32LE1A

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 03,04; RTU (LSB first, apply address offset of +1 for Function 3 Holding Registers)

bench facts as documented (unverified)
protocol notesScan Rate: <= 100mS. FLOAT ordering = MSB.LSB (2301) - FLOAT REVERSE WORD.
serial register30684
doc revisionRI-F200-C-COMM V01
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms defaults (baud rate 9600, unit ID 1, parity N, stop bits 1, RTU framing, function codes 3 and 4) — confirmed by RI-F200-C Modbus Registers document (RI-F200-C-COMM V01) [1.1.1]
  • confirmed: serial register address 30684 — confirmed by RI-F200-C Modbus Registers document (RI-F200-C-COMM V01)
  • confirmed: float ordering as FLOAT REVERSE WORD (MSB.LSB / 2301) and scan rate <= 100ms — confirmed by RI-F200-C Modbus Registers document (RI-F200-C-COMM V01)
  • confirmed: register map addresses (e.g., voltage_v1_n @ 0, current_i1 @ 16, total_kw @ 42, kwh @ 58, neutral_current_thd @ 122) — confirmed by RI-F200-C Modbus Registers document (RI-F200-C-COMM V01)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Device not here? Upload its manual and get a checked map back. It's free.

Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.

Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.