Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| outdoor_temp | 1 | I16 | 0.1 | °C |
| heating_primary_supply_temp | 358 | I16 | 0.1 | °C |
| heating_primary_return_temp | 359 | I16 | 0.1 | °C |
| cooling_primary_supply_temp | 360 | I16 | 0.1 | °C |
| cooling_primary_return_temp | 361 | I16 | 0.1 | °C |
| supply_temp_hs1 | 2 | I16 | 0.1 | °C |
| outdoor_compensated_setpoint_supply_temp_hs1 | 3 | I16 | 0.1 | °C |
| room_temp_hs1 | 4 | I16 | 0.1 | °C |
| setpoint_room_temp_hs1 | 17 | I16 | 0.1 | °C |
| return_temp_hs1 | 5 | I16 | 0.1 | °C |
| control_signal_hs1_cv | 153 | I16 | 0.1 | V |
| controller_output_hs1 | 160 | I16 | 0.1 | % |
| supply_temp_hs2 | 6 | I16 | 0.1 | °C |
| outdoor_compensated_setpoint_supply_temp_hs2 | 7 | I16 | 0.1 | °C |
| room_temp_hs2 | 8 | I16 | 0.1 | °C |
| return_temp_hs2 | 9 | I16 | 0.1 | °C |
| control_signal_hs2_cv | 154 | I16 | 0.1 | |
| controller_output_hs2 | 161 | I16 | 0.1 | |
| supply_temp_hs3 | 10 | I16 | 0.1 | °C |
| outdoor_compensated_setpoint_supply_temp_hs3 | 11 | I16 | 0.1 | °C |
| room_temp_hs3 | 12 | I16 | 0.1 | °C |
| return_temp_hs3 | 13 | I16 | 0.1 | °C |
| control_signal_hs3_cv | 155 | I16 | 0.1 | |
| controller_output_hs3 | 162 | I16 | 0.1 | |
| supply_temp_hwc1 | 14 | I16 | 0.1 | °C |
| setpoint_supply_hwc1 | 52 | I16 | 0.1 | |
| control_signal_hw1_cv | 156 | I16 | 0.1 | |
| controller_output_hw1 | 163 | I16 | 0.1 | |
| supply_temp_hwc2 | 15 | I16 | 0.1 | °C |
| setpoint_supply_hwc2 | 53 | I16 | 0.1 | |
| control_signal_hwc2_cv | 157 | I16 | 0.1 | |
| controller_output_hwc2 | 164 | I16 | 0.1 | |
| supply_temp_hp1 | 16 | I16 | 0.1 | °C |
| return_temp_hp1 | 17 | I16 | 0.1 | °C |
| boiler_temp | 18 | I16 | 0.1 | |
| boiler_return_temp | 356 | I16 | 0.1 | |
| boiler_supply_temp | 394 | I16 | 0.1 | |
| difference_pressure | 19 | I16 | 0.1 | |
| wind_speed | 20 | I16 | 0.1 | |
| energy_consumption_mwh | 65 | I16 | 0.1 | |
| water_consumption_m3 | 66 | I16 | 0.1 | |
| power_usage_instant | 27 | I16 | 0.1 | |
| cold_water_1_consumption_m3 | 67 | I16 | 0.1 | |
| cold_water_1_flow | 30 | I16 | 0.1 | |
| cold_water_2_consumption_m3 | 68 | I16 | 0.1 | |
| cold_water_2_flow | 36 | I16 | 0.1 | |
| electric_consumption_mwh | 69 | I16 | 0.1 | |
| leakage_power | 42 | I16 | 0.1 |
| wiring notes | For Modbus, the bottom layer can be RS485, RS422 or RS232. |
| max registers/read | 47 |
| inter-frame delay | 16 ms |
| protocol notes | The Modbus master must wait for a minimum of 3.5 character times (4 ms at 9600 bps) between two messages. When communicating with more than one controller on the same RS485 line, the master must wait for a minimum of 14 character times (16 ms at 9600 bps) between the answer and the first question for the next controller. The controller is limited to 10 fast communications every 30 seconds; other communications will have a delayed answer time of approximately 1 second. |
| doc revision | Revision 14, January 2015 |
| firmware applicability | From version 3.4 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.