Register map(s) for this device, with a note of how far each has been checked. Addresses are 0-based, as on the wire. Scale and byte order are confirmed only at the hardware-verified rung.
Round-trips through a real Modbus stack with no overlapping addresses and a word-order-sensitive codec — the map is internally coherent and wire-decodable. Does NOT prove byte-order or scaling match a real device: the emulator is seeded from the map's own types, so a uniformly wrong byte-order still round-trips. Only hardware-verified confirms byte-order/scale on the wire.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| air_quality_voc_sensor | 0 | I16 | 1 | |
| auto_mode_set_point | 1 | I16 | 1 | |
| confort_heating_set_point | 2 | I16 | 0.1 | |
| eco_heating_set_point | 3 | I16 | 0.1 | |
| confort_cooling_set_point | 4 | I16 | 0.1 | |
| eco_cooling_set_point | 5 | I16 | 0.1 | |
| humidity_set_point | 6 | I16 | 0.1 | |
| outdoor_humidity | 7 | I16 | 0.1 | |
| supply_humidity | 8 | I16 | 0.1 | |
| return_humidity | 9 | I16 | 0.1 | |
| high_pressure_circuit_1 | 11 | I16 | 0.1 | |
| high_pressure_circuit_2 | 12 | I16 | 0.1 | |
| high_pressure_circuit_3 | 13 | I16 | 0.1 | |
| high_pressure_heat_recovery_circuit | 14 | I16 | 0.1 | |
| outdoor_temperature | 15 | I16 | 0.1 | |
| supply_temperature | 16 | I16 | 0.1 | |
| return_ambient_temperature | 18 | I16 | 0.1 | |
| exhaust_fresh_air_damper | 21 | I16 | 1 | |
| air_quality_co2_sensor | 208 | U16 | 1 | |
| number_of_compressors_working | 209 | U16 | 1 | |
| horas_compresor_1_c1 | 210 | U16 | 1 | |
| horas_compresor_1_c2 | 211 | U16 | 1 | |
| horas_compresor_1_c3 | 212 | U16 | 1 | |
| horas_compresor_2_c1 | 213 | U16 | 1 | |
| horas_compresor_2_c2 | 214 | U16 | 1 | |
| horas_compresor_2_c3 | 215 | U16 | 1 | |
| horas_compresor_cr | 216 | U16 | 1 | |
| arranques_compresor_1_c1 | 217 | U16 | 1 | |
| arranques_compresor_1_c2 | 218 | U16 | 1 | |
| arranques_compresor_1_c3 | 219 | U16 | 1 | |
| arranques_compresor_2_c1 | 220 | U16 | 1 | |
| arranques_compresor_2_c2 | 221 | U16 | 1 | |
| arranques_compresor_2_c3 | 222 | U16 | 1 | |
| arranques_compresor_cr | 223 | U16 | 1 | |
| actual_supply_fan_flow_l | 228 | U16 | 1 | |
| actual_supply_fan_flow_h | 229 | U16 | 1 | |
| actual_return_fan_flow_l | 230 | U16 | 1 | |
| actual_return_fan_flow_h | 231 | U16 | 1 |
| power | 230 Vac |
| environment | -10ºC/+60°C |
| doc revision | MR_KCR_1602A_EN_EU |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Device not here? Upload its manual and get a checked map back. It's free.
Want it confirmed against your own device? Order hardware verification. If it doesn't check out, you don't pay.
Building on a lot of devices? License the library — machine-readable maps, the firmware matrix, and API access.